Lineage Power CAR4010K1TN-1A 4000 watt 24 / 48v front end Datasheet

CAR4000 Series
4000 Watt 24 / 48V Front End
Features:
∎
∎
∎
∎
∎
∎
∎
Hot-swap N+1 Redundancy
Single phase or Three phase Input
Power Factor Correction
Over Voltage, Over Current and Thermal Protection
Visual LED Indicators
19” 3U High / 3-Bay Power Shelf
International Safety Approvals
FEATURES
BENEFITS
KEY MARKET SEGMENTS & APPLICATIONS
No minimum load requirements
Eliminates the need for preload on system backplace
∎ Distributed Power
∎ Blade Servers
Modular design
Easy insertion and extraction during hot swap
∎ Mid-end servers
∎ Network Equipment
Single phase or three phase inputs
One stop shopping, breadth of line
∎ Network Storage
∎ Test Equipment
Ideal for Network Bus Applications
∎ Storage Area Networks
Constant current characteristics
SPECIFICATIONS
Input Voltage Range
Input Current
Inrush Current
Input Fuse
Power Factor
Efficiency
Output Voltage & Current
Adjust Range (Trim Pot)
Over Voltage Protection
OVP Protection Type
CAR4010K1
CAR4010L1
Single Phase Input / 180-264 VAC / 47-63 Hz
25.5Amax
50Amax
Single Fuse 30A 3AG
0.99
90% Typical @ 230 VAC
+24 VDC @ 167A
+48 VDC @ 83.3A
21.6~26.4
43.2~52.8
29.5~30.5 VDC
58.5~59.5 VDC
Recycle AC Input to Reset
CAR4030K1
CAR4030L1
Three Phase Input / 180-264 VAC / 47-63 Hz
15A per phase max.
50A max (per phase)
Single Fuse per Phase 20A 3AG
0.95
90% Typical @ 230 VAC
+24 VDC @ 167A
+48 VDC @ 83.3A
21.6~26.4
43.2~52.8
29.5~30.5 VDC
58.5~59.5 VDC
Standby Voltage
Line Regulation
Load Regulation
Output Ripple & Noise
Transient Response
Start-up Time
Hold-up Time
Overshoot / Undershoot
Temperature Coefficient
Remote ON/OFF
Power Fail Signal
Over Current Protection
Over Temperature Protection
MTBF
Output Power Good
LED Indicators
Operating Temperature
Cooling
EMI/EMC
Dimensions
Weight
Safety Approvals
5VSB @ 500mA
0.5% using remote sense (5% on Stand-by Voltage)
0.5% using remote sense (5% on Stand-by Voltage)
<1% (pk-pk)
3% max deviation 0.50ms recovery time for a 25% load change
2 seconds
>20ms at low line
1% at turn ON/OFF
0.02% per °C
Logic 1 (TTL High) or open enables unit (ON), Logic 0 (TTL Low) or short shuts unit down (OFF)
Signal goes low (TTL Low) 2ms before loss output regulation
110-140% V1, 5VSB < 2.5A. Automatic recovery.
Automatic shutdown with auto recovery. Thermal shutdown point @ 95°C
300,000 hrs per Bellcore standard
TTL High = Power Good, TTL Low = Output out of limits
DC Good: Green LED; Temperature OK: Green LED and AC Good: Amber LED
0°C to 50°C at rated output power. Supply derates linearly from 50°C to 65°C at 2.2% per °C
Self contained ball bearing fan
Meets EN61000-3-2, -3 CISPR22 and FCC Part 15 Class A, Bellcore GR-1089-CORE
14.12 x 5.00 x 5.00” / 333.2 x 127 x 127mm (handle extends additional 1.00” / 25.4mm from faceplate)
11.5 pounds / 5.23 kg
UL1950, CSA 22.2 No. 650, TUV EN0950 & CE Mark
rev 100506
www.lineagepower.com/oem
Lineage Power
Lineage Power
Lineage Power (China)
3000 Skyline Dr.
Mesquite, TX 75149 Phone: (972) 284-2000
2841 Dow Avenue
Tustin, CA 92780 USA Phone: (714) 544-6665
1353 Chenqiao Road, Shanghai Sengpu Industrial Park
Shanghai, 201401 China
Phone: 021 6710 8910
CAR4000 Series
4000 Watt 24 / 48V Front End
OUTLINE DRAWING:
14.12
Side & Bottom Views are of
Bus Bar Output Connector Versions
SIDE VIEW
5.00
1.04
1.00
1 .02
AIRFLOW
15.12
5.00
Latch
BOTTOM VIEW
3.20
LEDs
3 2 1
8.00
0.16
0.822
1.79
0.25
REAR PANEL CONNECTIONS:
CAR4030x1
CAR4010x1
1.25
V1 Rtn
1.20
0.641
V1
V1 RTN
1.25
Single Phase Input with Positronic
CAR4030x1H
Three Phase Input with Positronic
V1
1.56
1.56
3.00
CAR4010x1H
Three Phase Input with Bus Bar
Single Phase Input with Bus Bar
2.99
0.84
0.65
15-PIN D-SUB CONNECTOR1 1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
5 VSB
5VSB RTN
MODULE PRESENT
POWER GOOD
ON/OFF
I SHARE
MOD-ENABLE
OVP TEST POINT
AC FAIL
V PROGRAM
+ REMOTE SENSE
CURRENT MONITOR
TEMPERATURE OK
- REMOTE SENSE
NO CONNECTION
THREE PHASE AC INPUT4 4
1
2
3
4
LINE 1
LINE 2
LINE 3
GROUND
0.59
2.44
Positronic Output Connector 2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
V1
V1
V1
V1
V1 RETURN
V1 RETURN
V1 RETURN
V1 RETURN
V1
5VSB RTN
MODULE PRESENT
MODULE ENABLE
CURRENT SHARE
ON/OFF
OVP
V1 RETURN
5VSB
POWER GOOD
AC FAIL
MARGIN 1
+ SENSE
TEMP OK
MARGIN 2
- SENSE
0.98
3.095
SINGLE PHASE AC INPUT 3
1
2
3
4
5
6
GROUND
LINE
NEUTRAL
GROUND
LINE
NEUTRAL
MATING CONNECTORS
1) AMP 205205-2 Housing with
205090-1 Pins
2) Positronics PLC24F4BN0A1/AA
Housing with FC114N2 pins
3) Positronics PLB06F000 Housing
with FC114N2 pins
4) Positronics PLA04F8000 Housing
with FC114N2 pins
Output Bus Bars Mate with Elcon
Part Number 538-17-00100
PART NUMBER DEFINITION GUIDE
CAR 40 xx xx x xx - 1A
CAR 40 xx xx x x Rev.
x xx - 1A
Series
Blank=Non-Compliant
40=4000W
Series
Rev.
Y0=5 of 6 Compliant
Power
Blank=Non-Compliant
40=4000W
Z0=6
of
6
Compliant
10 = 1Ø
Y0=5 of 6 Compliant
Power
RoHS Compliance
30 = 3Ø
Z0=6 of 6 Compliant
10 = 1Ø
Blank
=
Bus
Bar
Input Phase
RoHS Compliance
30 = 3Ø
H
=
Positornic
K1=+24V
Blank
=
Bus Bar
Input
Phase
L1= +48V Output Connector
H = Positronic (front-end only)
K1=24V
Output V
Output Connector
L1=48V
Output V
Blank = Positive
Blank = Front End N = Negative
T = Rectifier
Polarity
Type
Examples:
CAR4010L1-Z01A: 4000W / +48V Front End / Single Phase
AC Input / 6 of 6 RoHS Compliant
CAR4030L1H-Z01A: 4000W / +48V Front End / 3-Phase AC
Input / Positronic Connector / 6 of 6 RoHS Compliant
rev 100506
www.lineagepower.com/oem
Lineage Power
Lineage Power
Lineage Power (China)
3000 Skyline Dr.
Mesquite, TX 75149 Phone: (972) 284-2000
2841 Dow Avenue
Tustin, CA 92780 USA Phone: (714) 544-6665
1353 Chenqiao Road, Shanghai Sengpu Industrial Park
Shanghai, 201401 China
Phone: 021 6710 8910
Similar pages