Delta EOE11010160 Cliq din rail power supply 12v 100w 1 phase Datasheet

CliQ Din Rail Power Supply
12V 100W 1 Phase
DRP012V100W1AA
DRP012V100W1AA
100Watts
Total Power: 100Watts
Input Voltage: 85-264Vac
# of Output: Single
Model number
DRP012V100W1AA
EOE11010160
Special Features
Output power
Output voltage range
Output current
Residual ripple/peak switching (20MHz)
(@ nominal values)
Mains buffering at nominal load (typ.)
Line regulation
Load regulation
100W
11-14V
8.33A (100W max.)
< 100mV
•
Reference no.
OUTPUT (DC)
> 22ms @ 115Vac, > 110ms @ 230Vac
< 0.5% typ. (@ 85 - 264Vac input, 100% load)
< 1% Typical (with rated input, 0 to 100% load)
INPUT (AC)
Input voltage range
Input frequency
Nominal current
85 - 264Vac (DC input range 120 - 375Vdc)
47 - 63Hz
2.90A Max ( 2.5A @ 115Vac & 1.5A @ 230Vac)
Efficiency
Power factor
Inrush current limitation I²t (+25°C) typ.
Leakage current
Min 86% @ 115Vac & Min 87.5% @ 230Vac
Conform to EN61000-3-2 STD
< 100A @ 115VAC & No Damage @ 230VAC
< 1mA
•
•
•
•
•
•
•
Ease of multiple wire
connection
Compact design for easy
handling
Overload protection
Thermal protection
Power boost 150% for 3secs
Expected life time: 10 years
Redundancy: Yes
(with external ORing diode)
RoHS compliant
MECHANICAL DESIGN
Case cover
Aluminium (Al5052)
Dimensions (L x W x H)
121mm x 50mm x 118.2mm
Unit weight / box
0.636kg
MTBF
> 300,000 hrs
Noise
Cooling
Sound pressure level (SPL) < 40dBA
Convection
Input terminal
Output terminal
M4 x 3
M4 x 2 QPA-2pcs
Mounting rail
Standard TS35 mounting rail
Shock proof
Vibration
Protection structure
IEC60068-2-27
IEC60068-2-6
EN60950 meet IPX0
3 PET
E315355
R
CliQ Din Rail Power Supply
12V 100W 1 Phase
DRP012V100W1AA
MECHANICAL DRAWING
Delta Electronics (Thailand)
Public Company Limited
909 Moo 4, E.P.Z.,
Bangpoo Industrial Estate,
Tambon Prakasa, Amphur
Muang Samutprakarn,
Samutprakarn 10280, Thailand
Tel: +662 709 2800
Fax: +662 709 2827
E-mail: [email protected]
www.deltaenergysystems.com
SAFETY / ENVIRONMENTAL
EMC / Emissions
Immunity
Safety standard
Voltage dips
Galvanic isolation
EN61000-3-2, 3 : 1995/A1 : 2001/A2 : 2005,
EN55022 : 2006 Class B, EN55011 : 1998/A2 : 2002
Class B, EN6100-6-1 (IEC61000-4-2, 3, 4, 5, 6, 8,11)
EN61000-6-2, EN55024, EN61000-4-2,
IEC61000-4-3, 4, 5, 6, 8, 11
UL Listed for UL508 & CSA 22.2 no.107.1-01,
UL Recognized for UL60950-1 & CSA 22.2 no.60950-1,
UL60950-1 and CSA 22.2 no.107.1-01,
TUV Bavart Mark to EN60950-1, EN50178 : 1998,
IEC60204-1 : 1998 & IEC62103 : 2003,
CB cert from TUV to IEC60950-1,
CE (EMC and Low Voltage directive) ,
CCSAUS to CSA 22.2 no.60950-1
Conforms to EN61000-4-11
Input to output: 4KVac;
Input to ground: 1.5KVac;
Output to ground: 1.5KVac
Operating ambient temperature
Storage temperature
-20°C ~ 75°C *
-25°C ~ 85°C
Operating humidity
Note (*)
< 95%
Operating amb. > 50°C derate power by 2.5% /°C
Similar pages