Fuji EDS9-26A Fc series pt type alarm setter Datasheet

FC SERIES PT TYPE ALARM SETTER
DATA SHEET
PTP
The FC series PT type alarm setter accepts one or two
input signal, compares internal or external setting signal,
and outputs alarm contact signals of upper limit or lower
limit.
Its structure is plug-in style.
SPECIFICATIONS
INPUT SPECIFICATION
Input signal:
Input for monitor 2 points (Max.)
Input for external setting 2 points (Max.)
Input type
Voltage
Current
Input signal
1 to 5V DC
4 to 20mA DC
Input resistance 1 MΩ or over
250Ω
ALARM SETTING SPECIFICATION
Internal setting: By built-in trimmer resistor
External setting: By external signal
OUTPUT SPECIFICATION
Output signal:
2 points (Max.)
Output type:
Relay contact output
Contact capacity: 24V / 0.5A DC, 100V/ 0.4A AC
200V/ 0.2A AC or less (resistance load)
POWER SUPPLY
Power supply:
24V DC (20 to 30V DC)
24V AC, +13%, –10%,(47 to 63Hz)
100V AC (85 to 132V AC / 47 to 63Hz)
200V AC (187 to 264V AC / 47 to 63Hz)
as specified.
Power consumption:
Approx. 2W (at DC power)
Approx. 6VA (at AC power)
OPERATION CONDITION
Ambient temperature: 0 to 50°C
Ambient humidity:
Less than 90%RH (no condensation)
Outline dimension (HxWxD):
96 x 52 x 130mm
Mass:
Appox. 300g
Housing:
Plastic housing (color: black)
Mounting method:
Panel mounting or DIN rail mounting
CHARACTERISTICS
Accuracy:
Less than ± 0.2% of full span
Reproducibility: Less than ± 0.1% of full span
Hysteresis width: Approx. 0.3% of full span
Response time: Less than 0.2 sec.
Dielectric strength:
1500V AC, 1 min.
(Input - Output - Power - Ground)
Insulation resistance:
500V DC, 100MΩ or over
(Input - Output - Power - Ground)
Ambient temperature effect:
Less than ± 0.15% of full span/10°C
Power regulation effect:
Less than ± 0.15% of full span
CODE SYMBOLS
1 2 3 4 5 6 7 8
P T P
9 10
Description
1
Input signal
1 to 5V DC
4 to 20mA
1
2
Output signals
1 point
2 points
1
2
Alarm setting system
Internal setting
External setting
A
B
Power supply
24V DC / 24V AC (50/60Hz)
100V AC (50/60Hz)
200V AC (50/60Hz)
1
2
3
1st alarm specifications
Excitation ON (upper limit alarm)
Excitation ON (lower limit alarm)
Excitation OFF (upper limit alarm)
Excitation OFF (lower limit alarm)
Non- Excitation ON (upper limit alarm)
Non- Excitation ON (lower limit alarm)
Non- Excitation OFF (upper limit alarm)
Non- Excitation OFF (lower limit alarm)
1
2
3
4
5
6
7
8
0
1
2
3
4
5
6
7
8
2nd alarm specifications
None (The 5th digit : 1)
Excitation ON (upper limit alarm)
Excitation ON (lower limit alarm)
Excitation OFF (upper limit alarm)
Excitation OFF (lower limit alarm)
Non- Excitation ON (upper limit alarm)
Non- Excitation ON (lower limit alarm)
Non- Excitation OFF (upper limit alarm)
Non- Excitation OFF (lower limit alarm)
EDS9-26a
Date
Feb. 20, 1996
PTP
FUNCTIONAL DIAGRAM
Internal Setting
31
Output 1
Comparator 1
11
32
Monitor input 1
12
21
22
Setting 1
41
Output 2
Comparator 2
42
13
Monitor input 2
14
23
24
Setting 2
Power
supply
circuit
43
Power supply
44
34
External setting
31
Output 1
Comparator 1
11
32
Monitor input 1
12
21
Setting input 1
41
22
Output 2
Comparator 2
42
13
Monitor input 2
14
23
Setting input 2
24
Power
supply
circuit
43
Power supply
44
34
OUTLINE DIAGRAM (Unit: mm)
Terminal screw M2.5
(for transmission)
35
74
Main unit
94
Terminal screw M4
Terminal
2
48
52
100
Stopper
130
Panel mounting
DIN rail mounting
2-M4
DIN rail
40
52
EXTERNAL CONNECTION DIAGRAM
INPUT 1
INPUT 2
+
11 12
+
13 14
EXT. SP1
EXT. SP2
+
21 22
+
23 24
5
6
31 32
33 34
OUTPUT 1
41 42
43 44
+
-
OUTPUT 2
POWER
RANGE OF DELIVERY
Main unit and socket
Stopper
PTP
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fesys.co.jp/eng
Instrumentation Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http://www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan
Similar pages