XP Power DPC70US24 Ac-dc power supply Datasheet

DPC70 Series
AC-DC Power Supplies
70 Watts
xxx Series
• Ultra Slim Design
• Ambient Operation from -25 °C to +70 °C
• High Efficiency
• Wide Output Adjustment Range
• 12 V to 48 V Nominal Outputs
• <0.5 W No Load Input Power
• 3 Year Warranty
GREEN
POWER
Dimensions:
DPC70:
3.6 x 1.59 x 3.94” (90.0 x 40.5 x100.0 mm)
Models & Ratings
Output Voltage
12 V
24 V
48 V
Output Power
66 W
72 W
72 W
Output Voltage Trim(2)
11.4-15.6 V
22.5-28.5 V
47.0-52.8 V
Output Current
5.5 A
3.0 A
1.5 A
Typical Efficiency(1)
88%
89%
89%
Notes
1. Typical efficiency at 230 VAC and full load.
2. Output current should be limited so that nominal output power is not exceeded.
Mechanical Details
1.59 (40.5)
3.94 (100.0)
-V -V +V +V
VOUT ADJ.
3.60
(90.0)
ON
DPC70
xppower.com
N
L
Notes
1. All dimensions in inches (mm)
2. Weight: 0.51 lbs (230 g)
3. Tolerance: ±0.02 in (±0.5 mm)
1
4. Screw terminal: 12-26 AWG cables size.
5. Connection screw maximum torque: 5.0 lbs-in (0.56 Nm)
www.xppower.com
Model Number
DPC70US12
DPC70US24
DPC70US48
DPC70 Series
AC-DC Power Supplies
Input
Characteristic
Minimum
Input Voltage - Operating
85
Input Frequency
47
Typical
50/60
Maximum
Units
Notes & Conditions
264
VAC
See input voltage derating curve
63
Hz
Power Factor
Conforms to EN61000-3-2 Class A
Input Current - Full Load
1.45/0.8
Inrush Current
Earth Leakage Current
Input Protection
A
115/230 VAC
30/60
A
At 115/230 VAC
1
mA
0.5
W
At 264 VAC, 60 Hz
T3.15 A / 250 V internal in-line fuse
No Load Input Power
Output
Maximum
Units
Notes & Conditions
Output Voltage - V1
12
48
VDC
See Models and Ratings table
Initial Set Accuracy
0
+1
%
At 100% load
%
See Models and Ratings table, output power rating must
not be exceeded
Characteristic
Minimum
Typical
Output Voltage Adjustment
Minimum Load
0
Capacitive Load
Start Up Delay
Start Up Rise Time
Hold Up Time
A
No minimum load required
3500/1000
µF
12 V & 24 V Output/48 V Output
2.5
s
150
ms
15/50
ms
Line Regulation
±1
%
Load Regulation
±1
%
Transient Response - V1
4
%
100
18.0
32.4
mV pk-pk
16.2
28.8
57.6
62.4
Ripple & Noise
Overvoltage Protection
Overload Protection
At full load and 115 VAC/230 VAC
Recovery within 1% in less than 2 ms
for a 50% step load change at 0.2 A/µs
Measured at 20 MHz bandwidth
12 V model
24 V model
V
48 V model
150
%
Short Circuit Protection
Trip and Restart (Hiccup Mode)
Temperature Coefficient
0.03
%/˚C
General
Characteristic
Minimum
Efficiency
Isolation: Input to Output
Input to Ground
Output to Ground
Switching Frequency
Output LED
Mean Time Between Failure
Weight
Typical
Maximum
87
Units
%
3000
Notes & Conditions
See Models & Ratings table
VAC
1500
VAC
500
VAC
40
100
kHz
Green LED to indicate output on.
kHrs
550
0.51 (230.0)
www.xppower.com
BELLCORE issue 6 at 40 °C, GB
lb (g)
2
DPC70 Series
AC-DC Power Supplies
Environmental
Characteristic
Maximum
Units
Operating Temperature
Minimum
-25
Typical
+70
°C
Storage Temperature
-40
+85
°C
20
95
%RH
5000
m
Cooling
Operating Humidity
Notes & Conditions
See thermal derating curve
Natural convection
Operating Altitude
Non-condensing
Shock
IEC68-2-27, 15 g, 11 ms half sine, 3 times in each of
6 axes
Vibration
IEC68-2-6, 10-500 Hz, 2 g 10 mins/sweep. 60 mins
for each of 3 axes
EMC: Emissions
Phenomenon
Standard
Test Level
Conducted
EN55032
Class B
Radiated
EN55032
Class B
Harmonic Current
EN61000-3-2
Class A
Voltage Fluctuations
EN61000-3-3
Criteria
Notes & Conditions
Criteria
Contact
EMC: Immunity
Phenomenon
Standard
ESD Immunity
EN61000-4-2
Radiated Immunity
EN61000-4-3
Test Level
8 kV
A
15 kV
10 V/m
A
EFT/Burst
EN61000-4-4
4
A
Surges
EN61000-4-5
Installation class 4
A
Conducted
EN61000-4-6
10 V
A
Magnetic Fields
EN61000-4-8
4
EN55024
Air Discharge
A
Dip: 100%, 10 ms
Dips and Interruptions
Notes & Conditions
A
Dip: 30%, 10 ms
A
Dip: 60%, 100 ms
A/B
High Line/Low Line
B
Int: 100%, 5000 ms
Safety Approvals
3
Safety Agency
Safety Standard
Notes & Conditions
UL
UL508
Industrial Control Equipment
cTUVus
UL60950-1
Information Technology
TUV
EN60950-1
Information Technology
www.xppower.com
DPC70 Series
AC-DC Power Supplies
Mechanical Details
1.59 (40.5)
3.94 (100.0)
-V -V +V +V
VOUT ADJ.
3.60
(90.0)
ON
DPC70
xppower.com
N
L
Notes
1. All dimensions in inches (mm)
2. Weight: 0.51 lbs (230 g)
3. Tolerance: ±0.02 in (±0.5 mm)
4. Screw terminal: 12-26 AWG cables size.
5. Connection screw maximum torque: 5.0 lbs-in (0.56 Nm)
Application Notes
Derating Curves
Ambient Temperature
Input Voltage
40 °C Ambient
100
85
50
0
-25
50 °C Ambient
Power Out (%)
Power Out (%)
100
Temperature (°C)
50
70
0
85
www.xppower.com
100
Input Voltage (VAC)
264