40W Single Output with Battery Charger (UPS Function) LPS ■ Features ‧Universal AC input / Full range ‧Protections: Short circuit / Overload / Over voltage ‧Battery low protection / Battery reverse polarity protection by fuse ‧Can be installed on DIN rail TS-35/7.5 or 15 ‧Alarm signal for AC OK and Battery low DRC-40 series Bauart gepruft Sicherheit egel ma ge od o s be wac g www.tuv.com ID 2000000000 ■ Applications ‧Security system ‧Emergency lighting system ‧Alarm system ‧DC UPS system •Central monitoring system ‧Access systems (via TTL open collector, optional via relay) ‧Cooling by free air convection ‧Pass LPS ‧LED indicator for power on ‧100% full load burn-in test ‧3 years warranty ■ Description DRC-40 is a 40W AC/DC DIN rail type security power supply series. In addition to the primary output, there is a charger output with a smaller rated current, enabling the backup power supply application the security access systems require. DRC-40 accepts the universal input between 90VAC and 264VAC, and supplies 13.8VDC and 27.6VDC at output, respectively. With the efficiency up to 87%, it can operate with air convection cooling under -30 ℃ through 70 ℃ . In addition to the key protection features such as overload protection, over voltage protection, battery low cut off, and battery reverse polarity protection (by fuse), the alarm signal for AC OK and battery low signaling is provided, via TTL open collector output for the standard model ( via relay contact output as the optional model), to facilitate the system design. ■ Model Encoding DRC - 40 A Output voltage Output wattage Series name File Name:DRC-40-SPEC 2015-03-12 40W Single Output with Battery Charger (UPS Function) DRC-40 series SPECIFICATION MODEL OUTPUT DRC-40A DRC-40B OUTPUT NUMBER CH1 CH2 CH1 CH2 DC VOLTAGE 13.8V 13.8V 27.6V 27.6V RATED CURRENT 1.9A 1A 0.95A 0.5A CURRENT RANGE 0 ~ 2.9A -------- 0 ~ 1.45A -------- RATED POWER 40.02W 40.02W RIPPLE & NOISE (max.) Note.2 120mVp-p VOLTAGE ADJ. RANGE -------- VOLTAGE TOLERANCE Note.3 ±1.0% -------- ±1.0% -------- LINE REGULATION ±0.5% -------- ±0.5% -------- LOAD REGULATION ±0.5% -------- ±0.5% -------- HOLD UP TIME (Typ.) 50ms/230VAC VOLTAGE RANGE 90 ~ 264VAC FREQUENCY RANGE 47 ~ 63Hz EFFICIENCY (Typ.) 86% AC CURRENT (Typ.) 0.8A/115VAC INRUSH CURRENT (Typ.) OVERLOAD PROTECTION FUNCTION -------- CH1:24 ~ 30V SETUP, RISE TIME Note.4 400ms, 50ms/230VAC INPUT 200mVp-p CH1:12 ~ 15V OVER VOLTAGE 800ms, 50ms/115VAC at full load 10ms/115VAC at full load 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)] 87% 0.6A/230VAC COLD START 30A/115VAC 60A/230VAC 105 ~ 150% rated output power Protection type : Hiccup mode, recovers automatically after fault condition is removed CH1:14.49 ~ 18.63V CH1:28.98 ~ 37.26V Protection type : Shut down o/p voltage, re-power on to recover BATTERY CUT OFF 10±0.5V AC OK Open collector output, CONTACT : AC OK ; CUT OFF : AC Fail ; max. rating : 50V/30mA BATTERY LOW 20±1V Open collector output, CUT OFF : Battery ; CONTACT : Battery Low ; max. rating : 50V/30mA Battery low voltage : < 11V WORKING TEMP. -30 ~ +70℃ (Refer to "Derating Curve") WORKING HUMIDITY 20 ~ 90% RH non-condensing Battery low voltage : < 22V ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85℃, 10 ~ 95% RH TEMP. COEFFICIENT ±0.03%/℃ (0 ~ 55℃) on CH1 output VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes SAFETY STANDARDS UL60950-1, TUV EN60950-1 approved I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC SAFETY & WITHSTAND VOLTAGE EMC ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH (Note 5) EMC EMISSION Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3 EMC IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61204-3, light industry level, criteria A MTBF 536.6K hrs min. OTHERS DIMENSION PACKING NOTE MIL-HDBK-217F (25℃) 40*90*100mm (W*H*D) 0.3Kg; 42pcs/13.6Kg/0.82CUFT 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time. 5. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com) 6. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended. File Name:DRC-40-SPEC 2015-03-12 DRC-40 40W Single Output with Battery Charger (UPS Function) series Block Diagram AC OK Bat. Low ALARM CIRCUIT EMI FILTER & RECTIFIER I/P POWER SWITCHING +V -V Bat. + DETECTION CIRCUIT PWM CONTROL O.L.P. RECTIFIERS & FILTER Bat. Battery Charger & Back up Control O.V.P. Derating Curve Static Characteristics 100 100 90 80 80 230VAC Input only 70 60 60 40 50 20 -30 40 -20 0 15 30 40 50 55 60 AMBIENT TEMPERATURE (℃) 70 (VERTICAL) 90 100 125 135 145 155 165 175 180 200 230 264 INPUT VOLTAGE (V) 60Hz File Name:DRC-40-SPEC 2015-03-12 DRC-40 40W Single Output with Battery Charger (UPS Function) series Suggested Application 1.Backup connection for AC interruption (1) Please refer to Fig1.1 for suggested connection. The power supply charges the battery and provides energy to the load at the same time when AC mains is OK. The battery starts to supply power to the load when AC mains fails. A : 12V B : 24V Battery + Bat+ Load - - + Bat- V+ V- D C OK + +V AD J Fig 1.1 Suggested system connection 2.Alarm signal for AC OK and battery low (1) Alarm signal is sent out through " AC OK " & " Battery Low " pins.(TTL open collector output is provided for standard model, and relay contact output is provided as optional model.) (2) An external voltage source is required for this function. The maximum applied voltage is 50V and the maximum sink current is 30mA. Please refer to Fig 2.2. (3) Table2.1 explains the alarm function built in the power supply Function Description Output of alarm The signal is "Low" when the power supply turns ON. Low (0.3V max. at 30mA) The signal turns to be "High" when the power supply turns OFF. High or open (External applied voltage 50V max.) The signal is "Low" when the voltage of battery is under A:11V, B:22V. Low (0.3V max. at 30mA) The signal is "High" when the voltage of battery is above A:11V, B:22V. High or open (External applied voltage 50V max.) AC OK Battery Low Table 2.1 Explanation of alarm signal AC OK (Battery low) R V Pin6(Pin8) Short with output -V External voltage and R (The max. Sink is 30mA and 50V) Fig 2.2 Internal circuit of AC OK (Battery Low), via TTL open collector File Name:DRC-40-SPEC 2015-03-12 DRC-40 40W Single Output with Battery Charger (UPS Function) Mechanical Specification Case No.962A series Unit:mm 40 1 00 3.81 ×7 8 7 6 5 4 3 2 1 TB2 D C OK + +V AD J T B1 3 2 1 7.5 7.5 Terminal Pin No. Assignment (TB1): Pin No. 1 2 3 Assignment AC/L or DC+ AC/N or DCFG Terminal Pin No. Assignment (TB2): Pin No. 1 2 3 Assignment -V +V Bat. + Pin No. 4 5,6 7,8 Assignment Bat. AC OK Bat. Low Installation Instruction This series fits DIN rail TS35/7.5 or TS35/15. (This diagram is for reference. The rail is not included with unit.) Back View File Name:DRC-40-SPEC 2015-03-12