EPCOS B84299D1101B003 Filters for power lines 16 to 150 a, 100 db from 14 khz Datasheet

Filters for Power Lines
16 to 150 A,
100 dB from 14 kHz
Series/Type:
B84299*B003/B84299*E003
Date: January 2004
 EPCOS AG 2004. Reproduction, publication and dissemination of this data sheet, enclosures hereto and the
information contained therein without EPCOS' prior express consent is prohibited.
Purchase orders are subject to the General Conditions for the Supply of Products and Services of the Electrical
and Electronics Industry recommended by the ZVEI (German Electrical and Electronic Manufacturers' Association), unless otherwise agreed.
Filters for power lines
B84299*B003
16 to 150 A, 100 dB from 14 kHz
B84299*E003
2- and 4-line-filters
16 to 150 A
Multi-stage
Stopband attenuation 14 kHz to 40 GHz
Features
General-purpose use through design with separate lines without intercoupling
Use of single chokes. Thus the insertion loss values are not reduced under all operating current conditions and not when operated with artificial mains networks (AMN) or other equipment
with high leakage currents.
Insertion loss to CISPR 17
Design
The electrical components are incorporated in an RF-tight case of stainless steel. The cables
enter through glands. The RF-tight termination of the openings is produced by specially shaped
lids.
The conductors and equipment grounding conductor are connected by threaded bolts. The surface around the fixing holes is left as bare metal (unpainted) to ensure good RF contact with metal surfaces (chassis, ground).
Protective measures (grounding)
The high capacitances between the lines and ground require special protective measures. If there
are no product-specific requirements, protection with a secondary ground wire (cross section min.
10 mm2) in accordance with EN 50178 is necessary. For this purpose the filter case have connecting bolts at each end.
Resistors are incorporated in the filter to discharge capacitors after turn-off.
Scope of supply
Filters are supplied complete with all parts required for RF-tight installation (fixing screws,
flanges, RF gaskets, cable glands) and installation instructions.
Installation
No welding is needed on the shielding wall, so any subsequent installation is quite simple.
Accessories and special versions
RF-tight flexible connector fittings are available for installation spaced away from the shielding
wall. Filters with an EMP protection add-on for surge currents up to 100 kA per line are available
on request. To match requirements, filters can be supplied with different kinds of EMC or shielding cable glands.
Tests
All filters are 100% tested and the results are archived under a filter's serial number. If required, a
test report can be generated for the serial number.
2
Filters for power lines
B84299*B003
16 to 150 A, 100 dB from 14 kHz
B84299*E003
Circuit diagrams
2-line filters
16 and 32 A
63 A
100 A
3
Filters for power lines
B84299*B003
16 to 150 A, 100 dB from 14 kHz
B84299*E003
4-line filters
16 and 32 A
63 A
100 and 150 A
4
Filters for power lines
B84299*B003
16 to 150 A, 100 dB from 14 kHz
B84299*E003
Insertion loss αe (typical values at Z = 50 Ω)
Asymmetrical measurement circuit
to MIL-STD-220A
General technical data
Rated voltage
2-line filters
VR
250
V
Line/line
Line/case
Rated voltage
4-line filters
VR
440
250
V
V
Line/line
Line/case
Rated frequency
fR
50/60
Hz
Rated current
See characteristics
75 IR for 50 ms
10 IR for 1 s
2 IR for 1 min
1.4 IR for 15 min
1200 VDC, 2 s
1200 VDC, 2 s
Maximum admissible
overcurrent
Iover
Test voltage
Vtest
Voltage drop/phase
∆V
<1
Maximum DC resistance
Rmax
See characteristics
Referred to +40 °C ambient
temperature
Line/line
Line/case
% Of VR at 50 Hz and IR
5
Per line
Filters for power lines
B84299*B003
16 to 150 A, 100 dB from 14 kHz
B84299*E003
General technical data (continued)
Power dissipation
PD
See characteristics
At rated current IR
Capacitive reactive current/line Ireactive See characteristics
Max. permissible harmonic
distortion (THD)
Permissible ambient
temperature
TA
At 400/230 V and 50 Hz (typical
value)
8
% To EN 50160
25/+40
°C
Climatic category
(EN 60068-1)
25/085/56
25 °C/+85 °C/56 days damp
heat test
Mechanical version
C
Cable glands at both ends or
flexible connector fitting
D
Direct connection to shielding
wall
Characteristics and ordering codes
IR
A
Mechanical Rmax
version
mΩ
2-line filters
16 C
16 D
32 C
32 D
63 C
63 D
100 C
100 D
4-line filters
16 C
16 D
32 C
32 D
63 C
63 D
100 C
100 D
150 C
150 D
PD
W
Ireactive Dimensional Page Approx. Ordering code
drawing
weight
A
kg
< 50
< 50
< 20
< 20
< 6.0
< 6.0
< 3.5
< 3.5
< 30
< 30
< 40
< 40
< 50
< 50
< 70
< 70
1.2
1.2
2.7
2.7
4.9
4.9
6.5
6.5
1
2
3
4
5
6
7
8
7
8
9
10
11
12
13
14
12
12
20
20
36
36
60
60
B84299C2160B003
B84299D2160B003
B84299C2320B003
B84299D2320B003
B84299C1630B003
B84299D1630B003
B84299C1101B003
B84299D1101B003
< 50
< 50
< 20
< 20
< 6.0
< 6.0
< 3.5
< 3.5
< 2.0
< 2.0
< 30
< 30
< 40
< 40
< 70
< 70
< 100
< 100
< 140
< 140
1.2
1.2
2.7
2.7
4.9
4.9
6.5
6.5
6.5
6.5
9
10
11
12
5
6
7
8
13
14
15
16
17
18
11
12
13
14
19
20
24
24
30
30
40
40
60
60
95
95
B84299C2160E003
B84299D2160E003
B84299C2320E003
B84299D2320E003
B84299C1630E003
B84299D1630E003
B84299C1101E003
B84299D1101E003
B84299C1151E003
B84299D1151E003
6
Filters for power lines
B84299*B003
16 to 150 A, 100 dB from 14 kHz
B84299*E003
Dimensional drawings
Dimensional drawing 1 (cable glands at both ends)
2 x 16 A
B84299C2160B003
➀ Input end:
➁ Shielded end:
Cable gland PG 21 (mounted)
Cable gland PG 29/21
(cable gland PG 29, PG 21 and reducer ring in accessory bag)
Paint color: RAL 7035 (light gray, semigloss)
Fixing dimensions
The cable glands (with cutout sealing ring) are suitable for the following overall cable diameter:
PG 29
PG 21
17 to 19 mm
9 to 11 mm
20 to 22 mm
12 to 14 mm
23 to 25 mm
15 to 17 mm
RF-tight connection to shielding wall with connector fitting, see page 21.
7
26 to 28 mm
18 to 20 mm
Filters for power lines
B84299*B003
16 to 150 A, 100 dB from 14 kHz
B84299*E003
Dimensional drawing 2 (direct connection to shielding wall)
2 x 16 A
B84299D2160B003
➀ Input end:
➁ Shielded end:
Cable gland PG 21 (mounted)
Cable gland PG 29/21
(cable gland PG 29, PG 21 and reducer ring in accessory bag)
Paint color: RAL 7035 (light gray, semigloss)
Fixing dimensions
The cable glands (with cutout sealing ring) are suitable for the following overall cable diameter:
PG 29
PG 21
17 to 19 mm
9 to 11 mm
20 to 22 mm
12 to 14 mm
RF-tight connection to shielding wall, see page 21.
8
23 to 25 mm
15 to 17 mm
26 to 28 mm
18 to 20 mm
Filters for power lines
B84299*B003
16 to 150 A, 100 dB from 14 kHz
B84299*E003
Dimensional drawing 3 (cable glands at both ends)
2 x 32 A
B84299C2320B003
➀ Input end:
➁ Shielded end:
Cable gland PG 21 (mounted)
Cable gland PG 29/21
(cable gland PG 29, PG 21 and reducer ring in accessory bag)
Paint color: RAL 7035 (light gray, semigloss)
Fixing dimensions
The cable glands (with cutout sealing ring) are suitable for the following overall cable diameter:
PG 29
PG 21
17 to 19 mm
9 to 11 mm
20 to 22 mm
12 to 14 mm
23 to 25 mm
15 to 17 mm
RF-tight connection to shielding wall with connector fitting, see page 21.
9
26 to 28 mm
18 to 20 mm
Filters for power lines
B84299*B003
16 to 150 A, 100 dB from 14 kHz
B84299*E003
Dimensional drawing 4 (direct connection to shielding wall)
2 x 32 A
B84299D2320B003
➀ Input end:
➁ Shielded end:
Cable gland PG 21 (mounted)
Cable gland PG 29/21
(cable gland PG 29, PG 21 and reducer ring in accessory bag)
Paint color: RAL 7035 (light gray, semigloss)
Fixing dimensions
The cable glands (with cutout sealing ring) are suitable for the following overall cable diameter:
PG 29
PG 21
17 to 19 mm
9 to 11 mm
20 to 22 mm
12 to 14 mm
RF-tight connection to shielding wall, see page 21.
10
23 to 25 mm
15 to 17 mm
26 to 28 mm
18 to 20 mm
Filters for power lines
B84299*B003
16 to 150 A, 100 dB from 14 kHz
B84299*E003
Dimensional drawing 5 (cable glands at both ends)
2 x 63 A / 4 x 63 A
B84299C1630B003, ...E003
➀ Input end:
Cable gland PG 29/21
(PG 29 mounted, PG 21 and reducer ring in accessory bag)
➁ Shielded end:
Cable gland PG 29/21
(cable gland PG 29, PG 21 and reducer ring in accessory bag)
Paint color: RAL 7035 (light gray, semigloss)
Fixing dimensions
The cable glands (with cutout sealing ring) are suitable for the following overall cable diameter:
PG 29
PG 21
17 to 19 mm
9 to 11 mm
20 to 22 mm
12 to 14 mm
23 to 25 mm
15 to 17 mm
RF-tight connection to shielding wall with connector fitting, see page 21.
11
26 to 28 mm
18 to 20 mm
Filters for power lines
B84299*B003
16 to 150 A, 100 dB from 14 kHz
B84299*E003
Dimensional drawing 6 (direct connection to shielding wall)
2 x 63 A / 4 x 63 A
B84299D1630B003, ...E003
➀ Input end:
Cable gland PG 29/21
(PG 29 mounted, PG 21 and reducer ring in accessory bag)
➁ Shielded end:
Cable gland PG 29/21
(cable gland PG 29, PG 21 and reducer ring in accessory bag)
Paint color: RAL 7035 (light gray, semigloss)
Fixing dimensions
The cable glands (with cutout sealing ring) are suitable for the following overall cable diameter:
PG 29
PG 21
17 to 19 mm
9 to 11 mm
20 to 22 mm
12 to 14 mm
RF-tight connection to shielding wall, see page 21.
12
23 to 25 mm
15 to 17 mm
26 to 28 mm
18 to 20 mm
Filters for power lines
B84299*B003
16 to 150 A, 100 dB from 14 kHz
B84299*E003
Dimensional drawing 7 (cable glands at both ends)
2 x 100 A / 4 x 100 A
B84299C1101B003, ...E003
➀ Input end:
Cable gland PG 42/29
(PG 42 mounted, PG 29 and reducer ring in accessory bag)
➁ Shielded end:
Cable gland PG 42/29
(cable gland PG 42, PG 29 and reducer ring in accessory bag)
Paint color: RAL 7035 (light gray, semigloss)
Fixing dimensions
The cable glands (with cutout sealing ring) are suitable for the following overall cable diameter:
PG 42
PG 29
29 to 31 mm
17 to 19 mm
32 to 34 mm
20 to 22 mm
35 to 37 mm
23 to 25 mm
RF-tight connection to shielding wall with connector fitting, see page 21.
13
38 to 40 mm
26 to 28 mm
Filters for power lines
B84299*B003
16 to 150 A, 100 dB from 14 kHz
B84299*E003
Dimensional drawing 8 (direct connection to shielding wall)
2 x 100 A / 4 x 100 A
B84299D1101B003, ...E003
➀ Input end:
Cable gland PG 42/29
(PG 42 mounted, PG 29 and reducer ring in accessory bag)
➁ Shielded end:
Cable gland PG 42/29
(cable gland PG 42, PG 29 and reducer ring in accessory bag)
Paint color: RAL 7035 (light gray, semigloss)
Fixing dimensions
The cable glands (with cutout sealing ring) are suitable for the following overall cable diameter:
PG 42
PG 29
29 to 31 mm
17 to 19 mm
32 to 34 mm
20 to 22 mm
RF-tight connection to shielding wall, see page 21.
14
35 to 37 mm
23 to 25 mm
38 to 40 mm
26 to 28 mm
Filters for power lines
B84299*B003
16 to 150 A, 100 dB from 14 kHz
B84299*E003
Dimensional drawing 9 (cable glands at both ends)
4 x 16 A
B84299C2160E003
➀ Input end:
➁ Shielded end:
Cable gland PG 21 (mounted)
Cable gland PG 29/21
(cable gland PG 29, PG 21 and reducer ring in accessory bag)
Paint color: RAL 7035 (light gray, semigloss)
Fixing dimensions
The cable glands (with cutout sealing ring) are suitable for the following overall cable diameter:
PG 29
PG 21
17 to 19 mm
9 to 11 mm
20 to 22 mm
12 to 14 mm
23 to 25 mm
15 to 17 mm
RF-tight connection to shielding wall with connector fitting, see page 21.
15
26 to 28 mm
18 to 20 mm
Filters for power lines
B84299*B003
16 to 150 A, 100 dB from 14 kHz
B84299*E003
Dimensional drawing 10 (direct connection to shielding wall)
4 x 16 A
B84299D2160E003
➀ Input end:
➁ Shielded end:
Cable gland PG 21 (mounted)
Cable gland PG 29/21
(cable gland PG 29, PG 21 and reducer ring in accessory bag)
Paint color: RAL 7035 (light gray, semigloss)
Fixing dimensions
The cable glands (with cutout sealing ring) are suitable for the following overall cable diameter:
PG 29
PG 21
17 to 19 mm
9 to 11 mm
20 to 22 mm
12 to 14 mm
RF-tight connection to shielding wall, see page 21.
16
23 to 25 mm
15 to 17 mm
26 to 28 mm
18 to 20 mm
Filters for power lines
B84299*B003
16 to 150 A, 100 dB from 14 kHz
B84299*E003
Dimensional drawing 11 (cable glands at both ends)
4 x 32 A
B84299C2320E003
➀ Input end:
➁ Shielded end:
Cable gland PG 21 (mounted)
Cable gland PG 29/21
(cable gland PG 29, PG 21 and reducer ring in accessory bag)
Paint color: RAL 7035 (light gray, semigloss)
Fixing dimensions
The cable glands (with cutout sealing ring) are suitable for the following overall cable diameter:
PG 29
PG 21
17 to 19 mm
9 to 11 mm
20 to 22 mm
12 to 14 mm
23 to 25 mm
15 to 17 mm
RF-tight connection to shielding wall with connector fitting, see page 21.
17
26 to 28 mm
18 to 20 mm
Filters for power lines
B84299*B003
16 to 150 A, 100 dB from 14 kHz
B84299*E003
Dimensional drawing 12 (direct connection to shielding wall)
4 x 32 A
B84299D2320E003
➀ Input end:
➁ Shielded end:
Cable gland PG 21 (mounted)
Cable gland PG 29/21
(cable gland PG 29, PG 21 and reducer ring in accessory bag)
Paint color: RAL 7035 (light gray, semigloss)
Fixing dimensions
The cable glands (with cutout sealing ring) are suitable for the following overall cable diameter:
PG 29
PG 21
17 to 19 mm
9 to 11 mm
20 to 22 mm
12 to 14 mm
RF-tight connection to shielding wall, see page 21.
18
23 to 25 mm
15 to 17 mm
26 to 28 mm
18 to 20 mm
Filters for power lines
B84299*B003
16 to 150 A, 100 dB from 14 kHz
B84299*E003
Dimensional drawing 13 (cable glands at both ends)
4 x 150 A
B84299C1151E003
➀ Input end:
Cable gland PG 42/29
(PG 42 mounted, PG 29 and reducer ring in accessory bag)
➁ Shielded end:
Cable gland PG 42/29
(cable gland PG 42, PG 29 and reducer ring in accessory bag)
Paint color: RAL 7035 (light gray, semigloss)
Fixing dimensions
The cable glands (with cutout sealing ring) are suitable for the following overall cable diameter:
PG 42
PG 29
29 to 31 mm
17 to 19 mm
32 to 34 mm
20 to 22 mm
35 to 37 mm
23 to 25 mm
RF-tight connection to shielding wall with connector fitting, see page 21.
19
38 to 40 mm
26 to 28 mm
Filters for power lines
B84299*B003
16 to 150 A, 100 dB from 14 kHz
B84299*E003
Dimensional drawing 14 (direct connection to shielding wall)
4 x 150 A
B84299D1151E003
➀ Input end:
Cable gland PG 42/29
(PG 42 mounted, PG 29 and reducer ring in accessory bag)
➁ Shielded end:
Cable gland PG 42/29
(cable gland PG 42, PG 29 and reducer ring in accessory bag)
Paint color: RAL 7035 (light gray, semigloss)
Fixing dimensions
The cable glands (with cutout sealing ring) are suitable for the following overall cable diameter:
PG 42
PG 29
29 to 31 mm
17 to 19 mm
32 to 34 mm
20 to 22 mm
RF-tight connection to shielding wall, see page 21.
20
35 to 37 mm
23 to 25 mm
38 to 40 mm
26 to 28 mm
Filters for power lines
B84299*B003
16 to 150 A, 100 dB from 14 kHz
B84299*E003
RF-tight connection to shielding wall with connector fitting (mechanical version C)
Cable
gland
PG 29
PG 42
Connector fitting (must
be ordered separately)
Nominal width 25 mm
Nominal width 40 mm
Ordering code
B84298A0042L***
B84298A0044L***
Hole in shielding
wall
∅ 37 +0.5 mm
∅ 54 +0.5 mm
Bare metal area
on shielding wall
∅ 55 +5 mm
∅ 70 +5 mm
(***: add required length in cm (see also chapter "Installation accessories").
RF-tight connection to shielding wall (mechanical version D)
Cable
gland
Parts for RF-tight mounting (in accessory bag)
Required hole in
shielding wall
Bare metal area
on shielding wall
PG 21
Suitable cable gland with
long thread, RF gasket
∅ 37 +0.5 mm
∅ 55 +5 mm
PG 29
PG 42
and check nut.
∅ 54 +0.5 mm
∅ 70 +5 mm
21
Similar pages