Gamewell-FCI A2143-20 Addressable control and relay module Datasheet

SCE-SS and RCE-SS
Features
Addressable Control and Relay Modules
Description
ONES
6724mod2.tif
TENS
SCE-SS Module
(See wiring diagram Fig. 5 for RCE-SS)
SCE-SS Control Module — The SCE-SS
Addressable SmartScan™ Control Module
provides Gamewell intelligent control panels a circuit for Notification Appliances
(horns, strobes, speakers, etc.) or to monitor a telephone circuit. Addressability allows
the SCE-SS to be activated, either manually or through panel programming, on a
select (zone or area of coverage) basis.
RCE-SS Relay Module — The RCE-SS
Addressable Relay Module provides the
system with a dry-contact output for activating a variety of auxiliary devices, such
as fans, dampers, control equipment, etc.
Addressability allows the dry contact to
be activated, either manually or through
panel programming, on a select basis.
Applications
• Internal circuitry and relay
powered directly by two-wire
SLC loop. The SCE-SS module
requires power (for horns,
strobes, etc.), audio (for speakers), or a telephone riser (for
handsets). Internal relay feature
available on SmartScan™
systems only.
• Use with IF602, 610, 632, 654
and 658.
• Integral LED “blinks” green each
time a communication is
received from the control panel
and turns on in steady red when
activated.
• LED blink may be deselected
globally (affects all devices).
• High noise immunity (EMF/RFI).
• The SCE-SS may be used to
switch 24-volt NAC power, audio
(up to 70.7 VRMS) or telephone.
• Wide viewing angle of LED.
The SCE-SS is used to switch 24 VDC audible/visual power, high-level audio (speakers), or control telephone devices. The RCE-SS may be programmed to operate dry
contacts for door holders, Air Handling Unit shutdown, etc., and to reset four-wire
smoke detector power.
Construction
• The face plate is made of off-white Noryl®.
• Controls include two rotary switches for direct-dial entry of address (01-99).
• The SCE-SS is configured for a single Class B (Style Y) or Class A (Style Z)
Notification Appliance Circuit.
• The RCE-SS provides two Form-C dry contacts that switch together.
Operation
Each SCE-SS or RCE-SS uses one of 99 possible module addresses on a SLC loop.
It responds to regular polls from the control panel and reports its type and status,
including the open/normal/short status of its Notification Appliance Circuit (NAC). The
LED blinks with each poll received. On command, it activates its internal relay. The
SCE-SS supervises Class B (Style Y) or Class A (Style Z) notification or control circuits.
Upon code command from the panel, the SCE-SS will disconnect the supervision and
connect the external power supply in the proper polarity across the load device. The
disconnection of the supervision provides a positive indication to the panel that the
control relay actually turned ON. The external power supply is always relay isolated
from the communication loop so that a trouble condition on the external power supply
will never interfere with the rest of the system.
Rotary switches set a unique address for each module. The address may be set before or after mounting. The built-in TYPE CODE (not settable) will identify the module
to the control panel, so as to differentiate between a module and a sensor address.
SmartScan™ is a trademark of Gamewell.
SCE-SS and RCE-SS CS-2466 09/01/06
• Built-in type identification
automatically identifies these
devices to the control panel.
Page 1 of 4
• SEMS screws with clamping
plates for wiring ease.
• Direct-dial entry of address 01–
99 for SmartScan™.
• Speaker, audible/visual, and
telephone applications may be
wired for Class B or A (Style Y or
Z).
Listings
Listings and approvals below
apply to the SCE-SS & RCE-SS
Series Addressable Control and
Relay Modules. In some cases,
certain modules may not be
listed by certain approval
agencies, or listing may be in
process. Consult factory for
latest listing status.
• UL Listed: file S521.
• CSFM approved:
file 7300-1288:171.
Specifications for SCE-SS
Product Line Information
Normal operating voltage: 15 to 32
VDC.
SCE-SS
Intelligent Addressable Control Module.
RCE-SS
Intelligent Addressable Relay Module.
A2143-20
Capacitor, required for Class A (Style Z) operation of speakers.
SMB500
Optional Surface-Mount Backbox.
CB500
Control Module Barrier — required by UL for separating power-limited
and non-power-limited wiring in the same junction box as SCE-SS-1.
Relay Contact Ratings for both SCE-SS and RCE-SS models
Load Description
Application
Maximum
Voltage
Current
Rating
Resistive
Non-coded
30 VDC
3.0 A
Resistive
Coded
30 VDC
2.0 A
Resistive
Non-coded
110 VDC
0.9 A
Resistive
Non-coded
125 VAC
0.9 A
Inductive (L/R = 5 ms)
Coded
30 VDC
0.5 A
Inductive (L/R = 2 ms)
Coded
30 VDC
1.0 A
Inductive (PF = 0.35)
Non-coded
125 VAC
0.5 A
Maximum current draw: 6.5 mA (LED
on).
Average operating current: 375 µA
group poll (SmartScan™ mode) with
LED flashing.
External supply voltage (between
Terminals T3 and T4): maximum 80
volts (RMS or DC).
Drain on external supply: 2 mA maximum (using internal EOL relay).
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F
(0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x
4" (10.16 cm) wide x 1.25" (3.175 cm)
deep. Mounts to a 4" (10.16 cm)
square x 2.125" (5.398 cm) deep box.
Specifications for RCE-SS
Mounting Diagrams
Normal operating voltage: 15 to 32
VDC.
Note CB500 Module Barrier,
which creates isolated quadrant.
Maximum current draw: 6.5 mA (LED
on).
Average operating current: 255 µA
group poll (SmartScan™ mode) with
LED flashing.
EOL resistance: not used.
Temperature range: 32°F to 120°F
(0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x
4" (10.16 cm) wide x 1.25" (3.175 cm)
deep. Mounts to a 4" (10.16 cm)
square x 2.125" (5.398 cm) deep box.
6724mt2.wmf
Normal operating voltage: 15 to 32
VDC.
Maximum current draw: 6.5 mA (LED
on).
Average operating current: 255 µA
group poll (SmartScan™ mode) with
LED flashing.
EOL resistance: not used.
Temperature range: 32°F to 120°F
(0°C to 49°C).
6724mt1.wmf
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x
4" (10.16 cm) wide x 1.25" (3.175 cm)
deep. Mounts to a 4" (10.16 cm)
square x 2.125" (5.398 cm) deep box.
Page 2 of 4
SCE-SS and RCE-SS CS-2466 09/01/06
Wiring Diagrams
The following wiring diagrams are provided:
1) SCE-SS: Typical notification appliance circuit configuration, NFPA Style Y.
2) SCE-SS: Typical fault-tolerant notification appliance circuit configuration, NFPA Style Z.
3) SCE-SS: Typical wiring for speaker supervision and switching, NFPA Style Y.
4) SCE-SS: Typical fault-tolerant wiring for speaker supervision and switching, NFPA Style Z.
5) RCE-SS: Relay module wiring diagram.
Fig. 1 SCE-SS: Typical notification appliance circuit configuration, NFPA Style Y.
• Connect modules to Listed compatible Gamewell control panels only.
• All wiring shown is supervised and power limited.
• Module polarities are shown in alarm.
6827wir1.wmf
Fig. 2 SCE-SS: Typical fault-tolerant notification appliance circuit configuration, NFPA Style Z.
• Connect modules to Listed compatible Gamewell control panels only.
• All wiring shown is supervised and power limited.
• Module polarities are shown in alarm.
6827wir2.wmf
SCE-SS and RCE-SS
CS-2466 09/01/06
Page 3 of 4
Fig. 3 SCE-SS: Typical wiring for speaker supervision and switching, NFPA Style Y.
• Connect modules to Listed compatible
Gamewell control panels only.
• All wiring shown is supervised.
• Wires must be supervised per NFPA.
• Module polarities are shown in alarm.
6724wir3.wmf
Fig. 4 SCE-SS: Typical fault-tolerant wiring for speaker supervision and switching, NFPA Style Z.
•
•
•
•
Connect modules to Listed compatible Gamewell control panels only.
All wiring shown is supervised.
Wires must be supervised per NFPA.
Module polarities are shown in alarm.
NOTE regarding
AUDIO AMPLIFIER in
Figures 3 & 4:
1) Audio circuit wiring
must be twisted-pair as a
minimum. See Gamewell
installation manual for
detailed information.
6724wir4.wmf
Fig. 5 RCE-SS:
Relay module wiring
diagram.
• Connect modules to Listed
compatible Gamewell
control panels only.
• Module does NOT supervise
controlled circuits.
6724wir5.wmf
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com
A Honeywell Company
© 2006 Gamewell-FCI
Specifications and wiring information are provided for information only and are believed
to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring instructions
shipped with the product shall always be used for actual installation. For more
information, contact Gamewell-FCI.