Cooper BSPD400208Y2P High capacity type 1 and type 2 spds for overvoltage protection on switchgear and power distribution panel Datasheet

Technical Data 10209
Effective December 2015
Supersedes September 2014
BUSSMANN
SERIES
BSPD surge protective devices
High capacity Type 1 and Type 2 SPDs for overvoltage protection
on switchgear and power distribution panels
Contents
Description
Page
Introduction
2
Applications
2
Features
2
Standards and certifications
2
Configuration
3
Enclosure options, dimensions, and weights
Voltage protection ratings
3
4-5
Specifications
6
Catalog number system
7
Technical support information
7
Technical Data 10209
BSPD SPDs for overvoltage protection on
switchgear and power distribution panels
Effective December 2015
Introduction
Factory sealed to improve electrical safety
The BSPD surge protective devices are tested by Underwriters
Laboratory and Listed to UL® 1449, 3rd Edition to help ensure
equipment is protected with highly reliable surge protection
technology. Delta and Wye system units are available in three
configurations to increase application flexibility. The BSPD
Series is for installation external to an electrical enclosure or
panelboard. Application of BSPD Series units throughout a
facility will help ensure that equipment is protected.
All BSPD units are factory-sealed to eliminate arc flash and
shock hazards, as the user/installer has no chance of coming
into contact with energized parts. The units also contain no
user-serviceable parts or wire lugs that require periodic
retightening to eliminate the need for periodic maintenance.
Applications
BSPD units are available for common Delta and Wye system
voltages in a variety of surge current capacity ratings from
120kA to 400kA. Available in three configurations, the BSPD
Series’ features and options make it easy to specify units
for many electrical applications including service entrances,
distribution switchboards, panelboards and point-of-use. All
possible combinations of product attributes are available for
ordering in the catalog number system (see page 7).
Features
•
BSPD uses Bussmann series SurgePOD™ thermally
protected Metal Oxide Varistor (MOV) technology to safely
shunt overvoltages to ground while its thermal disconnect
capability eliminates the need for additional fusing
BSPD uses Bussmann series SurgePOD modules that each
contain an internal element that safely disconnects upon
reaching an overvoltage breakdown condition.
Prewired
All BSPD units are factory wired for ease of installation. Simply
install any necessary conduit runs, mount the unit and make all
wire connections. No need for internal wiring or access to the
unit’s inside.
Compact size takes less space
Available in enclosures that are up to 50% smaller than other
products with comparable ratings the BSPD Series come in
NEMA® 1 and 4X enclosures that differ in size according to their
surge current capacity (Imax).
NEMA 1 BSPD units.
•
The 120-200kA surge current capacity units are housed in a 74
square-inch enclosure that is only 3-1/2 inches deep.
Models available to meet the overvoltage protection needs
of Wye and Delta electrical systems from 208 to 600 volts,
3-phase
•
The 300-400kA surge current capacity units are housed in a
74 square-inch enclosure that is only 6 inches deep.
BSPD has the highest nominal discharge current (In) of 20kA
per UL 1449 3rd Edition. This rating indicates the SPD’s ability
to handle a number of large-magnitude surges over a short
period of time and remain operational.
•
The 120-200kA surge current capacity units are housed in a
108 square-inch enclosure that is only 5-3/8 inches deep.
•
The 300-400kA surge current capacity units are housed in a
108 square-inch enclosure that is only 7-11/16 inches deep.
•
200kA SCCR meets the highest NEC® requirements
•
•
Bussmann series SurgePOD technology eliminates the need
for additional fusing
•
120kA to 400kA surge current capacity (Imax) ratings meet
the needs of larger switchgear and power distribution panel
applications
•
Optional Form C contact relay, EMI/RFI filtering and surge
counter available to meet additional system requirements.
•
200kA Short-Circuit Current Rating (SCCR)
•
NEMA 1 or NEMA 4X enclosures
•
RoHS compliant
•
10 year warranty
NEMA 4X BSPD units.
Agency information
•
Basic, standard and standard withsurge counter
configurations UL Listed, 1449 3rd Edition, File E316410,
Guide VZCA, CSA® Certified, Notice 516, File 243397
•
Standard and standard with surge counter configurations are
also UL Recognized, 1283 5th Edition, File E316410, Guide
VZCA2, CSA component acceptance, Std. C22.2, No. 8-M1986,
File 243397
BSPD unit mounted externally to a Bussmann series
Quik-Spec™ Coordination Panelboard
2
Eaton.com/bussmannseries
BSPD SPDs for overvoltage protection on
switchgear and power distribution panels
Technical Data 10209
Effective December 2015
Dimensions - in (mm) and weights
Enhanced protection status indicators
Unlike many SPDs that only have single-color indicators, all
BSPD units include green and red Light Emitting Diodes (LEDs)
that indicate the true protection status for each phase.
7.28
(184.9)
5.27
(133.9)
If power is removed from any one phase, the unit’s LEDs
continue to indicate the protection status on that phase —
regardless if power is applied to the phase. This feature ensures
proper indication.
Although many SPDs on the market have N-G surge protection,
they do not always have a means of monitoring and indicating
the protection status of that mode. All BSPD units for Wye
systems also contain green and red LED surge protection status
indicators for the Neutral-to-Ground (N-G) connection. Like the
phase protection status LEDs, the N-G protection status LEDs
show the true protection status in the N-G mode.
By specifying the BSPD, users are supplied with accurate
information concerning the surge protection status of their
electrical systems.
Configurations
10.48
(266.2)
12.05
(306.1)
The BSPD provides users with three configurations. These are:
•
Basic (UL Type 1 - can be installed in UL Type 2 locations)
•
Standard (UL Type 2)
•
Standard with surge counter (UL Type 2)
11.25
(285.8)
0.68
(17.3)
5.24
(133.1)
0.78
(19.8)
1.00
(25.4)
2.00
(50.8)
3.48
(88.4)
4.41
(112.0)
Ø0.20
(Ø5.1)
7.47
(189.7)
0.40
(10.2)
Figure 1. NEMA 1, 120kA-200kA Units,
Weight = 6.8 Lbs (3.1 kg)
5.47
(138.9)
The proper configuration can be selected based on application
requirements or specification.
1.00
(25.4)
Table 1. configuration comparisons
Configuration
Feature
Surge protection using
thermally protected MOV
technology
Green and red LED
protection status
indicators for each phase
Green and red LED
protection status
indicators for the Neutralto-Ground protection
mode (Wye systems only)
Basic
(Type 1)
Standard
(Type 2)
Standard
with
surge counter
(Type 2)
X
X
X
X
X
X
X
Audible alarm with silence
button
X
X
Form C relay contact
X
X
EMI/RFI filtering,
providing up to 50dB of
noise attenuation from
10kHz to 100MHz
X
X
Surge counter with reset
button held in nonvolatile
memory
X
X
12.05
(306.1)
10.48
(266.2)
0.67
(17.0)
5.24
(133.1)
0.78
(19.8)
11.25
(285.8)
2.00
(50.8)
5.76
(146.3)
6.69
(169.9)
Ø0.20
(Ø5.1)
7.47
(189.7)
0.40
(10.2)
Figure 2. NEMA 1, 300kA-400kA Units,
Weight = 13.5 Lbs (6.1 kg)
X
120-200kA
250-400kA
A
2.60 (66.0)
4.10 (104.1)
B
5.39 (137.0)
7.68 (195.0)
Figure 3. NEMA 4X, 120kA-400kA Units,
Weight = 120-200kA; 14.6 Lbs (6.6 kg),
250-400kA; 21.0 Lbs (9.5 kg)
Eaton.com/bussmannseries
3
Technical Data 10209
BSPD SPDs for overvoltage protection on
switchgear and power distribution panels
Effective December 2015
Voltage protection ratings
ANSI/UL 1449 3rd Edition voltage protection ratings
Voltage Protection Rating (VPR) data for all units is included
in the following tables, The data varies based upon the
configuration and NEMA enclosure. VPR values for the Basic
configurations are on the left-hand side of the page. Tables
on the right-hand side contain VPR values for the Standard or
Standard with Surge Counter configurations.
NEMA 1: Basic
(cat. nos. ending with 1K)
NEMA 1: Standard or Standard w/ Surge Counter
(cat. nos. ending with 2K or 3K)
Table 2. 120-200kA
Table 5. 120-200kA
Voltage/
system
code
Protection mode
L-N
L-G
N-G
L-L
Protection mode
L-N
L-G
N-G
L-L
208Y
700
700
700
1200
208Y
600
800
600
1000
480Y
1200
1200
1200
2000
480Y
1200
1200
1200
1800
600Y
1500
1500
1500
2500
600Y
1500
1500
1500
2500
240D
—
1000
—
1000
240D
—
1000
—
1000
480D
—
2000
—
2500
480D
—
2500
—
2500
600D
—
2500
—
2500
600D
—
2500
—
2500
Table 6. 300kA
Table 3. 300kA
Voltage/
system
code
Protection mode
L-N
L-G
N-G
L-L
Voltage/
system
code
Protection mode
L-N
L-G
N-G
L-L
1000
208Y
700
700
700
1000
208Y
600
700
600
480Y
1200
1200
1200
1800
480Y
1000
1200
1000
1800
600Y
1500
1500
1500
2500
600Y
1500
1500
1500
2500
240D
—
1000
—
1000
240D
—
1000
—
1000
—
1800
—
2000
—
2500
—
2500
480D
—
1800
—
2000
480D
600D
—
2500
—
2500
600D
Table 7. 400kA
Table 4. 400kA
4
Voltage/
system
code
Voltage/
system
code
L-N
L-G
N-G
L-L
1000
208Y
600
700
600
1000
Voltage/
system
code
Protection mode
L-N
L-G
N-G
L-L
208Y
700
700
700
Protection mode
480Y
1200
1200
1200
1800
480Y
1000
1200
1000
1800
600Y
1500
1500
1500
2500
600Y
1500
1500
1500
2500
240D
—
1000
—
1000
240D
—
1000
—
1000
480D
—
1800
—
2000
480D
—
1800
—
2000
600D
—
2500
—
2500
600D
—
2500
—
2500
Eaton.com/bussmannseries
BSPD SPDs for overvoltage protection on
switchgear and power distribution panels
Technical Data 10209
Effective December 2015
NEMA 4X: Basic
(cat. nos ending with 1P)
NEMA 4X: Standard or Standard w/ Surge Counter
(cat. nos. ending with 2P or 3P)
Table 8 120–200kA
Table 11. 120–200kA
Voltage/
system
code
Protection mode
L-N
L-G
N-G
L-L
Voltage/
system
code
Protection mode
L-N
L-G
N-G
L-L
208Y
700
800
700
1200
208Y
900
900
700
1500
480Y
1200
1200
1000
2000
480Y
1200
1200
1000
2500
600Y
1500
1500
1500
2500
600Y
1500
1500
1500
2500
240D
—
1000
—
1000
240D
—
1000
—
1000
480D
—
2000
—
2500
480D
—
2500
—
2500
600D
—
2500
—
2500
600D
—
2500
—
2500
L-N
L-G
Table 9. 300kA
Voltage/
system
code
Table 12. 300kA
Protection mode
L-N
L-G
N-G
L-L
Voltage/
system
code
Protection mode
N-G
L-L
208Y
700
800
700
1200
208Y
800
900
700
1500
480Y
1200
1200
1200
2000
480Y
1200
1200
1000
2000
600Y
1500
1500
1500
2500
600Y
1500
1500
1500
2500
240D
—
1000
—
1000
240D
—
1000
—
1000
480D
—
1800
—
2000
480D
—
2000
—
2000
600D
—
2500
—
2500
600D
—
2500
—
2500
Table 10. 400kA
Table 13. 400kA
Voltage/
system
code
Protection mode
Voltage/
system
code
L-N
L-G
N-G
L-L
208Y
700
800
700
Protection mode
L-N
L-G
N-G
L-L
1200
208Y
800
900
700
1500
480Y
1200
1200
1200
2000
480Y
1200
1200
1000
2000
600Y
1500
1500
1500
2500
600Y
1500
1500
1500
2500
240D
—
1000
—
1000
240D
—
1000
—
1000
480D
—
1800
—
2000
480D
—
2000
—
2000
600D
—
2500
—
2500
600D
—
2500
—
2500
Eaton.com/bussmannseries
5
Technical Data 10209
BSPD SPDs for overvoltage protection on
switchgear and power distribution panels
Effective December 2015
5.0 Specifications
Table 14. specifications
Description
Specification
Available system voltages
Three-phase Wye
120/208, 277/480 and 347/600
Three-phase Delta
240, 480 and 600
Input power frequency
50/60Hz
Maximum continuous operating voltage (MCOV)
208Y, and 240D voltage/system type codes
150 L-N,150 L-G, 150 N-G, 300 L-L
480Y Voltage/system type code
320 L-N, 320 L-G, 320 N-G, 640 L-L
600Y Voltage/system type code
420 L-N, 420 L-G, 420 N-G, 840 L-L
480D Voltage/system type code
640 L-G, 640 L-L
600D Voltage/system type code
840 L-G, 840 L-L
Short-Circuit Current Rating (SCCR)
200kA
Nominal discharge current (In)
20kA
Surge current capacity per phase (Imax)
120kA, 200kA, 300kA and 400kA ratings available
SPD Types
Type 1 (Basic configuration, can also be used in Type 2 applications)
Type 2 (Standard and Standard With Surge Counter configurations)
Enclosure types
NEMA 1, NEMA 4X 304 Stainless Steel
Ports
1
SPD Conductor length/gauge
48” (1.22m) 10AWG Stranded copper
Form C contact relay (Standard and standard with surge counter configurations only)
Contact ratings
150Vac or 125Vdc, 1A maximum
Lead length/gauge
48 inches (1.22m) / 14AWG
Contact logic
Power ON, normal state; N.O. contact = Open, N.C. contact = Closed
Power OFF, fault state; N.O. contact = Closed, N.C. contact = Open
Power consumption
Basic configuration
208Y and 240D voltage/system type codes
0.5W
480Y and 480D voltage/system type codes
1.1W
600Y and 600D voltage/system type codes
1.3W
Standard and Standard With Surge Counter configurations
6
208Y and 240D voltage/system type codes
0.6W
480Y, and 480D voltage/system type codes
1.7W
600Y and 600D voltage/system type codes
2.1W
Protection modes
Three-phase Delta; L-G, L-L
Three-phase Wye; L-N, L-G, N-G, L-L
Operating temperature / humidity
-40 to +50°C (-40 to +122°F) / 5% to 95%, non-condensing
Operating altitude - ft (m)
16,000 (5000)
EMI/RFI filtering attenuation
Up to 50dB from 10kHz to 100MHz (standard and standard with surge counter
configurations)
Weight - lbs (kg)
NEMA 1: 120kA-200kA - 6.8 (3.1), 30- 400kA -13.5 (6.1) NEMA 4X: 120-200kA - 14.6
(6.6), 300-400kA - 21.0 (9.5)
Agency information
- Basic, Standard and Standard With Surge Counter configurations UL Listed 1449 3rd
Edition File E316410 Guide VZCA, CSA Certified Notice 516 File 243397
- Standard and Standard With Surge Counter configurations are also UL Recognized
1283 5th Edition File E316410 Guide VZCA2, CSA Component Acceptance Std. C22.2
No. 8-M1986 File 243397
Seismic withstand capability
Meets or exceeds the requirements specific to I.B.C. 2006, C.B.C 2007 and U.B.C zone 4
Warranty
10 Years (see warranty statement 3A1502 for details at www.cooperbussmann.com/
Surge)
Eaton.com/bussmannseries
BSPD SPDs for overvoltage protection on
switchgear and power distribution panels
Technical Data 10209
Effective December 2015
6.0 Catalog Number System
Table 15. BSPD part number system
All possible combinations of the BSPD attributes are available
for ordering.
BSPD 200 480D 2 K
Enclosure rating
Series
BSPD
K = NEMA 1
P = NEMA 4X
kA Rating
per phase
120kA
200kA
300kA
400kA
Voltage/system type code
208Y = 120/208 Wye (4W + G)
480Y = 277/480 Wye (4W + G)
600Y = 347/600 Wye (4W + G)
240D = 240 Delta (3W + G)
480D = 480 Delta (3W + G)
600D = 600 Delta (3W + G)
Configurations
1 = Basic
Green and red LEDs per phase to indicate protection status
Green and red LEDs on Wye units to indicate protection status of the Neutral-to-Ground mode
2 = Standard
Green and red LEDs per phase to indicate protection status
Green and red LEDs on Wye units to indicate protection status of the Neutral-to-Ground mode
Audible alarm with Silence button
Form C contact relay. See Table 3, Specifications
EMI/RFI filtering providing up to 50dB of noise attenuation from 10kHz to 100MHz
3 = Standard With Surge Counter
Green and red LEDs per phase to indicate protection status
Green and red LEDs on Wye units to indicate protection status of the Neutral-to-Ground mode
Audible alarm with silence button
Form C contact relay
EMI/RFI filtering providing up to 50dB of noise attenuation from 10kHz to 100MHz
Surge counter with reset button
Technical support information
If you have any questions or need additional information,
please contact the Eaton’s Bussmann Division
application engineers between the hours of 7:00 am and
5:00 pm central time at 855-287-7626 (855-Bussmann) or by
email, [email protected].
The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this
document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical
information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction of
any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any
technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Bussmann Division
114 Old State Road
Ellisville, MO 63021
United States
Eaton.com/bussmannseries
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. 10209 – BU-SB14678
December 2015
For Eaton’s Bussmann series
product information,
call 1-855-287-7626 or visit:
Eaton.com/bussmannseries
Eaton and Bussmann are valuable
trademarks of Eaton in the US and other
countries. You are not permitted to use the
Eaton trademarks without prior written
consent of Eaton.
CSA is a registered trademark of the
Canadian Standards Group.
UL is a registered trademark of the
Underwriters Laboratories, Inc.
Follow us on social media to get the
latest product and support information.
7
Similar pages