Mean Well DRC-40B 40w single output with battery charger (ups function) Datasheet

40W Single Output with Battery Charger (UPS Function)
LPS
■ Features
‧Universal AC input / Full range
‧Protections: Short circuit / Overload / Over voltage
‧Battery low protection / Battery reverse polarity protection
by fuse
‧Can be installed on DIN rail TS-35/7.5 or 15
‧Alarm signal for AC OK and Battery low
DRC-40
series
Bauart gepruft
Sicherheit
egel ma ge
od
o s
be wac
g
www.tuv.com
ID 2000000000
■ Applications
‧Security system
‧Emergency lighting system
‧Alarm system
‧DC UPS system
•Central monitoring system
‧Access systems
(via TTL open collector, optional via relay)
‧Cooling by free air convection
‧Pass LPS
‧LED indicator for power on
‧100% full load burn-in test
‧3 years warranty
■ Description
DRC-40 is a 40W AC/DC DIN rail type security power supply series. In addition to the primary output, there
is a charger output with a smaller rated current, enabling the backup power supply application the security
access systems require. DRC-40 accepts the universal input between 90VAC and 264VAC, and supplies
13.8VDC and 27.6VDC at output, respectively. With the efficiency up to 87%, it can operate with air
convection cooling under -30 ℃ through 70 ℃ . In addition to the key protection features such as overload
protection, over voltage protection, battery low cut off, and battery reverse polarity protection (by fuse),
the alarm signal for AC OK and battery low signaling is provided, via TTL open collector output for the
standard model ( via relay contact output as the optional model), to facilitate the system design.
■ Model Encoding
DRC - 40 A
Output voltage
Output wattage
Series name
File Name:DRC-40-SPEC 2015-03-12
40W Single Output with Battery Charger (UPS Function)
DRC-40
series
SPECIFICATION
MODEL
OUTPUT
DRC-40A
DRC-40B
OUTPUT NUMBER
CH1
CH2
CH1
CH2
DC VOLTAGE
13.8V
13.8V
27.6V
27.6V
RATED CURRENT
1.9A
1A
0.95A
0.5A
CURRENT RANGE
0 ~ 2.9A
--------
0 ~ 1.45A
--------
RATED POWER
40.02W
40.02W
RIPPLE & NOISE (max.) Note.2 120mVp-p
VOLTAGE ADJ. RANGE
--------
VOLTAGE TOLERANCE Note.3 ±1.0%
--------
±1.0%
--------
LINE REGULATION
±0.5%
--------
±0.5%
--------
LOAD REGULATION
±0.5%
--------
±0.5%
--------
HOLD UP TIME (Typ.)
50ms/230VAC
VOLTAGE RANGE
90 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
86%
AC CURRENT (Typ.)
0.8A/115VAC
INRUSH CURRENT (Typ.)
OVERLOAD
PROTECTION
FUNCTION
--------
CH1:24 ~ 30V
SETUP, RISE TIME Note.4 400ms, 50ms/230VAC
INPUT
200mVp-p
CH1:12 ~ 15V
OVER VOLTAGE
800ms, 50ms/115VAC at full load
10ms/115VAC at full load
127 ~ 370VDC
[DC input operation possible by connecting AC/L(+), AC/N(-)]
87%
0.6A/230VAC
COLD START 30A/115VAC
60A/230VAC
105 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
CH1:14.49 ~ 18.63V
CH1:28.98 ~ 37.26V
Protection type : Shut down o/p voltage, re-power on to recover
BATTERY CUT OFF
10±0.5V
AC OK
Open collector output, CONTACT : AC OK ; CUT OFF : AC Fail ; max. rating : 50V/30mA
BATTERY LOW
20±1V
Open collector output, CUT OFF : Battery ; CONTACT : Battery Low ; max. rating : 50V/30mA
Battery low voltage : < 11V
WORKING TEMP.
-30 ~ +70℃ (Refer to "Derating Curve")
WORKING HUMIDITY
20 ~ 90% RH non-condensing
Battery low voltage : < 22V
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT
±0.03%/℃ (0 ~ 55℃) on CH1 output
VIBRATION
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
SAFETY & WITHSTAND VOLTAGE
EMC
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
(Note 5)
EMC EMISSION
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61204-3, light industry level, criteria A
MTBF
536.6K hrs min.
OTHERS DIMENSION
PACKING
NOTE
MIL-HDBK-217F (25℃)
40*90*100mm (W*H*D)
0.3Kg; 42pcs/13.6Kg/0.82CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
5. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power
supplies.” (as available on http://www.meanwell.com)
6. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded
permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
File Name:DRC-40-SPEC 2015-03-12
DRC-40
40W Single Output with Battery Charger (UPS Function)
series
Block Diagram
AC OK
Bat. Low
ALARM
CIRCUIT
EMI FILTER
&
RECTIFIER
I/P
POWER
SWITCHING
+V
-V
Bat. +
DETECTION
CIRCUIT
PWM
CONTROL
O.L.P.
RECTIFIERS
&
FILTER
Bat. Battery Charger
&
Back up Control
O.V.P.
Derating Curve
Static Characteristics
100
100
90
80
80
230VAC
Input only
70
60
60
40
50
20
-30
40
-20
0
15
30
40
50 55 60
AMBIENT TEMPERATURE (℃)
70 (VERTICAL)
90
100
125
135
145
155 165
175
180
200
230
264
INPUT VOLTAGE (V) 60Hz
File Name:DRC-40-SPEC 2015-03-12
DRC-40
40W Single Output with Battery Charger (UPS Function)
series
Suggested Application
1.Backup connection for AC interruption
(1) Please refer to Fig1.1 for suggested connection.
The power supply charges the battery and provides energy to the load at the same time when AC mains is OK.
The battery starts to supply power to the load when AC mains fails.
A : 12V
B : 24V
Battery
+
Bat+
Load
-
-
+
Bat-
V+
V-
D C OK
+
+V AD J
Fig 1.1 Suggested system connection
2.Alarm signal for AC OK and battery low
(1) Alarm signal is sent out through " AC OK " & " Battery Low " pins.(TTL open collector output is provided for standard model, and relay contact output is provided as
optional model.)
(2) An external voltage source is required for this function. The maximum applied voltage is 50V and the maximum sink current is 30mA. Please refer to Fig 2.2.
(3) Table2.1 explains the alarm function built in the power supply
Function
Description
Output of alarm
The signal is "Low" when the power supply turns ON.
Low (0.3V max. at 30mA)
The signal turns to be "High" when the power supply turns OFF.
High or open (External applied voltage 50V max.)
The signal is "Low" when the voltage of battery is under A:11V, B:22V.
Low (0.3V max. at 30mA)
The signal is "High" when the voltage of battery is above A:11V, B:22V.
High or open (External applied voltage 50V max.)
AC OK
Battery Low
Table 2.1 Explanation of alarm signal
AC OK (Battery low)
R
V
Pin6(Pin8) Short with output -V
External voltage and R
(The max. Sink is 30mA and 50V)
Fig 2.2 Internal circuit of AC OK (Battery Low), via TTL open collector
File Name:DRC-40-SPEC 2015-03-12
DRC-40
40W Single Output with Battery Charger (UPS Function)
Mechanical Specification
Case No.962A
series
Unit:mm
40
1 00
3.81 ×7
8 7 6 5 4 3 2 1
TB2
D C OK
+
+V AD J
T B1
3
2
1
7.5 7.5
Terminal Pin No. Assignment (TB1):
Pin No.
1
2
3
Assignment
AC/L or DC+
AC/N or DCFG
Terminal Pin No. Assignment (TB2):
Pin No.
1
2
3
Assignment
-V
+V
Bat. +
Pin No.
4
5,6
7,8
Assignment
Bat. AC OK
Bat. Low
Installation Instruction
This series fits DIN rail TS35/7.5 or TS35/15.
(This diagram is for reference. The rail is not included with unit.)
Back View
File Name:DRC-40-SPEC 2015-03-12