Crydom D1210 Panel mount Datasheet

Panel Mount
DataSheet
Series 1 120 VAC
• Ratings from 10A to 40A @ 24-140 VAC
• SCR output for heavy industrial loads
• Zero turn-on or instantaneous turn-on outputs
• UL/CSA/VDE Approved, CE Compliant to EN60950-1
• Improved SEMS screw and washer
• Redesigned housing with anti-rotation barriers
• AC or DC control
• Direct bond copper substrate
• EMC compliant to Level 3
• Direct power lead frame
• Epoxy free design
For Generation 3 datasheet click here
PRODUCT SELECTION
Control Voltage
3-32 VDC
90-280 VAC
18-36 VAC
10A
25A
40A
D1210
A1210
A1210E
D1225
A1225
A1225E
D1240
A1240
A1240E
AVAILABLE OPTIONS
Control Voltage
A: 90-280 VAC
D: 3-32 VDC
AxxxxE: 18-36 VAC
4
A
Output Frecuency
Blank: 47-440 Hz
4: 400 Hz
12
Overvoltage Protection
Blank: Not Included
P: Included (8)
10
E
Operating
Rated Load Current
Voltage
10: 10 Amps
12: 24-140 VAC 25: 25 Amps
40: 40 Amps
K
P
G
Termination
Blank: Screw
F: Quick Connect (7)
K: Round standoffs
Snubber
Blank: Not Included
S: Included
S
H
Input Status LED
Blank: Not Included
G: Included
Switching Type
Blank: Zero Voltage Turn-On
-10: Instantaneous Turn-On (9)
-10
Thermal Pad
Blank: Not Included
H: Included
Required for valid part number
For options only and not required for valid part number
OUTPUT SPECIFICATIONS (1)
Description
Operating Voltage (47-440Hz) [Vrms] (2)
Transient Overvoltage [Vpk]
Maximum Off-State Leakage Current @ Rated Voltage [mArms] (3)
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec]
Maximum Load Current [Arms] (4)
Minimum Load Current [mArms]
Maximum 1 Cycle Surge Current (50/60Hz) [Apk]
Maximum On-State Voltage Drop @ Rated Current [Vrms]
Thermal Resistance Junction to Case (Rjc) [°C/W]
Maximum 1/2 Cycle I² t for Fusing (50/60Hz) [A² sec]
Minimum Power Factor (at Maximum Load)
10A
25A
40A
24-140
600
1
500
10
150
115/120
1.15
1.03
66/60
0.5
24-140
600
1
500
25
150
239/250
1.15
0.8
285/259
0.5
24-140
600
1
500
40
150
597/625
1.15
0.5
1770/1629
0.5
INPUT SPECIFICATIONS (1)
Description
D12xx
Control Voltage Range
Maximum Reverse Voltage
Minimum Turn-On Voltage
Minimum Turn-Off Voltage
Minimum Input Current [mA]
Maximum Input Current [mA]
Nominal Input Impedance [Ohms]
Maximum Turn-On Time [msec]
Maximum Turn-Off Time [msec]
3-32 VDC
-32
3.0 VDC (5)
1.0 VDC
7
12
1/2 Cycle (6)
1/2 Cycle
Do not forget to visit us at: www.crydom.com
Copyright © 2013 Crydom Inc. Specifications subject to change without notice.
A12xx
A12xxE
90-280 Vrms
90 Vrms
10 Vrms
5
10
Current Regulated
20
30
18-36 Vrms
18 Vrms
4 Vrms
16
20
20
30
Panel Mount
DataSheet
GENERAL SPECIFICATIONS (1)
Description
Parameters
Dielectric Strength, Input/Output/Base (50/60Hz)
Minimum Insulation Resistance (@ 500 VDC)
4000 Vrms
109 Ohm
8 pF
-40 to 80 °C
-40 to 125 °C
2.6 oz (74.9g)
UL 94 V-0
Aluminum
13-15 /1.5-1.7
18-20 / 2.0-2.2
18-20 / 2.0-2.2
85% non-condensing
w/”G” option (green)
Maximum Capacitance, Input/Output
Ambient Operating Temperature Range
Ambient Storage Temperature Range
Weight (typical)
Housing Material
Baseplate Material
Input Terminal Screw Torque Range (in-lbs/Nm)
Load Terminal Screw Torque Range (in-lbs/Nm)
SSR Mounting Screw Torque Range (in-lbs/Nm)
Humidity
LED Input Status Indicator
WIRING DIAGRAM
AC
Input
2 ( )
OUTPUT
Output
2
4
INPUT
4 (– / )
24 AWG (0.2 mm2) / 0.2 [minimum]
10 [44.5]
2 x 12 AWG (3.3 mm2) / 3.3 [maximum]
90 [400]
20 AWG (0.5 mm2) / 0.518 [minimum]
30 [133]
2 x 10 AWG (5.3 mm2) / 5.3
110 [490]
2 x 8 AWG (8.4
S O L I D S TAT E R E L AY
Wire Pull-Out
Strength (lbs)[N]
mm2)
/ 8.4 [maximum]
25
Input Current (mA)
1
Wire Size
(Solid / Stranded)
Terminals
Load (13)
1 ( )
Input Current vs Input Voltage
Standard Regulated “DC” Inputs
Recommended Wire Sizes
V
90 [400]
20
15
10
5
0
0
3
5
10
15
20
25
DC Input Voltage
3 (+ / )
EQUIVALENT CIRCUIT BLOCK DIAGRAMS
Diagram: Series 1 AC control
AC 4
1 AC
AC/DC
Converter
Current
Limiter
-DC 4
1 AC
(11)
Trigger
Circuit
(10)
AC 3
Diagram: Series 1 DC control
(10)
(12)
2 AC
Do not forget to visit us at: www.crydom.com
+DC 3
Copyright © 2013 Crydom Inc. Specifications subject to change without notice.
Current
Limiter
(11)
Trigger
Circuit
(12)
2 AC
30
Panel Mount
DataSheet
MECHANICAL SPECIFICATIONS (1)
Screw Termination
1.1
[27.9]
0.49
[12.4]
1
1.88
[47.6]
OUTPUT
INPUT
1.1
[27.9]
0.49
[12.4]
0.89
[22.6]
Mounting
Hole/Slot
0.18 [4.5]
DIA.
2
S O L I D S TAT E R E L AY
4
Round Standoff Termination (“K” Option)
1
2.25
[57.3]
1.7
[43.2]
1.88
[47.6]
Mounting
Hole/Slot
r 0.09 [2.2]
1.0
[25.4]
1.1
[27.9]
0.49
[12.4]
1
1.88
[47.6]
INPUT
1.0
[25.4]
1.75
[44.5]
1.31
[33.4]
1.1
[27.9]
0.49
[12.4]
Mounting
Hole/Slot
0.18 [4.5]
DIA.
1
2.25
[57.3]
1.7
[43.2]
1.88
[47.6]
0.89
[22.6]
1.25
[31.8]
Mounting
Hole/Slot
r 0.09 [2.2]
GENERAL NOTES
(1) All parameters at 25°C unless otherwise specified.
(2) For “S” option, operating voltage frequency is 47-63Hz.
(3) For parts with option “S” maximum leakage current is 10mA.
(4) Heat sinking required, see derating curves.
(5) Increase minimum voltage by 1V for operations from -20 to -40°C.
(6) Turn-on time for Instantaneous turn-on versions is 0.02 msec (DC Control Models).
(7) Single pair (up to 25A) Double pair* (50A model only). *Caution: User must connect to both pairs.
(8) Output will self trigger between 450-600Vpk, not suitable for capacitive loads.
(9) Instantaneous turn-on version is not recomended for capacitive loads. Use zero turn-on only.
(10) Elective Input Status LED, “G” option.
(11) Elective Overvoltage Protection, “P” option.
(12) Elective Internal Snubber, “S” option.
(13) Load can be wired to either SSR output terminal 1 or 2.
Do not forget to visit us at: www.crydom.com
Copyright © 2013 Crydom Inc. Specifications subject to change without notice.
OUTPUT
8-32 Output Screw
(2 places)
Faston Terminal
0.25 x 0.032 (4 places)
INPUT
1.0
[25.4]
1.75
[44.5]
1.31
[33.4]
2
S O L I D S TAT E R E L AY
4
3
6-32 Input Screw
(2 places)
Faston Terminal
0.187 x 0.032 (2 places)
0.89
[22.6]
Quick Connect Termination (“F” Option) - Up to 50 Amp (7)
2
S O L I D S TAT E R E L AY
4
Mounting
Hole/Slot
r 0.09 [2.2]
OUTPUT
8-32 Output Screw
(2 places)
Faston Terminal
0.25 x 0.032 (2 places)
Mounting
Hole/Slot
r 0.09 [2.2]
1.75
[44.5]
Quick Connect Termination (“F” Option) - Up to 25 Amp (7)
2.25
[57.3]
1.7
[43.2]
3
1.0
[25.4]
0.92
[23.3]
1.75
[44.5]
Mounting
Hole/Slot
0.18 [4.5]
DIA.
INPUT
1.08
[27.5]
2
S O L I D S TAT E R E L AY
4
3
OUTPUT
Mounting
Hole/Slot
0.18 [4.5]
DIA.
2.25
[57.3]
1.7
[43.2]
3
6-32 Input Screw
(2 places)
Faston Terminal
0.187 x 0.032 (2 places)
0.89
[22.6]
1.25
[31.8]
Panel Mount
DataSheet
SURGE CURRENT INFORMATION
25 A
250
100
200
Surge Current (Amp)
Surge Current (Amp)
10 A
120
80
60
40
20
0
0.01
0.1
1
Surge Duration (Secs)
150
100
50
0
0.01
10
0.1
1
Surge Duration (Secs)
10
40 A
Surge Current (Amp)
600
500
400
300
200
100
0
0.01
0.1
1
Surge Duration (Secs)
10
Non repetitive peak surge current at Tj initial 40ºC.
THERMAL DERATE INFORMATION
10 A
3ºC/W
5ºC/W
25 A
1.5ºC/W
No Heatsink
8
6
4
2
0
2ºC/W
3ºC/W
25
Load Current (Amps)
Load Current (Amps)
10
20
30
40
50
60
70
Ambient Temperature (ºC)
20
15
10
5
0
80
20
40 A
1ºC/W
1.5ºC/W
2ºC/W
3.5ºC/W
Load Current (Amps)
40
30
20
10
0
20
30
40
50
60
70
Ambient Temperature (ºC)
Do not forget to visit us at: www.crydom.com
Copyright © 2013 Crydom Inc. Specifications subject to change without notice.
80
30
40
50
60
70
Ambient Temperature (ºC)
80
Panel Mount
DataSheet
AGENCY APPROVALS
EN60950 : Meets the requirements of sections1.5: 1,7: 2.9: 2.10.5.3: 4.2: 4.5: 4.7:
Designed in accordance with the requirements of IEC 62314
IEC 61000-4-2 : Electrostatic Discharge – Level 3
IEC 61000-4-4 : Electrically Fast Transients – Level 3
IEC 61000-4-5 : Electrical Surges – Level 3
IEC 60068-2-6 : Vibration 0.33mm and 0.75 mm Amplitude over 10-55 Hz
IEC 60068-2-27 : Shock Resistance 15g/11ms
E116949
LR81689
10143 UG (Not Applicable: -B and 4D)
ACCESORIES
Recommended Accessories
New Accessories!
Protective Cover & Hardware Kits
Protective Cover
Part number: KS101
Clear
plastic
cover
compatible with all new S1
designs. Safety covers
provide added protection
from electric shock when
installing or checking
equipment.
Cover
Hardware
Kit
KS101
HK1
HS501DR
5.0
TRM1
HSP-1
HK3
HS301 / HS301DR
3.0
TRM6
HSP-2
HK4
HS251
2.5
HS201 / HS201DR
2.0
HS172
1.7
HS151 / HS151DR
1.5
HS103 / HS103DR
1.0
HS072
0.7
HS053
0.5
Hardware Kit
Part number: HK3
Bag with 2 threaded
standoffs, 2 screws 8-32 x
1/4, and 2 lockwashers
M8 for output, and 2
threaded standoffs, 2
screws 6-32 x 3/16, and 2
lockwashers M6 for input.
Standoff screws provide additional mounting options
such as "dead bug" mounting, using lug terminals or
wire terminals to the side of the relay.
Heat Sink
Part No.
Thermal Resistance Lug Terminal Thermal Pad
[ºC/W]
Hardware Kit
Part number: HK4
Bag with 2 square brass
accessories and 2 screw
8-32 x 5/8 for output. Used
to mount TMR1 lug
terminals.
Rev. 081913
Do not forget to visit us at: www.crydom.com
Copyright © 2013 Crydom Inc. Specifications subject to change without notice.
Panel Mount
DataSheet
DANGER / PELIGRO / DANGER /GEFAHR / PERICOLO / 危险
HAZARD OF
ELECTRIC
SHOCK,
EXPLOSION,
OR ARC FLASH.
• Disconnect all
power before
installing or
working with
this equipment.
• Verify all
connections
and replace all
covers before
turning on
power.
Failure to follow
these
instructions will
result in death
or serious injury.
RIESGO DE
DESCARGA
ELECTRICA O
EXPLOSION.
• Desconectar
todos los
suministros de
energia a este
equipo antes
de trabajar
con este equipo.
• Verificar todas
las conexiones
y colocar todas
las tapas antes
de energizer
el equipo.
El
incumplimiento
de estas
instrucciones
puede provocar
la muerte o
lesiones serias.
RISQUE DE
DESCHARGE
ELECTRIQUE
OU EXPLOSION
• Eteindre
toutes les
sources
d'énergie de
cet appareil
avant de
travailler
dessus de cet
appareil
GEFAHR EINES
ELEKTRISCHE
N SCHLAGES
ODER EINER
EXPLOSION.
• Stellen Sie
jeglichen
Strom ab, der
dieses Gerät
versorgt, bevor
Sie an dem
Gerät Arbeiten
durchführen
• Vor dem
Drehen auf
Energie alle
Anschlüsse
überprüfen
und alle
Abdeckungen
ersetzen.
• Vérifier tous
connections, et
remettre tous
couverts en
olace avant de
mettre sous
De non-suivi de
ces instructions
provoquera la
mort ou des
lésions sérieuses
sérieuses.
Unterlassung
dieser
Anweisungen
können zum
Tode oder zu
schweren
Verletzungen
führen.
RISCHIO DI
SCOSSA
ELETTRICA O
DELL’ESPLOSI
ONE.
• Spenga tutta
l'alimentazion
e che fornisce
questa
apparecchiatu
ra prima del
lavorare a questa
apparecchiatu ra
存在电击、
爆炸或电弧
闪烁危险
•
在操作此设
备之前请先
关闭电源。
若不遵守这些说明,
可能会导致严重的
人身伤害甚至死亡。
• Verificare tutti
i collegamenti
e sostituire
tutte le coperture
prima della
rotazione
sull'alimentazi one
L'omissione di
seguire queste
istruz ioni
provocherà la
morte o di
lesioni serie
WARNING / AVERTISSEMENT / WARNUNG /ADVERTENCIA / AVVERTENZA / 警告
RISK OF MATERIAL DAMAGE AND HOT
ENCLOSURE
RISQUE DE DOMMAGE MATERIEL ET DE
SURCHAUFFE DU BOITIER
GEFAHR VON MATERIALSCHÄDEN UND
GEHÄUSEERHITZUNG
• The product's side panels may be hot, allow
the product to cool before touching.
• Follow proper mounting instructions including
torque values.
• Do not allow liquids or foreign objects to enter
this product.
• Les panneaux latéraux du produit peuvent être
chauds. Laisser le produit refroidir avant de le
toucher.
• Respecter les consignes de montage, et
notamment les couples de serrage.
• Ne pas laisser pénétrer de liquide ni de corps
étrangers à l'intérieur du produit.
• Die Seitenwände können heiß sein. Lassen Sie
das Produkt abkühlen, bevor Sie es berühren.
• Beachten Sie die Montageanweisungen,
• Führen Sie keine Flüssigkeiten oder
Fremdkörper in das Produkt ein.
Le non-respect de cette directive peut entraîner,
Failure to follow these instructions can result in des lésions corporelles graves ou des
serious injury, or equipment damage.
dommages matériels.
Die Nichtbeachtung dieser Anweisung kann
Körperverletzung oder Materialschäden
zur Folge haben.
RIESGO DE DAÑOS MATERIALES Y DE
SOBRECALENTAMIENTO DE LA UNIDAD
RISCHIO DI DANNI MATERIALI E D'INVOLUCRO
CALDO
材料损坏和高温外壳的危险性
• Los paneles laterales del producto pueden
estar calientes. Esperar que el producto se
enfríe antes de tocarlo.
• Respetar las instrucciones de montaje, y en
particular los pares de apretado.
• No dejar que penetren líquidos o cuerpos
extraños en el producto.
• I pannelli laterali dell'apparecchio possono
scottare; lasciar quindi raffreddare il prodotto
prima di toccarlo.
• Seguire le istruzioni di montaggio corrette.
• Non far entrare liquidi o oggetti estranei in questo
apparecchio.
Si no se respetan estas precauciones pueden
producirse graves lesiones, daños materiales.
La mancata osservanza di questa precauzione può
causare gravi rischi per l'incolumità personale o
danni alle apparecchiature.
Do not forget to visit us at: www.crydom.com
Copyright © 2013 Crydom Inc. Specifications subject to change without notice.
• 产品的一侧面板可能很热,在其冷却前请
不要触碰。
• 遵照正确的安装说明,包括扭矩值。
• 请勿让液体及其他异物进入本产品。
如不能正确执行这些操作说明,
极有可能造成严重人体伤害或者设备的损坏。
Panel Mount
DataSheet
ANNEX - ENVIROMENTAL INFORMATION
The environmental information disclosed in this annex including the EIP Pollution logo are in compliance with People’s Republic of China
Electronic Industry Standard SJ/T11364 – 2006, Marking for Control of Pollution Caused by Electronic Information Products.
Part
Name
Toxic or hazardous Substance and Elements
Lead
(Pb)
Mercury
(Hg)
Cadmium
(Cd)
Hexavalent
Chromium
(Cr (VI))
Polybrominated
biphenyls
(PBB)
Polybrominated
diphenyl ethers
(PBDE)
Semiconductor die
Solder
附件 - 环保信息
此附件所标示的包括电子信息产品污染图标的环保信息符合中华人民共和国电子行业标准 SJ/T11364 - 2006,
电子信息产品污染控制标识要求。
部件
名称
铅
汞
镉
有毒有害物质或元素
六价铬
多溴联苯
(Pb)
(Hg)
(Cd)
(Cr (VI))
半导体芯片
焊接点
50
Do not forget to visit us at: www.crydom.com
Copyright © 2013 Crydom Inc. Specifications subject to change without notice.
(PBB)
多溴二苯醚
(PBDE)
Similar pages