SMALL FLANGE REMOTE SEAL TYPE PRESSURE TRANSMITTER FKW...5 DATA SHEET The FCX – AIII small flange remote seal type pressure transmitter accurately measures gauge pressure and transmits a proportional 4 to 20mA signal. The transmitter utilizes a unique micromachined capacitance silicon sensor with state-of-the-art microprocessor technology to provide exceptional performance and functionality. Totally welded construction of the seals assures excellent reliability in high temperature and highly corrosive process conditions. FEATURES 1. Directly connectable to 1-1/2in and 2in flanges The transmitter is connectable to 1-1/2in and 2in pipes without a reducer. 2. Connectable to 1/2in and 3/4in pipes Use of direct mounting adapter allows the transmitter to be connected to the following process. 1/2in and 3/4in flanges Screw connection 1/2-14NPT, 3/4-14NPT, Rc1/2, Rc3/4 3. Minimum environmental influence The “Floating Cell” design which protects the pressure sensor against changes in temperature, and overpressure substantially reduces total measurement error in actual field applications. 4. Fuji/HART® bilingual communications protocol FCX – AIII series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®. Any HART® compatible devices can communicate with FCX – AIII. 5. Application flexibility Various options that render the FCX – AIII suitable for almost any process applications include: – Full range of hazardous area approvals – Built-in RFI filter and lightning arrester – 5-digit LCD meter with engineering unit – Stainless steel electronics housing – Wide selection of materials – High temperature, vacuum seals 6. Burnout current flexibility (Under Scale: 3.2 to 4.0mA, Over Scale: 20.0 to 22.5mA) Burnout signal level is adjustable using Model FXW Hand Held Communicator (HHC) to comply with NAMUR NE43. 7. Dry calibration without reference pressure Thanks to the best combination of unique construction of mechanical parts (Sensor unit) and high performance electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as wet calibration. SPECIFICATIONS Functional specifications Service: Liquid, gas, or vapour Span, range, and overrange limit: Span limit [kPa]{bar} Type Min. F KW 2 F KW 3 F KW 4 50 {0.5} 300 {3} 1000 {10} Max. 500 {5} 3000 {30} 10000 {100} Range limit [kPa]{bar} −100 to +500 {−1 to +5} −100 to +3000 {−1 to +30} −100 to 10000 {−1 to 100} Overrange limit [MPa] {bar} 1.5 {15} 4.5 {45} 15 {150} – Lower range limit (vacuum limit) ; Silicone fill sensor: See Fig. 1 Fluorinated fill sensor: Atmospheric pressure – Conversion factors to different units; 1MPa=103kPa=10bar=10.19716kgf/cm2=145.0377psi 1kPa=10mbar=101.9716mmH2O=4.01463inH2O Output signal: 4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal. Power supply: Transmitter operates on 10.5V to 45V DC at transmitter terminals. 10.5V to 32V DC for the units with optional arrester. EDSX5-95h Date Aug. 10, 2011 FKW...5 Load limitations: see figure below Temperature limit: Ambient: −15 to +65°C (−15 to +60°C for arrester option) (−10 to +60°C for fluorinated oil fill transmitter) (−10 to +60°C for silicone oil “H”, “S”) (−15 to + 45°C for capillary length more than 7m) For explosionproof units (flameproof or intrinsic safety), ambient temperature must be within the limits specified by each standard. Process: [Ω] Load resistance 2000 1500 1474Ω R= E-10.5 (Imax+0.9)x10-3 1000 577Ω Operating area 500 24V 250 0 45V Fill fluid 10 16.35 10.5V Power voltage (DC) 50 E[ V ] Fluorinated oil W, A and D Hazardous locations: SEE TABLE2 Zero/span adjustment: Zero and span are adjustable from the HHC(1). Zero and span are also adjustable externally from the adjustment screw. Damping: Adjustable from HHC or local configurator unit with LCD display. The time constant is adjustable between 0.06 to 32 seconds. Zero elevation/suppression: Zero can be elevated or suppressed within the specified range limit of each sensor model. Normal/reverse action: Selectable from HHC(1) Indication: Analog indicator or 5-digit LCD meter, as specified. Burnout direction: Selectable from HHC(1) If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale” or “Output Underscale” modes. “Output Hold”: Output signal is hold as the value just before failure happens. “Output Overscale”: Adjustable within the range 20.0mA to 22.5mA from HHC(1) “Output Underscale”: Adjustable within the range 3.2mA to 4.0mA from HHC(1) 4 20 22.5 [mA] Over scale Burnout Normal operating range Under scale Probable under range Burnout Probable over range Output limits conforming to NAMUR NE43 by order. Loop-check output: Transmitter can be configured to provide constant signal 3.2mA through 22.5mA by HHC(1). Silicone oil −20 to 120°C 0 to 250°C Y and G −40 to 180°C S 0 to 250°C 2 (1) HHC: Hand Held Communicator Atmospheric pressure 2.7kPa abs {20mmHg abs} Storage: −40 to +70°C Humidity limit: 0 to 100% RH Communication: With HHC(1) (Model FXW, consult Data Sheet No. EDS8-47), following items can be remotely displayed or configured. Note: HHC’s version must be higher than 7.0 (or FXW 1– 4), for FCX AIII. Local configurator with LCD display (option): Local confi gurator with 3 push button and LCD display can support following items. Items By communication By local configurator with FXW (with 3 push button) Display Set Display Set Tag No. v v v v Model No. v v v v Serial No. & Software Version v — v — Engineering unit v v v v Range limit v — v — Measuring range v v v v Damping v v v v Output mode v — v — Burnout direction v v v v Calibration v v v v Output adjust — v — v Data v — v — Self diagnoses v — v — Printer (In case of FXW with printer option) v — — — External switch lock v v v v Transmitter display v v v v Linearize v v — — Rerange v v v v Saturate current v v v v Write protect v v v v History – Calibration history – Ambient temperature history v v v — v v v — EMC Conformity: EN61326-1: 2006 (Note) Lower limit of static press. Process temperature H Note: For communication with HHC (Model: FXW), min. of 250 is required. 3.2 13th digit of “Code symbols” Performance specifications Physical specifications Reference conditions, silicone oil fill, SS316 isolating diaphragms, 4 to 20mA analog output in linear mode and capillary length 3m. Accuracy rating: (including linearity, hysteresis, and repeatability) (Standard) For spans greater than 1/10 of URL: ±0.25% of span For spans below 1/10 of URL: x ± 0.17+0.08 0.1 URL % of span Span (Option) (Code; 21th digit H) For spans greater than 1/10 of URL: ±0.1% of span For spans below 1/10 of URL: x ± 0.05+0.05 0.1 URL % of span Span ( ) ( ) Stability: ±0.2% of upper range limit (URL) for 10 years. Temperature effect: Effect per 28°C change between the limits of −15°C and +65°C Zero shift: ±0.5%/28°C (x equal to 1/6.5 URL or more) URL Zero shift; ± (0.5 )%/28°C 6.5 x x (x less than 1/6.5 URL) Total shift; ±0.75%/28°C (x less than 1/6.5 URL or more) URL Total shift; ±(0.25 + 0.5 )%/28°C 6.5 x x (x less than 1/6.5 URL) Where, x: Calibrated span URL: Maximum span (Upper Range Limit) Note : Above specifications are based on the conditions that flange and sensor unit are at the same temperature and in the same level. If temperature is different at flange, capillary or sensor unit, output variation may increase. Overrange effect: Zero shift; 0.2% of URL/(1.5 x URL) Supply voltage effect: Less than 0.005% of calibrated span per 1V Update rate: 60 msec Step response: Time constant: 0.3s (at 23°C) Dead time: 0.12s (without electrical damping) Dielectric strength: 500V AC, 50/60Hz 1 min., between circuit and earth. Insulation resistance: More than 100M/500V DC. Internal resistance for external field indicator: 12 or less Electrical connections: G1/2, 1/2-14 NPT, Pg13.5, or M20 x 1.5 conduit, as specified. Process connections: JIS; 10K, 20K, 30K, 63K −40, 50A 10K, 20K, 30K, 63K −15, 20A (with Adapter) ANSI/JPI; 150LB, 300LB, 600LB, −1 1/2", 2" 150LB, 300LB, 600LB, −1/2", 3/4" (with Adapter) Screw connection (with Adapter) ; Rc1/2, Rc3/4, 1/2-14NPT, 3/4-14NPT Diaphragm extension: 0, 50, 100, 150, or 200mm as specified. (See model code. Extended diaphragm is available only with 316L stainless steel diaphragm) Process-wetted parts material: Diaphragm: 316L stainless steel, Hastelloy-C Monel or Tantalum Flange face: 316 stainless steel, Hastelloy-C lining, Monel lining or Tantalum lining Extension: 316 stainless steel (Refer to “Code symbols”) Non-wetted parts material: Electronics housing: Low copper die-cast aluminum alloy finished with polyester coating (standard), or 316 stainless steel (ASTM CF8M), as specified. Capillary: In case of 11th code “D. E. L”, PE armored stainless steel. In case of 11th code “Q. R. S”, stainless steel armored stainless steel. Mounting flange: 304 stainless steel or carbon steel, as specified. Fill fluid: Silicone oil (standard) or fluorinated oil Mounting bracket: 304 stainless steel. Environmental protection: IEC IP67 and NEMA 6/6P Mounting: On 60.5mm (JIS 50A) pipe using mounting bracket, direct wall mounting Mass {weight}: Transmitter approximately 8.2 to 11.2kg without options. Add; 0.5kg for mounting bracket 4.5kg for stainless steel housing option 1.5kg per 50mm extension of diaphragm 3 FKW...5 Optional features ACCESSORIES Indicator: A plug-in analog indicator (2.5% accuracy) An optional 5-digit LCD meter with engineering unit is also available. Local configurator with LCD display: An optional 5 digits LCD meter with 3 push buttons can support items as using communication with FXW. Arrester: A built-in arrester protects the electronics from lightning surges. Lightning surge immunity: 4kV (1.2 × 50µs). Oxygen service: Special cleaning procedures are followed throughout the process to maintain all process wetted parts oil-free. The fill fluid is fluorinated oil. Chlorine service: Oil-free procedures as above. Includes fluorinated oil for fill. Degreasing: Process-wetted parts are cleaned, but the fill fluid is standard silicone oil. Not for use on oxygen or chlorine measurement. Vacuum and high temperature service: Special silicone oil and filling procedure are applied. See Fig.1. Optional tag plate: An extra stainless steel tag for customer tag data is wired to the transmitter. Coating of cell: Cell's surface is finished with epoxy/polyurethane double coating. Specify if environment is extremely corrosive. Filled liquid: Silicone (Code Y,G) [kPa abs] {m bar abs} Silicone (Code S) Operating pressure 101 {1010} 53.3 {533} Operating area 13.3 {133} Non-operating area 2.7 {27} −40 0 60 85 120 180 Process temperature 230 250 [°C ] Fig. 1 Relation between process temperature and operating pressure 4 Hand-held communicator: (Model FXW, refer to Data Sheet No. EDS8-47) CODE SYMBOLS 1 2 3 4 5 6 7 8 Digit 4 Description Note <Conduit connection> Conduit connection Case type G1/2 T type 1/2-14NPT T type Pg13.5 T type M20×1.5 T type G1/2 L type 1/2-14NPT L type Pg13.5 L type M20×1.5 L type 5 <Flange> Material Size and rating 304 stainless JIS 10K 40A steel JIS 10K 50A JIS 20K 40A JIS 20K 50A JIS 30K 40A JIS 30K 50A JIS 63K 40A JIS 63K 50A ANSI/JPI 150LB 1 1/2" ANSI/JPI 150LB 2" ANSI/JPI 300LB 1 1/2" ANSI/JPI 300LB 2" ANSI/JPI 600LB 1 1/2" ANSI/JPI 600LB 2" Carbon steel JIS 10K 40A JIS 10K 50A JIS 20K 40A JIS 20K 50A JIS 30K 40A JIS 30K 50A JIS 63K 40A JIS 63K 50A ANSI/JPI 150LB 1 1/2" ANSI/JPI 150LB 2" ANSI/JPI 300LB 1 1/2" ANSI/JPI 300LB 2" ANSI/JPI 600LB 1 1/2" ANSI/JPI 600LB 2" None 40A, 1 1/2B (Wafer type) 50A, 2B Note 1 Direct mounting adapter connection (* 1) 6 <Span limit [kPa] {bar} > 50.......500 ( 0.5...5) 300.....3000 ( 3...30) 1000...10000 (10...100) 7 <Material/diapharagm extension> Diaphragm Diaphragm extension (mm) Flange face 316L stainless steel 316 stainless steel 0 Note 2 316L stainless steel 316 stainless steel 50 316L stainless steel 316 stainless steel 100 (* 2) 316L stainless steel 316 stainless steel 150 316L stainless steel 316 stainless steel 200 316L stainless steel 316 stainless steel 0 +Au coating Hastelloy-C 0 Hastelloy-C Hastelloy-C 0 316 stainless steel Monel 0 Monel Tantalum 0 Tantalum Note1: (*1) Direct mounting adapter type is specified at 16th to 20th digit. Direct mounting adapter is available only for 7th digit code "V". Note2: (*2) Diaphragm extension is available only for 2" (50A) flanges. F KW 5 9 10 11 12 13 14 15 16 17 18 19 20 0 21 Digit No. of code 5 6 7 8 S T V W 0 1 2 3 4 5 6 7 A B C D E F G H J K L M N P Q R S T U V W X Y 2 3 4 V A B C D J H W M T 5 FKW...5 1 2 3 4 5 6 7 8 Digit 9 10 11 12 13 14 15 Description <Indicator and arrester> Indicator Arrester None None Analog, 0 to 100% linear scale None Analog, custom scale None None Yes Analog, 0 to 100% linear scale Yes Analog, custom scale Yes Digital, 0 to 100% linear scale None Digital, custom scale None Digital, 0 to 100% linear scale Yes Digital, custom scale Yes Digital, 0 to 100% linear scale (Local configurator unit with LCD display) None Digital, custom scale (Local configurator unit with LCD display) None Digital, 0 to 100% linear scale (Local configurator unit with LCD display) Yes Digital, custom scale (Local configurator unit with LCD display) Yes <Approvals for hazardous locations> None (for ordinary locations) TIIS, Flameproof (Cable gland seal) (*7) TIIS, Intrinsic safety FM, Flameproof (or explosionproof) (*10) FM, Intrinsic safety and nonincentive FM Combined of flameproof and intrinsic safety (*10) ATEX Flameproof (*9) ATEX Intrinsic safety ATEX Type n ATEX Combined of flameproof and intrinsic safety (*9) IECEx Scheme, Flameproof (*9) IECEx Scheme, Intrinsic safety CSA, Flameproof (or explosionproof) (*10) CSA, Intrinsic safety and nonincentive NEPSI, Flameproof (or exprosionproof) NEPSI, Intrinsic safety NEPSI, Combined of flameproof and intrinsic safety <Capillary and mounting bracket> Mounting bracket Capillary Armor of Capillary Stainless steel 1.5m PE Stainless steel 3m PE Stainless steel 5m PE (*5) Stainless steel 6m PE Stainless steel 7m PE Stainless steel 8m PE Stainless steel 10m PE Stainless steel 1.5m Stainless steel Stainless steel 3m Stainless steel Stainless steel 5m Stainless steel Stainless steel 6m Stainless steel Stainless steel 7m Stainless steel Stainless steel 8m Stainless steel Stainless steel 10m Stainless steel <Options> Stainless steel elec. housing Coating of cell Extra SS tag plate None None None Yes None None None (*3) None Yes Yes None Yes None Yes Yes (*6) Yes Yes Yes <Special applications and fill fluid> Treatment Fill fluid Standard Silicone oil Standard Fluorinated oil Degreasing Silicone oil Fluorinated oil (7th digit code "V", "W", "A", "B", "C" and "D") Oxygen service Chlorine service Fluorinated oil (7th digit code "H" and "T") High temp. 250°C Silicone oil (7th digit code "V", "W", "A", "B", "C", "D" and "H") High temp. and vacuum (250°C) Silicone oil (7th digit code "V", "W", "A", "B", "C" and "D") <Teflon membrane> None Yes (Available for 7th digit code "V", "J", "W. Not available for 5th digit code "Y" and 13th digit code "H", "S".) <Bolt/nut> (*4) None 6th digit code "2", "3" Cr-Mo alloy hexagon socket head cap bolt/ carbon steel nut 6th digit code "4" Cr-Mo alloy hexagon bolt/carbon steel nut 304 stainless steel bolt/304 stainless steel nut 316 stainless steel bolt/316 stainless steel nut Note3: (*3) Note4: (*4) Note5: (*5) Note6: (*6) 6 Note F KW 9 10 11 12 13 14 15 16 17 18 19 20 5 21 Digit No. of code A B D E F H L P Q S 1 2 4 5 A C G D H V X K P M R T E J F S U Note 7 Note 10 Note 10 Note 9 Note 9 Note 9 Note 10 D E L F M N P Q R S T V W X Note 5 Y B M N P Q Note 3 Note 6 Note 6 Y W G A D H S Note 11 Note 11 Y C Note 4 Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select "Yes". In case of tropical use, select stainless bolts and nuts. Available for 13th digit code "Y, W, G, A, D". Not available for 10th digit code "C". Y A B E U Note7: Note9: Note10: Note11: (*7) (*9) (*10) (*11) Available for 4th digit code "S". Available for 4th digit code "6", "8", "T", "W". Available for 4th digit code "6", "T". Treatment: Standard. Specifications of connecting pipeless adapter {for 15, 20A (1/2, 3/4") connection} and others Note 1. When odering the instrument with connecting pipeless adapter, specify “Y” in the 5th digit of Code Symbol, and specify 16th digit to 20th digit. When odering the instrument without connecting pipeless adapter, nothing should be filled in the 16th to 20th digit. 2. Unless otherwise described in the specifications, leave the 21st digit blank. 1 2 3 4 5 6 7 8 Digit Description Note 16, 17 <Process connection (connecting pipeless adapter)> JIS 10K 15A JIS 10K 20A JIS 20K 15A JIS 20K 20A JIS 30K 15A JIS 30K 20A JIS 63K 15A JIS 63K 20A ANSI/JPI 150LB 1/2" ANSI/JPI 150LB 3/4" ANSI/JPI 300LB 1/2" ANSI/JPI 300LB 3/4" ANSI/JPI 600LB 1/2" ANSI/JPI 600LB 3/4" Screw connection Rc1/2 Screw connection Rc3/4 Screw connection Rc1/2 - 14NPT Screw connection Rc3/4 - 14NPT 18 <Material (connecting pipeless adapter)> Note 12 Adapter Bolts/nuts (* 12) 316 Stainless Steel Cr-Mo steel/carbon steel 19 <Vent/drain (for connecting pipeless adapter)> Standard Long type 20 <Gasket (for connecting pipeless adapter)> Standard (Teflon)(Only Y, W, G, A and D can be specified on 13th digit). For high temperature (spiral gasket) (Only H and S can be specified on 13th digit). Note 13 21 <Other options> (* 13) High accuracy type Instruction manual attached Instruction manual unattached High accuracy type Instruction manual unattached F KW 9 10 11 12 13 14 15 16 17 18 19 20 21 5 Digit No. of code 1 1 1 2 2 1 2 2 3 1 3 2 6 1 6 2 1H 1T 2H 2T 4H 4T SR S2 SN ST W A N 1 2 H L T Note12: (* 12) For connection of transmitter receiving pressure unit and connecting pipeless adapter Note13: (* 13) In other option is not necessary, 21st digit code is blank. In case of 21st digit code is blank, instruction manual attached. 7 FKW...5 ORDERING INFOMATION When ordering this instrument, specify. 1. CODE SYMBOLS 2. Measuring range. 3. Output orientation (burnout direction) when abnormality is occurred in the transmitter. Hold / Overscale / Underscale Unless otherwise specified, output hold function is supplied. 4. Indication method (indicated value and unit) in case of the actual scale (code D, H, P, S 2,5 on 9th digit). 5. Tag No. (up to 14 alphanumerical characters), if required. 8 OUTLINE DIAGRAM (Unit:mm) <AMP. case: L type> IN CASE OF 4TH DIGIT CODE “S, V, W” ZERO ADJ. SCREW φ81 8 IN CASE OF 4TH DIGIT CODE “T” 103 φ81 103 10 MTG. PIPE JIS 50A (2B) 38 57 “B” CONDUIT CONN. 37 U-BOLT M8 172 (21) WITH ANALOG IND. (11) 4 HOLES 9 DIA. WITH DIGITAL IND. N HOLES h DIA φ E P φ48±1 φF φ49 φD INNER OF GASKET FLANGE 20 L t 163 DETAIL “B” (CONDUIT. CONN.) 126 41 φ15 J S (m) 1.5 3 5 6 7 8 10 EARTH TERMINAL 198 K M 11th digit of the code symbols D, Q E, R L, S F, T M, V N, W P, X 43 SEE TABLE1 conduit conn. J K M 7th digit of the code symbols L V, W, J, H, M, T A B C D 0 50 100 150 200 S G1/2 18 2 T 1/2-14NPT 16 4 V Pg13.5 W M20×1.5 10.5 4.5 2-M8×12 S 4 TABLE 1 φD φE 0, G 1, H 2, J 3, K 4, L 5, M 6, N 7, P A, Q B, R C, S D, T E, U F, V 140 155 140 155 160 165 175 185 127 152 156 165 156 165 105 120 105 120 120 130 130 145 95.4 120.6 114.3 127 114.3 127 CorrosionStandard resistant materials specification materials specification Note 1 Note 2 73 84 100 84 73 84 100 84 73 84 100 84 73 84 100 84 73 84 100 84 73 84 100 84 73 84 100 84 t P N-φh FLANGE 36 36 38 38 42 42 52 54 37.5 39.5 41 42.5 42.5 45.5 60 71 60 71 60 71 60 71 60 71 60 71 60 71 4-19 4-19 4-19 8-19 4-23 8-19 4-25 8-23 4-16 4-20 4-23 8-20 4-23 8-20 JIS-10K-40A JIS-10K-50A JIS-20K-40A JIS-20K-50A JIS-30K-40A JIS-30K-50A JIS-63K-40A JIS-63K-50A ANSI/JPI-150LB-1 1/2B ANSI/JPI-150LB-2B ANSI/JPI-300LB-1 1/2B ANSI/JPI-300LB-2B ANSI/JPI-600LB-1 1/2B ANSI/JPI-600LB-2B Note1) In case of the 7th digit of type code is V, A, B, C, D, J or W. Note2) In case of the 7th digit of type code is H, M, T. CONNECTION DIAGRAM <SS TAG PLATE> 2-M6 SCREW DEPTH 9 INNER OF GASKET φF 5th digit of the code symbols H.P. 62 70 120 φF Q 16 MASS. APPROX. (kg) 8.2 9.2 10.2 10.7 11.2 φ49 4th digit of the code symbols 20 <WAFER TYPE> 40A, 1 1/2B 50A, 2B OPTION PARTS FOR FLAMEPROOF OF TIIS (JAPAN) 10th digit code C (Cable gland type) NOTE1) G1/2 DETAIL “C” φ33.5 φ13 −/CK− CK+ 75 19 106 20 17 + Q 60 71 "C" CONDUIT CONN. G1/2 CABLE GLAND NOTE1) IN CASE OF 10TH CODE C , φ11 CABLE IS SUITBLE. 9 FKW...5 <AMP. case: T type> IN CASE OF 4TH DIGIT CODE “5, 7, 8” IN CASE OF 4TH DIGIT CODE “6” EARTH TERMINAL 8 10 MTG. PIPE JIS 50A (2B) φ81 100 100 38 57 φ81 ZERO ADJ. SCREW (21) 37 WITH ANALOG IND. (11) U-BOLT M8 185 4 HOLES 9 DIA. WITH DIGITAL IND. “B” CONDUIT CONN. P φ48±1 φF φ49 φD φ E N HOLES h DIA INNER OF GASKET FLANGE 20 L 185 t 127 20 DETAIL “B” (CONDUIT. CONN.) φ15 K J S (m) 226 M 11th digit of the code symbols D, Q E, R L, S F, T M, V N, W P, X 1.5 3 5 6 7 8 10 SEE TABLE1 7th digit of the code symbols L V, W, J, H, M, T A B C D 0 50 100 150 200 5 G1/2 18 2 6 1/2-14NPT 16 4 7 Pg13.5 8 M20×1.5 10.5 4.5 16 MASS. APPROX. (kg) 8.2 9.2 10.2 10.7 11.2 2-M8×12 S H.P. 62 70 120 4 TABLE 1 φD φE 0, G 1, H 2, J 3, K 4, L 5, M 6, N 7, P A, Q B, R C, S D, T E, U F, V 140 155 140 155 160 165 175 185 127 152 156 165 156 165 105 120 105 120 120 130 130 145 95.4 120.6 114.3 127 114.3 127 φF CorrosionStandard resistant materials specification materials specification Note 1 Note 2 73 84 100 84 73 84 100 84 73 84 100 84 73 84 100 84 73 84 100 84 73 84 100 84 73 84 100 84 t P N-φh FLANGE 36 36 38 38 42 42 52 54 37.5 39.5 41 42.5 42.5 45.5 60 71 60 71 60 71 60 71 60 71 60 71 60 71 4-19 4-19 4-19 8-19 4-23 8-19 4-25 8-23 4-16 4-20 4-23 8-20 4-23 8-20 JIS-10K-40A JIS-10K-50A JIS-20K-40A JIS-20K-50A JIS-30K-40A JIS-30K-50A JIS-63K-40A JIS-63K-50A ANSI/JPI-150LB-1 1/2B ANSI/JPI-150LB-2B ANSI/JPI-300LB-1 1/2B ANSI/JPI-300LB-2B ANSI/JPI-600LB-1 1/2B ANSI/JPI-600LB-2B Note1) In case of the 7th digit of type code is V, A, B, C, D, J or W. Note2) In case of the 7th digit of type code is H, M, T. CONNECTION DIAGRAM −/CK− CK+ 75 + <SS TAG PLATE> 20 10 2-M6 SCREW DEPTH 9 INNER OF GASKET φF 5th digit of the code symbols Q conduit conn. J K M φ49 4th digit of the code symbols 20 <WAFER TYPE> 40A, 1 1/2B 50A, 2B Q 60 71 <AMP. case: L type> (with direct mount adaptor) screw connection type 10 IN CASE OF 4TH DIGIT CODE “S, V, W” 103 φ81 103 8 IN CASE OF 4TH DIGIT CODE “T” φ81 ZERO ADJ. SCREW MTG. PIPE JIS 50A (2B) 38 U-BOLT M8 57 37 “B” CONDUIT CONN. 172 (21) (11) 4 HOLES 9 DIA. WITH ANALOG IND. S φ84 WITH DIGITAL IND. 25 HIGH PRESS. CONN. D VENT/DRAIN PLUG 20 23 163 126 DETAIL “B” (CONDUIT. CONN.) 41 43 M φ15 K EARTH TERMINAL 198 J SEE TABLE1 4th digit of the code symbols conduit conn. J K M G1/2 18 2 11th digit of the S (m) code symbols 4 D, Q E, R L, S V Pg13.5 10.5 4.5 M, V 7 W M20×1.5 16 4 N, W 8 P, X 10 S 1/2-14NPT 16 T 1.5 3 5 F, T 6 2-M8×12 62 70 120 TABLE 1 16th digit of the 17th digit of the code symbols code symbols Press. conn. “D” S R Rc 1/2 S N 1/2-14NPT S 2 Rc 3/4 S T 3/4-14NPT OPTION PARTS FOR FLAMEPROOF OF TIIS (JAPAN) CONNECTION DIAGRAM <SS TAG PLATE> 10th digit code C (Cable gland type) NOTE1) G1/2 φ13 φ33.5 −/CK− CK+ 75 19 106 20 17 + DETAIL “C” "C" CONDUIT CONN. G1/2 CABLE GLAND NOTE1) IN CASE OF 10TH CODE C , φ11 CABLE IS SUITBLE. 11 FKW...5 <AMP. case: T type> (with direct mount adaptor) screw connection type 10 MTG. PIPE JIS 50A (2B) EARTH TERMINAL 8 IN CASE OF 4TH DIGIT CODE “5, 7, 8” IN CASE OF 4TH DIGIT CODE “6” 38 U-BOLT M8 57 (21) “B” CONDUIT CONN. 37 φ81 φ81 100 100 ZERO ADJ. SCREW WITH ANALOG IND. (11) 185 4 HOLES 9 DIA. WITH DIGITAL IND. S 25 HIGH PRESS. CONN. D VENT/DRAIN PLUG 20 23 185 DETAIL “B” (CONDUIT. CONN.) 127 20 226 K M φ15 J SEE TABLE1 4th digit of the code symbols 5 6 conduit conn. J K M G1/2 18 2 1/2-14NPT 16 4 11th digit of the S (m) code symbols 7 Pg13.5 10.5 4.5 8 M20×1.5 16 4 D, Q E, R L, S 1.5 3 5 F, T 6 M, V 7 N, W 8 P, X 10 TABLE 1 16th digit of the 17th digit of the code symbols code symbols Press. conn. “D” S R Rc 1/2 S N 1/2-14NPT S 2 Rc 3/4 S T 3/4-14NPT CONNECTION DIAGRAM −/CK− CK+ 75 + <SS TAG PLATE> 20 12 2-M8×12 62 70 120 <AMP. case: L type> (with direct mount adaptor) IN CASE OF 4TH DIGIT CODE “S, V, W” 38 57 U-BOLT M8 37 172 (21) (11) φ81 16.4011 IN CASE OF 4TH DIGIT CODE “T” 103 φ81 103 MTG. PIPE JIS 50A (2B) 8 10 ZERO ADJ. SCREW “B” CONDUIT CONN. WITH ANALOG IND. 4 HOLES 9 DIA. S WITH DIGITAL IND. N HOLES h DIA. φ84 t 25 φF φE φD 80 20 163 126 VENT/DRAIN PLUG 41 43 DETAIL “B” (CONDUIT. CONN.) EARTH TERMINAL K 198 M φ15 J SEE TABLE1 2-M8×12 16th digit of the code symbols 17th digit of the code symbols φD φE φF t N-φh 1 1 95 70 51 12 4-15 JIS-10K-15A 1 2 100 75 56 14 4-15 JIS-10K-20A 2 1 95 70 51 14 4-15 JIS-20K-15A 2 2 100 75 56 16 4-15 JIS-20K-20A 3 1 115 80 55 18 4-19 JIS-30K-15A 3 2 120 85 60 18 4-19 JIS-30K-20A 6 1 120 85 55 23 4-19 JIS-63K-15A 6 2 135 95 60 25 4-23 JIS-63K-20A 1 H 89 60.3 34.9 11.5 4-16 ANSI/JPI-150LB 1/2B 1 T 98 69.9 42.9 13 4-16 ANSI/JPI-150LB 3/4B 2 H 95 66.7 34.9 14.5 4-16 ANSI/JPI-300LB 1/2B 2 T 117 82.5 42.9 16 4-20 ANSI/JPI-300LB 3/4B 4 H 95 66.7 34.9 14.5 4-16 ANSI/JPI-600LB 1/2B 4 T 117 82.5 42.9 16 4-20 ANSI/JPI-600LB 3/4B FLANGE 62 70 120 4th digit of the code symbols conduit conn. J K G1/2 S 18 M 11th digit of the code symbols 2 T 1/2-14NPT 16 4 V Pg13.5 10.5 4.5 W M20×1.5 16 4 D, Q S (m) 1.5 E, R 3 L, S 5 F, T 6 M, V 7 N, W 8 P, X 10 TABLE 1 OPTION PARTS FOR FLAMEPROOF OF TIIS (JAPAN) CONNECTION DIAGRAM <SS TAG PLATE> 10th digit code C (Cable gland type) NOTE1) G1/2 φ13 φ33.5 −/CK− CK+ 75 19 106 20 17 + DETAIL “C” "C" CONDUIT CONN. G1/2 CABLE GLAND NOTE1) IN CASE OF 10TH CODE C , φ11 CABLE IS SUITBLE. 13 FKW...5 <AMP. case: T type> (with direct mount adaptor) 10 MTG. PIPE JIS 50A (2B) EARTH TERMINAL 8 IN CASE OF 4TH DIGIT CODE “5, 7, 8” IN CASE OF 4TH DIGIT CODE “6” (21) (11) 38 U-BOLT M8 57 φ81 φ81 100 100 ZERO ADJ. SCREW 37 WITH ANALOG IND. 185 "B" CONDUIT CONN. WITH DIGITAL IND. 4 HOLES 9 DIA. S N HOLES h DIA. φ84 t 25 φF φE φD 20 185 23 80 127 20 VENT/DRAIN PLUG DETAIL “B” (CONDUIT. CONN.) K M 226 φ15 J SEE TABLE1 2-M8×12 16th digit of the code symbols 17th digit of the code symbols φD φE φF t N-φh 1 1 95 70 51 12 4-15 JIS-10K-15A 1 2 100 75 56 14 4-15 JIS-10K-20A FLANGE 2 1 95 70 51 14 4-15 JIS-20K-15A 2 2 100 75 56 16 4-15 JIS-20K-20A 3 1 115 80 55 18 4-19 JIS-30K-15A 3 2 120 85 60 18 4-19 JIS-30K-20A 6 1 120 85 55 23 4-19 JIS-63K-15A 6 2 135 95 60 25 4-23 JIS-63K-20A 1 H 89 60.3 34.9 11.5 4-16 ANSI/JPI-150LB 1/2B 1 T 98 69.9 42.9 13 4-16 ANSI/JPI-150LB 3/4B 2 H 95 66.7 34.9 14.5 4-16 ANSI/JPI-300LB 1/2B 2 T 117 82.5 42.9 16 4-20 ANSI/JPI-300LB 3/4B 4 H 95 66.7 34.9 14.5 4-16 ANSI/JPI-600LB 1/2B 4 T 117 82.5 42.9 16 4-20 ANSI/JPI-600LB 3/4B 62 70 120 4th digit of the code symbols 5 conduit conn. J G1/2 −/CK− CK+ 75 + <SS TAG PLATE> 20 14 18 M 2 6 1/2-14NPT 16 4 7 Pg13.5 10.5 4.5 8 M20×1.5 16 4 TABLE 1 CONNECTION DIAGRAM K 11th digit of the code symbols D, Q S (m) 1.5 E, R 3 L, S 5 F, T 6 M, V 7 N, W 8 P, X 10 TABLE 2 Authorities ATEX Authorities Intrinsic safety Ex II 1 G Ex ia IIC T5 Tamb = –40°C to +50°C Ex ia IIC T4 Tamb = –40°C to +70°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator), Ci=36nF (With Arrester), Li=0.7mH (With analog indicator) Factory Mutual 13th digit Y,G,H,S Y,G,H,S Y,G,H,S Y,G,H,S W,A,D Tamb Factory Mutual Class I Div.1 Groups B, C, D T6 Type 4X Class II III Div.1 Groups E, F, G T6 Type 4X Tamb max = +60°C CSA Class I Div.1 Groups C, D Class II Div.1 Groups E, F, G Class III Div.1 Note) “Seal Not Required” enclosure is allowed. Class I Div.1 Groups A, B, C, D Class II Div.1 Groups E, F, G Class III Div.1 Temp Code T5 Tamb max = +50°C Temp Code T4 Tamb max = +70°C Entity Parameters: Vmax=28V, Imax=94.3mA, Ci=25nF (Without Arrester), Ci=36nF (With Arrester),Li=0.6mH (Without analog meter), Li=0.7mH (With analog meter) TIIS Ex ia IIC T4 Tamb max = +60°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=38.4nF, Li=0.694mH IECEx Scheme Ex ia IIC T4 Tamb = –40°C to +70°C Ex ia IIC T5 Tamb = –40°C to +50°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator), Ci=36nF (With Arrester), Li=0.7mH (With analog indicator) NEPSI Ex II 2 GD Ex d IIC T6 IP66/67 T85°C Tamb = −40°C to +65°C Ex d IIC T5 IP66/67 T100°C Tamb = −40°C to +85°C −40°C to +85°C −20°C to +80°C −20°C to +60°C −40°C to +60°C −10°C to +60°C Entity Parameters: Vmax=78V, Imax=94.3mA, Pi=0.66W, Ci=35.98nF, Li=0.694mH CSA ATEX Class I II III Div.1 Groups A, B, C, D, E, F, G T4 Entity Type 4X Model code 9th digit A,B,D L,P,1,2 Q,S,4,5 E,F,H − TIIS Ex do IIB+H2 T4 Tamb max = +55°C Maximum process temp. = +120°C IECEx Scheme Ex d IIC T5 IP66/67 Tamb = −40°C to +85°C Ex d IIC T6 IP66/67 Tamb = −40°C to +65°C NEPSI Ex d IIB+H2 T6 Tamb = −40°C to +60°C 13th digit Y,G,H,S Y,G,H,S Y,G,H,S Y,G,H,S A,W,D ATEX Ex II 3 GD EEx nL IIC T5 Tamb = −40°C to +50°C EEx nL IIC T4 Tamb = −40°C to +70°C Specific Parameters: Model without arrester: Ui=42.4V, Ii=113mA, Pi=1W, Ci=25.18nF, Li=0.694mH Model with arrester: Ui=32V, Ii=113mA, Pi=1W, Ci=35.98nF, Li=0.694mH EEx nAL IIC T5 Tamb = −40°C to +50°C EEx nAL IIC T4 Tamb = −40°C to +70°C Specific Parameters: Model without arrester: Umax=42.4V, Imax=113mA, Pmax=1W, Model with arrester: Umax=32V, Imax=113mA, Pmax=1W Tamb −40°C to +85°C −20°C to +80°C −20°C to +60°C −40°C to +60°C −10°C to +60°C Type n Nonincendive Authorities Ex ia IIC T4 Ex d IIB+H2 T6 / Ex ia IIC T4 Model code 9th digit A,B,D L,P,1,2 Q,S,4,5 E,F,H − Flameproof Factory Mutual (pending) Class I II III Div.2 Groups A, B, C, D, F, G T4 Entity Type 4X Model code 13th digit 9th digit Entity Parameters: Ui=42.4V, Ii=113mA, Pi=1W, Ci=35.98nF, Li=0.694mH A,B,D Y,G,H,S −40°C to +85°C L,P,1,2 Y,G,H,S −20°C to +80°C Q,S,4,5 Y,G,H,S −20°C to +60°C E,F,H Y,G,H,S −40°C to +60°C W,A,D −10°C to +60°C − CSA Tamb Class I Div.2 Groups A, B, C, D Class II Div.2 Groups E, F, G Class III Div.2 Temp Code T5 Tamb max = +50°C Temp Code T4 Tamb max = +70°C Entity Parameters: Vmax=28V, Ci=25.18nF (Without Arrester), Ci=35.98nF (With Arrester), Li=0.694mH 15 FKW...5 Caution on Safety *Before using this product, be sure to read its instruction manual in advance. International Sales Div Sales Group Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fujielectric.com Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425 http://www.fjielectric.com/products/instruments/ Information in this catalog is subject to change without notice. Printed in Japan