THERMOELECTRIC COOLING UNITS FOR OUTDOOR ENCLOSURES AND KIOSKS
The AA Outdoor Cooler Series is an Air-to-Air thermoelectric assembly (TEA) that uses
impingement flow to transfer heat. It offers dependable, compact performance by cooling
objects via convection. Heat is absorbed and dissipated thru high density heat exchangers
equipped with air ducted shrouds and brand name fans. The heat pumping action occurs
from custom designed thermoelectric modules that achieve a high coefficient of performance
(COP) to minimize power consumption.
This product series has been designed to pass rigorous Telcordia test requirements conducted
by our customers, such as earthquake resistance, salt fog, wind-driven rain, high temperature
exposure and dust contaminants. This is due to the selection of world class components such
as brand fans with the highest degree of environmental protection and lifetime guaranteed
waterproof connectors, heavy duty anodization on the high-density heat sinks, overheat
protection, and double environmental seals for the thermoelectric modules.
FEATURES AND BENEFITS
• 200W capacity rated at ΔT = 0ºC, Tambient = 32°C
• Wide operating temperature range of -40°C to +55°C
• Telcordia GR-487-CORE tested and verified by customers when integrated
in telecom outdoor enclosures
• Gaskets, connectors, and fans provide a NEMA 4 seal for the enclosure
• UL60950 and UL50 approval obtained by customers when integrated in
telecom outdoor enclosures
• Environmentally friendly solid state operation – no compressor or CFC refrigerants
• Cooling and heating in the same unit; optional temperature controller reverses
the polarity of current to generate heating
APPLICATIONS
•
•
•
•
global solutions: local support
Americas: +1.888.246.9050
Europe: +46.31.704.67.57
Asia: +86.755.2714.1166
[email protected]
www.lairdtech.com/thermal
TM
Outdoor telecom enclosures
Outdoor kiosks and displays
Harsh condition electronic cabinets
Battery cabinets
AA-200-24-44-00-XX
Outdoor Thermoelectric Cooler Assemblies
Innovative Technology
for a Connected World
PERFORMANCE Qc VS ΔT
200
180
160
Qc (W)
140
120
100
80
60
40
20
0
5
10
15
20
25
30
35
40
45
50
dT (°C)
SPECIFICATIONS
AA-200-24-44-00-XX
Technical
Technology
Thermoelectric (TE) modules, forced air, closed loop (non-mixing), filterless, non-refrigerant
Cooling at dT = 0°C, and nominal / float voltage.1
Heating 2
193/214W (659/731 Btu/h)
250W (853 Btu/h)
Voltage (nominal / maximum)
24/28 VDC
Grounding (all voltages)
Positive or negative
Current draw, ±10% (nominal / startup)
Weight
11.3/14.3 A (24V version)
6.6 kg (14.5 lbs)
Panel mounting
Through
≥70,000 hours
Fan life (L10 at +40°C)
Number of connectors
3
Connector type
(on unit / mating side)
On unit: AMP part number: 350777-1, 794269, 350547-6, 794270-1
Mating side: AMP part number : 350778-1, 350550-6, 794270-1
Hi-pot testing
707 VDC
Environmental
Temperature range 3 (external ambient)
-40°C to +55°C (-40°F to +131°F)
Temperature range (internal enclosure)
-20°C to +55°C (-4°F to +131°F)
Degree of protection, enclosure
4
NEMA 4 (IP55)
Degree of protection, unit 5
IP54
Sound level (1m distance)
63 dB(A)
Over-Temp Thermostat (Hot and cold side heat sink)
80°C ± 3°C
Cooling capacities at nominal / float voltage are rated at external temperatures of 32°C and 46°C respectively. Float voltage is defined at 27 VDC
Heating capacity is rated at external temperature of -40°C, nominal voltage, and dT = -45°C.
3)
Controller function shall not operate the external fan during heating mode.
4)
The highest environmental protection level requires an external shroud and is defined as the protection level for the enclosure.
5)
Rating for unit without protective shroud.
1)
2)
Note: The specified performance of any Laird Technologies cooling unit is dependent on how it is handled and incorporated into the final product. This includes elements such
as the system design, insulation design, and assembly method. While Laird Technologies is able to provide general guidelines based upon our experience, it is ultimately
the responsibility of the device manufacturer to validate each product and its performance for its intended use.
AA-200-24-44-00-XX
Innovative Technology
for a Connected World
Outdoor Thermoelectric Cooler Assemblies
ISOMETRIC DRAWINGS
Cold Side
Warm Side
MOUNTING HOLE LOCATION
WIRING SCHEMATIC
Electrical connections
K1 Power to TEM Array (Operate in Cooling Mode)
P1 Positive (Red) Marked +24 VDC
P2 Negative (Black)
K2 Power to Exterior Fan (Hot Side)
P1 Positive (Orange) +24 VDC
P2 Negative (White)
330 ± 30
K3 Power to Interior Fan (Cold Side)
P1 Positive (Green)
P2 Negative (White)
AA-200-24-44-00-XX 1110
Any information furnished by Laird Technologies, Inc. and its agents is believed to be accurate and reliable. All specifications are subject to change without notice. Responsibility for the use and application of Laird Technologies materials rests
with the end user, since Laird Technologies and its agents cannot be aware of all potential uses. Laird Technologies makes no warranties as to the fitness, merchantability or suitability of any Laird Technologies materials or products for any
specific or general uses. Laird Technologies shall not be liable for incidental or consequential damages of any kind. All Laird Technologies products are sold pursuant to the Laird Technologies’ Terms and Conditions of sale in effect from time
to time, a copy of which will be furnished upon request. © Copyright 2010 Laird Technologies, Inc. All Rights Reserved. Laird, Laird Technologies, the Laird Technologies Logo, and other marks are trade marks or registered trade marks of Laird
Technologies, Inc. or an affiliate company thereof. Other product or service names may be the property of third parties. Nothing herein provides a license under any Laird Technologies or any third party intellectual property rights.
Similar pages