PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series POWER SUPPLY AC 100-240V Wide-range Input Width only 48mm Efficiency up to 95.6% Excellent Partial Load Efficiency 20% Output Power Reserves Easy Fuse Breaking – 3 times nominal current for 12ms Safe HiccupPLUS Overload Mode Active Power Factor Correction (PFC) Minimal Inrush Current Surge Full Power Between -25°C and +60°C DC-OK Relay Contact Current Sharing Feature for Parallel Use 3 Year Warranty GENERAL DESCRIPTION SHORT-FORM DATA The Dimension CP-Series are cost optimized power supplies without compromising quality, reliability and performance. The most outstanding features of the CP20 series are the high efficiency, electronic inrush current limitation, active PFC, wide operational temperature range and the extraordinary small size. Output voltage Adjustment range Output current The CP20.241-C1 is equipped with conformal coated pcboards preferred for applications in harsh areas. The CP20.241-S1 is equipped with quick-connect springclamp terminals preferred for applications which are exposed to mechanical vibration. The CP20.241-S2 has push-in terminals optimized for easy cabinet wiring. The CP20.241-V1 is equipped with a remote ON/OFF feature and the CP20.242 features an enhanced DC input voltage range. The devices have a power reserve of 20% included, which may even be used continuously up to +45°C. High immunity to transients and power surges as well as low electromagnetic emission, a DC-OK relay contact and a large international approval package makes this unit suitable for nearly every situation. ORDER NUMBERS Power Supply MARKINGS CP20.241 CP20.241-C1 With conformal coated pc-boards CP20.241-S1 With quick-connect spring-clamp terminals CP20.241-S2 With push-in terminals CP20.241-V1 With remote ON/OFF feature CP20.242 Enhanced DC input Mechanical Accessory ZM5.WALL DC 24V Nominal 24 - 28V Factory setting 24.1V 24.0 - 20.6A Below +45°C ambient 20.0 – 17.1A At +60°C ambient 15.0 – 13.0A At +70°C ambient Derate linearely between +45°C and +70°C Input voltage AC AC 100-240V -15%/+10% Mains frequency 50-60Hz ±6% Input current AC 4.26 / 2.23A At 120 / 230Vac Power factor 0.99 / 0.98 At 120 / 230Vac Input voltage DC DC 110-150V±20% For CP20.241 (-xx) DC 110-300V±20% For CP20.242 Input current DC 4.64A / 1.66A At 110 / 300Vdc AC Inrush current 10.0 / 4.5Apk At 120 / 230Vac Efficiency 94.2 / 95.6% At 120 / 230Vac Losses 29.6 / 22.1W At 120 / 230Vac Hold-up time 32/ 32ms At 120 / 230Vac Temperature range -25°C to +70°C Size (WxHxD) 48x124x127mm Without DIN-rail Weight 830g / 1.83lb For details or a complete approval list see section 20. IECEx IND. CONT. EQ. ATEX UL 60950-1 Wall/Panel mount bracket Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 1/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series INDEX Page 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. Intended Use .......................................................3 Installation Requirements...................................3 AC-Input...............................................................5 DC-Input...............................................................6 Input Inrush Current ...........................................7 Output .................................................................8 Hold-up Time.....................................................10 DC-OK Relay Contact ........................................11 Remote ON / OFF Function (CP20.241-V1 only)11 Efficiency and Power Losses..............................12 Lifetime Expectancy ..........................................13 MTBF ..................................................................13 Functional Diagram...........................................14 Terminals and Wiring........................................15 Front Side and User Elements...........................17 EMC....................................................................18 Environment ......................................................20 Safety and Protection Features ........................21 Dielectric Strength ............................................22 Page 20. Approvals .......................................................... 23 21. Other Fulfilled Standards ................................. 23 22. Physical Dimensions and Weight ..................... 24 23. Accessories ........................................................ 25 23.1. UF20.241 Buffer Module ..........................25 23.2. YR40.241/242 - Redundancy Modules .....25 23.3. YR40.245 - Redundancy Modules ............25 23.4. ZM5.WALL – Wall/Panel Mount Bracket .26 24. Application Notes............................................. 27 24.1. Peak Current Capability ...........................27 24.2. Output Circuit Breakers............................28 24.3. Series Operation .......................................29 24.4. Parallel Use to Increase Output Power....29 24.5. Parallel Use for Redundancy ....................30 24.6. Charging of Batteries ...............................31 24.7. Operation on Two Phases ........................31 24.8. Use in a Tightly Sealed Enclosure ............31 24.9. Mounting Orientations ............................32 The information given in this document is correct to the best of our knowledge and experience at the time of publication. If not expressly agreed otherwise, this information does not represent a warranty in the legal sense of the word. As the state of our knowledge and experience is constantly changing, the information in this data sheet is subject to revision. We therefore kindly ask you to always use the latest issue of this document (available under www.pulspower.com). No part of this document may be reproduced or utilized in any form without our prior permission in writing. TERMINOLOGY AND ABREVIATIONS PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol . Earth, Ground This document uses the term “earth” which is the same as the U.S. term “ground”. T.b.d. To be defined, value or description will follow later. AC 230V A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%) included. E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V) 230Vac A figure with the unit (Vac) at the end is a momentary figure without any additional tolerances included. 50Hz vs. 60Hz As long as not otherwise stated, AC 230V parameters are valid at 50Hz mains frequency. may A key word indicating flexibility of choice with no implied preference. shall A key word indicating a mandatory requirement. should A key word indicating flexibility of choice with a strongly preferred implementation. Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 2/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 1. INTENDED USE This device is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office, communication, and instrumentation equipment. Do not use this power supply in equipment, where malfunction may cause severe personal injury or threaten human life. 2. INSTALLATION REQUIREMENTS WARNING Risk of electrical shock, fire, personal injury or death. - Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input block for earth connection and not one of the screws on the housing. - Turn power off before working on the device. Protect against inadvertent re-powering. - Make sure that the wiring is correct by following all local and national codes. - Do not modify or repair the unit. - Do not open the unit as high voltages are present inside. - Use caution to prevent any foreign objects from entering the housing. - Do not use in wet locations or in areas where moisture or condensation can be expected. - Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns. Obey the following installation requirements: - This device may only be installed and put into operation by qualified personnel. - Install the device in an enclosure providing protection against electrical, mechanical and fire hazards. - The device is designed for use in pollution degree 2 areas in controlled environments. - The enclosure of the device provides a degree of protection of IP20 according to IEC 60529. - Mount the unit on a DIN-rail so that the input terminals are located on the bottom of the unit. For other mounting orientations see de-rating requirements in this document. - The device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation grid (e.g. cable conduits) by more than 15%! - Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are recommended when the device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15mm in case the adjacent device is a heat source (Example: another power supply). - Make sure that the wiring is correct by following all local and national codes. Use appropriate copper cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to +45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. Ensure that all strands of a stranded wire enter the terminal connection. Check also local codes and local requirements. In some countries local regulations might apply. - This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect. If damage or malfunction should occur during installation or operation, immediately turn power off and send the device to the factory for inspection. - The device is designed, tested and approved for branch circuits up to up to 30A (UL) or 32A (IEC) without additional protection device. If an external fuse is utilized, do not use circuit breakers smaller than 10A B- or C-Characteristic to avoid a nuisance tripping of the circuit breaker. - A disconnecting means shall be provided for the input of the power supply. Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 3/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 CP-Series 24V, 20A, 480W, SINGLE PHASE Notes for use in hazardous location areas: The power supply is suitable for use in Class I Division 2 Groups A, B, C, D locations. See chapter 20 for details. WARNING EXPLOSION HAZARDS! Substitution of components may impair suitability for this environment. Do not disconnect the unit or operate the voltage adjustment or S/P jumper unless power has been switched off or the area is known to be non-hazardous. Wiring must be in accordance with Class I, Division 2 wiring methods of the National Electrical Code, NFPA 70, and in accordance with other local or national codes. A suitable enclosure must be provided for the end product which has a minimum protection of IP54 and fulfils the requirements of the EN 60079-0. Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 4/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 3. AC-INPUT The device is suitable to be supplied from TN-, TT- and IT mains networks with AC voltage. For suitable DC supply voltages see chapter 4. Nom. AC 100-240V Min. 85-264Vac Continuous operation Min. 264-300Vac For maximal 500ms (occasional) Max. 300Vac Continuous, according to IEC 62477-1 Nom. 50–60Hz ±6% Typ. 82Vac Steady-state value, see Fig. 3-1 Typ. 72Vac Steady-state value, see Fig. 3-1 See recommendations in chapter 2. Allowed voltage L or N to earth Input frequency Turn-on voltage Shut-down voltage External input protection Input current Power factor Crest factor*) Typ. Typ. Typ. AC 100V 5.15A 0.996 1.65 Start-up delay Rise time Typ. Typ. 450ms 145ms 420ms 145ms 440ms 145ms Typ. 160ms 160ms 160ms Max. 200mV 200mV 200mV Turn-on overshoot AC 120V 4.26A 0.996 1.63 AC 230V 2.23A 0.980 1.63 Fig. 3-1 Input voltage range Rated input range Fig. 3-2 Turn-on behavior, definitions Input Voltage max. 500ms Turn-on Shut-down POUT Input Current, typ. a a) 100Vac b) 120Vac c) 230Vac 4 3 Rise Time Fig. 3-4 Power factor vs. output current at 24V output voltage b 5 Start-up delay 264V 300Vac Fig. 3-3 Input current vs. output current at 24V output voltage 6A - 5% Output Voltage VIN 85V At 24V, 20A, see Fig. 3-3 At 24V, 20A, see Fig. 3-4 At 24V, 20A, The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform. See Fig. 3-2 At 24V, 20A const. current load, 0mF load capacitance, see Fig. 3-2 At 24V, 20A const. current load, 20mF load capacitance, see Fig. 3-2 In single use mode, see Fig. 3-2 Overshoot AC input AC input range Power Factor, typ. a, b 1.0 c 0.95 0.9 c 2 a) 100Vac b) 120Vac c) 230Vac 0.85 0.8 1 Output Current 0 Output Current 0.75 2 4 6 8 10 12 14 16 18 20 22 24A 2 4 6 8 10 12 14 16 18 20 22 24A Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 5/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 4. DC-INPUT The device is suitable to be supplied from a DC input voltage. Use a battery or a similar DC source. A supply from the intermediate DC-bus of a frequency converter is not recommended and can cause a malfunction or damage the unit. Connect +pole to L, –pole to N and the PE terminal to an earth wire or to the machine ground. DC input DC input range DC input current Allowed Voltage (+) or (-) input to Earth Turn-on voltage Shut-down voltage Nom. DC 110-150V Nom. DC 110-300V Min. 88-180Vdc Typ. Typ. Max. 88-360Vdc 4.64A 1.66A 375Vdc ±20% For CP20.241, CP20.241-C1, CP20.241-S1, CP20.241S2, CP20.241-V1 ±20% For CP20.242 Continuous operation for CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1 Continuous operation for CP20.242 At 110Vdc, at 24V, 20A At 300Vdc, at 24V, 20A Continuous according to IEC 62477-1 Typ. Typ. 80Vdc 70Vdc Steady state value Steady state value Fig. 4-1 Wiring for DC Input Battery + Power Supply AC L N PE - + Load DC Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 6/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 5. INPUT INRUSH CURRENT An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage. The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on. Inrush current Max. Typ. Max. Inrush energy AC 100V 15Apeak 12Apeak 1A2s AC 120V 12Apeak 10Apeak 1A2s AC 230V 5.5Apeak 4.5Apeak 1A2s Temperature independent Temperature independent Temperature independent Fig. 5-1 Typical turn-on behavior at nominal load and 25°C ambient Input Current 5A / DIV 230Vac Input 24Vdc Output 100mS/DIV Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 7/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 6. OUTPUT The output provides a SELV/PELV rated voltage, which is galvanically isolated from the input voltage. The output is designed to supply any kind of loads, including capacitive and inductive loads. If extreme large capacitors, such as EDLCs (electric double layer capacitors or “UltraCaps”) with a capacitance > 1F are connected to the output, the unit might charge the capacitor in the HiccupPLUS mode. Output voltage Adjustment range Nom. Min. Max. Factory setting output voltage Typ. Line regulation Load regulation Max. Max. Typ. Ripple and noise voltage Output current Max. Nom. Nom. Nom. Nom. Nom. Nom. Fuse breaking current Typ. Overload protection Overload behavior Overload/ short-circuit current Min. Max. Typ. Max. Output capacitance Typ. 24V 24-28V 30V Guaranteed value This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not a guaranteed value which can be achieved. 24.1V In “single use” mode: ±0.2%, at full load, cold unit In “parallel use” mode: ±0.2%, at 20A, cold unit (results to 23.9V±0.2% at 24A and 25.1V±0.2% at no load) 10mV Between 85 and 300Vac input voltage change 100mV Between 0 and 24A in “single use” mode, static value 1000mV Between 0 and 24A in “parallel use” mode, static value, see Fig. 6-2 50mVpp Bandwidth 20Hz to 20MHz, 50Ohm 24A1) At 24V and an ambient temperature below 45°C 20A At 24V and 60°C ambient temperature 15A At 24V and 70°C ambient temperature At 28V and an ambient temperature below 45°C 20.6A1) 17.1A At 28V and 60°C ambient temperature 13A At 28V and 70°C ambient temperature Derate linearely between +45°C and +70°C 60A Up to 12ms once every five seconds, see Fig. 6-4. The fuse braking current is an enhanced transient current which helps to start heavy loads or to trip fuses on faulty output branches. The output voltage stays above 20V. See chapter 24.1 for additional measurements. Included Electronically protected against overload, no-load and short-circuits. In case of a protection event, audible noise may occur. Continuous current Output voltage above 13Vdc, see Fig. 6-1 Intermitted current2) Output voltage below 13Vdc, see Fig. 6-1 26A Continuous current, see Fig. 6-1 29.8A Continuous current, see Fig. 6-1 29A Intermitted current peak value for typ. 2s Load impedance 10mOhm, see Fig. 6-3 Discharge current of output capacitors is not included. 9.8A Intermitted current average value (R.M.S.) Load impedance 10mOhm, see Fig. 6-3 8 500μF Included inside the power supply Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 8/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series Back-feeding loads Max. 35V The unit is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is on or off. The absorbing energy can be calculated according to the built-in large sized output capacitor. 1) This current is also available for temperatures up to +70°C with a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes. 2) HiccupPLUS Mode At heavy overloads (when output voltage falls below 13V), the power supply delivers continuous output current for 2s. After this, the output is switched off for approx. 18s before a new start attempt is automatically performed. This cycle is repeated as long as the overload exists. If the overload has been cleared, the device will operate normally. See Fig. 6-3. Fig. 6-2 Output voltage in “parallel use” mode, typ. Fig. 6-1 Output voltage vs. output current, typ. Output Voltage (Single Use, typ.) 28V Output Voltage (Parallel Use, typ.) Adjustment Range Adjustment Range 29V 24 28V 20 27V A 16 26V 25V 12 A: continuous current B: intermitted current 8 4 0 23V 22V Output Current 0 5 10 15 20 25 Factory setting 24V B 30 35 40A Output Current 4 0 Fig. 6-3 Short-circuit on output, HiccupPLUS® mode, typ. 12 8 20 16 24A Fig. 6-4 Dynamic overcurrent capability, typ. Output Voltage (dynamic behavior, < 12ms) 28V Output Current Normal operation Normal operation Short -circuit 29A 24 Adjustment Range 20 16 12 t 0 2s 18s 2s 18s 2s 18s 8 4 0 Output Current 0 10 20 30 40 50 60 70A Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 9/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 7. HOLD-UP TIME Hold-up Time Typ. Min. Typ. Min. Fig. 7-1 Hold-up time vs. input voltage AC 100V 65ms 54ms 32ms 24ms AC 120V 65ms 54ms 32ms 24ms AC 230V 65ms 54ms 32ms 24ms At 24V, 10A, see Fig. 7-1 At 24V, 10A, see Fig. 7-1 At 24V, 20A, see Fig. 7-1 At 24V, 20A, see Fig. 7-1 Fig. 7-2 Shut-down behavior, definitions Hold-up Time Zero Transition 80ms 70 60 50 40 30 20 10 0 24V, 10A, typ. 24V, 10A, min. Input Voltage 24V, 20A, typ. 24V, 20A, min. Hold-up Time Input Voltage 85 120 155 190 - 5% Output Voltage 230Vac Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 10/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 8. DC-OK RELAY CONTACT This feature monitors the output voltage on the output terminals of a running power supply. Contact closes Contact opens As soon as the output voltage reaches typ. 90% of the adjusted output voltage level. As soon as the output voltage dips more than 10% below the adjusted output voltage. Short dips will be extended to a signal length of 100ms. Dips shorter than 1ms will be ignored. 1V Maximal 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, resistive load Minimal permissible load: 1mA at 5Vdc See dielectric strength table in section 18. Switching hysteresis Contact ratings Isolation voltage Fig. 8-1 DC-ok relay contact behavior VOUT = VADJ 10% < 1ms open 0.9* VADJ > 1...4ms 100ms closed open closed 9. REMOTE ON / OFF FUNCTION (CP20.241-V1 ONLY) This feature allows to switch-off the power supply output with a signal switch or transistor. A link between pin 15 and 16 turns the power supply on. Pin 15 is referenced to the (-) output voltage. The open-loop voltage between pin 16 and pin 15 can be up to 18V. The maximum current, when in remote ON mode, can be up to 2.5mA. The threshold level to switch-off the output is typically 5V and the turn-on threshold is typically 9V. When multiple power supplies are connected in parallel, pin 15 and pin 16 are also allowed to be paralleled to control all units with the same switch or transistor. 16 Remote ON/OFF 15 16 Remote ON/OFF 15 Please note: The remote ON/OFF function has no safety feature included. Fig. 9-1 The switch-off and the turn-on timing >1s Remote ON/OFF <1s 15-16 linked 15-16 open Output Voltage A: Turn-on delay acc. Fig. 3-2 C B: Rise time acc. Fig. 3-2 C A B 1s A B Time C: No active discharge of the output after switch-off Pulses shorter than 1s will be extended to 1s Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 11/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 10. EFFICIENCY AND POWER LOSSES Average efficiency*) Typ. Typ. Typ. AC 100V 93.6% 93.5% 93.2% AC 120V 94.2% 94.1% 93.8% AC 230V 95.6% 95.5% 95.0% Power losses typ. T.B.D. T.B.D. T.B.D. Typ. Typ. Typ. Typ. 2.5W 16.0W 32.8W 40.0W 2.2W 15.0W 29.6W 36.1W 2.2W 12.5W 22.1W 27.1W Efficiency *) At 24V, 20A At 24V, 24A (Power Boost) 25% at 5A, 25% at 10A, 25% at 15A. 25% at 20A CP20.241-V1 in “Remote OFF” mode At 24V, 0A At 24V, 10A At 24V, 20A At 24V, 24A (Power Boost) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25% of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100% of the nominal load for the rest of the time. Fig. 10-1 Efficiency vs. output current at 24V, typ Fig. 10-2 Losses vs. output current at 24V, typ. Efficiency Power Losses 96% 95 94 93 92 91 90 88 87 (c) (b) (a) (a) 100Vac (b) 120Vac (c) 230Vac Output Current 4 6 40W 35 30 25 20 15 10 5 0 (a) (b) (a) 100Vac (b) 120Vac (c) 230Vac (c) Output Current 0 2 4 6 8 10 12 14 16 18 20 22 24A 8 10 12 14 16 18 20 22 24A Fig. 10-3 Efficiency vs. input voltage at 24V, 20A, typ. Fig. 10-4 Losses vs. input voltage at 24V, 20A, typ. Efficiency Power Losses 96% 40W 95 35 94 30 93 25 92 20 15 91 Input Voltage 90 100 120 180 Input Voltage 10 230 264Vac 100 120 180 230 264Vac Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 12/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 11. LIFETIME EXPECTANCY The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years (131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices. Lifetime expectancy AC 100V 123 000h 348 000h 48 000h 136 000h 23 000h 64 000h AC 120V 149 000h 422 000h 60 000h 169 000h 31 000h 88 000h AC 230V 173 000h 488 000h 94 000h 265 000h 54 000h 152 000h At 24V, 10A and 40°C At 24V, 10A and 25°C At 24V, 20A and 40°C At 24V, 20A and 25°C At 24V, 24A and 40°C At 24V, 24A and 25°C 12. MTBF MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit has been running for 50 000h or only for 100h. For these types of units the MTTF (Mean Time To Failure) value is the same value as the MTBF value. MTBF SN 29500, IEC 61709 MTBF MIL HDBK 217F AC 100V 422 000h 790 000h 186 000h AC 120V 445 000h 832 000h 191 000h AC 230V 590 000h 1 060 000h 226 000h 256 000h 263 000h 313 000h 40 000h 42 000h 50 000h 53 000h 55 000h 67 000h At 24V, 20A and 40°C At 24V, 20A and 25°C At 24V, 20A and 40°C; Ground Benign GB40 At 24V, 20A and 25°C; Ground Benign GB25 At 24V, 20A and 40°C; Ground Fixed GF40 At 24V, 20A and 25°C; Ground Fixed GF25 Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 13/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 13. FUNCTIONAL DIAGRAM Fig. 13-1 Functional diagram CP20.241, CP20.241-C1, CP20,241-S1, CP20.242 L N Input Fuse Input Filter Input Rectifier Active Inrush Limiter Temperature Shutdown PFC Converter Output Power Manager Output Filter Power Converter Output Voltage Regulator Output OverVoltage Protection + + Link for Parallel Use VOUT DC-ok LED Output Voltage Monitor DC-ok Relay DC-ok Contact Output Filter + - Fig. 13-2 Functional diagram CP20.241-S2 L N Input Fuse Input Filter Input Rectifier Active Inrush Limiter Temperature Shutdown PFC Converter Output Power Manager Power Converter Output Voltage Regulator Output OverVoltage Protection Link for Parallel Use VOUT DC-ok LED Output Voltage Monitor DC-ok Relay DC-ok Contact Fig. 13-3 Functional diagram CP20.241-V1 L N Input Fuse Input Filter Input Rectifier Active Inrush Limiter Temperature Shutdown PFC Converter Output Power Manager Power Converter Output Filter Output Voltage Regulator Output OverVoltage Protection Output Voltage Monitor + + Link for Parallel Use VOUT DC-ok LED DC-ok Relay DC-ok Contact Remote ON/OFF Remote ON/OFF Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 14/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 14. TERMINALS AND WIRING The terminals are IP20 Finger safe constructed and suitable for field- and factory wiring. CP20.241, CP20.241-C1, CP20.241-V1, CP20.242 Type Solid wire Stranded wire American Wire Gauge Max. wire diameter (including ferrules) Recommended tightening torque Wire stripping length Screwdriver CP20.241-S1 Type Solid wire Stranded wire American Wire Gauge Max. wire diameter (including ferrules) Wire stripping length Screwdriver CP20.241-S2 Type Solid wire Stranded wire Stranded wire with ferrules American Wire Gauge Max. wire diameter (including ferrules) Wire stripping length Screwdriver Input Output Signal Terminals Screw termination Max. 6mm2 Max. 4mm2 AWG 20-10 2.8mm Max. 1Nm, 9lb-in 7mm / 0.28inch 3.5mm slotted or crosshead No 2 Screw termination Max. 6mm2 Max. 4mm2 AWG 20-10 2.8mm Max. 1Nm, 9lb-in 7mm / 0.28inch 3.5mm slotted or crosshead No 2 Push-in termination Max. 1.5mm2 Max. 1.5mm2 AWG 24-16 1.6mm 7mm / 0.28inch 3mm slotted to open the spring Input Quick-connect springclamp termination Max. 6mm2 Max. 4mm2 AWG 20-10 2.8mm 10mm / 0.4inch - Output Quick-connect springclamp termination Max. 6mm2 Max. 4mm2 AWG 20-10 2.8mm 10mm / 0.4inch - Signal Terminals Push-in termination Input Push-in termination Max. 2.5mm2 Max. 2.5mm2 Max. 1.5mm2 AWG 24-12 2.3mm 10mm / 0.4inch 3.0mm slotted to open the spring Output Push-in termination Max. 10mm2 Max. 6mm2 Max. 4mm2 AWG 24-8 3.3mm 15mm / 0.6inch 3.5mm slotted to open the spring Max. 1.5mm2 Max. 1.5mm2 AWG 24-16 1.6mm 7mm / 0.28inch 3mm slotted to open the spring Signal Terminals Push-in termination Max. 1.5mm2 Max. 1.5mm2 Max. 1.5mm2 AWG 24-16 1.6mm 7mm / 0.28inch 3mm slotted to open the spring Instructions for wiring: a) Use appropriate copper cables that are designed for minimum operating temperatures of: 60°C for ambient up to 45°C and 75°C for ambient up to 60°C and 90°C for ambient up to 70°C minimum. b) Follow national installation codes and installation regulations! c) Ensure that all strands of a stranded wire enter the terminal connection! d) Unused terminal compartments should be securely tightened. Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 15/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series Daisy chaining: Daisy chaining (jumping from one power supply output to the next) is not allowed. Use a separate distribution terminal block as shown in Fig. 14-1. Fig. 14-1 Using distribution terminals Distribution Terminals Power Supply + + - - Output Power Supply + + - - Output Load + - Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 16/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 15. FRONT SIDE AND USER ELEMENTS Fig. 15-1 Front side CP20.241, CP20.241-C1 A CP20.241-S1 CP20.241-S2 CP20.241-V1 CP10.242 Input Terminals N, L Line input PE (Protective Earth) input Output Terminals CP20.241-S2: one + pole and two identical - poles All other units: two identical + poles and three identical - poles + Positive output – Negative (return) output C Output Voltage Potentiometer D DC-OK LED (green) On, when the output voltage is >90% of the adjusted output voltage E DC-OK Relay Contact The DC-OK relay contact is synchronized with the DC-OK LED. See chapter 8 for details. F “Parallel Use” “Single Use” Link Link the two terminal poles when power supplies are connected in parallel. In order to achieve a sharing of the load current between the individual power supplies, the “parallel use” regulates the output voltage in such a manner that the voltage at no load is approx. 4% higher than at nominal load. See also chapter 24.4. G Remote ON/OFF Input Pin 15 and 16 must be connected to turn the power supply off. See chapter 9 for details. B Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 17/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 CP-Series 24V, 20A, 480W, SINGLE PHASE 16. EMC The EMC behavior of the device is designed for applications in industrial environment as well as in residential, commercial and light industry environments. EMC Immunity Electrostatic discharge Electromagnetic RF field Fast transients (Burst) Surge voltage on input Surge voltage on output Surge voltage on DC-OK Conducted disturbance Mains voltage dips Voltage interruptions Voltage sags Powerful transients According to the generic standards EN 61000-6-1 and EN 61000-6-2. EN 61000-4-2 Contact discharge 8kV Criterion A Air discharge 15kV Criterion A EN 61000-4-3 80MHz-2.7GHz 20V/m Criterion A EN 61000-4-4 Input lines 4kV Criterion A Output lines 2kV Criterion A Signal lines (coupling clamp) 2kV Criterion A EN 61000-4-5 LÆN 2kV Criterion A L Æ PE, N Æ PE 4kV Criterion A EN 61000-4-5 +Æ1kV Criterion A + / - Æ PE 2kV Criterion A EN 61000-4-5 Signal lines Æ PE 1kV Criterion A EN 61000-4-6 0.15-80MHz 20V Criterion A EN 61000-4-11 0% of 100Vac 0Vac, 20ms Criterion A 40% of 100Vac 40Vac, 200ms Criterion C 70% of 100Vac 70Vac, 500ms Criterion A 0% of 200Vac 0Vac, 20ms Criterion A 40% of 200Vac 80Vac, 200ms Criterion A 70% of 200Vac 140Vac, 500ms Criterion A EN 61000-4-11 0% of 200Vac (=0V) 5000ms Criterion C SEMI F47 0706 Dips on the input voltage according to SEMI F47 standard 80% of 120Vac (96Vac) 1000ms Criterion A 70% of 120Vac (84Vac) 500ms Criterion A 50% of 120Vac (60Vac) 200ms Criterion A VDE 0160 Over entire load range 750V, 0.3ms Criterion A Criterions: A: Power supply shows normal operation behavior within the defined limits. C: Temporary loss of function is possible. Device may shut-down and restarts by itself. No damage or hazards for the device will occur. According to the generic standards EN 61000-6-3 and EN 61000-6-4. EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 Class B EMC Emission Conducted emission input lines Conducted emission output lines Radiated emission Harmonic input current EN 55011, EN 55022 EN 61000-3-2 Voltage fluctuations, flicker EN 61000-3-3 IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 T.B.D. for information only, not mandatory for EN 61000-6-3 Class B Class A equipment: fulfilled Class C equipment: fulfilled in the load range from 8 to 24A Fulfilled, tested with constant current loads, non pulsing This device complies with FCC Part 15 rules. Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 18/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series Switching Frequencies PFC converter Main converter Auxiliary converter 100kHz 80kHz to 140kHz 60kHz Fixed frequency Output load dependent Fixed frequency Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 19/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 17. ENVIRONMENT Operational temperature -25°C to +70°C (-13°F to 158°F) The operational temperature is the ambient or surrounding temperature and is defined as the air temperature 2cm below the device. -40°C to +85°C (-40°F to 185°F) For storage and transportation 6.4W/°C Between +45°C and +60°C (113°F to 140°F) 12W/°C Between +60°C and +70°C (140°F to 158°F) 30W/1000m or 5°C/1000m For altitudes >2000m (6560ft), see Fig. 17-2 18W/-5kPa or 3°C/-5kPa For atmospheric pressures <80kPa, see Fig. 17-2 The de-rating is not hardware controlled. The customer has to take care by himself to stay below the de-rated current limits in order not to overload the unit. 5 to 95% r.h. According to IEC 60068-2-30 Do not energize while condensation is present. 110-47kPa See Fig. 17-2 for details Up to 6000m (20 000ft) See Fig. 17-2 for details III According to IEC 60664-1 for altitudes up to 2000m II According to IEC 60664-1 for altitudes from 2000 to 6000m and atmospheric pressures from 80 to 47kPa 2 According to IEC 62477-1, not conductive 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g According to IEC 60068-2-6 2 hours / axis 30g 6ms, 20g 11ms According to IEC 60068-2-27 3 bumps / direction, 18 bumps in total Shock and vibration is tested in combination with DIN-Rails according to EN 60715 with a height of 15mm and a thickness of 1.3mm and standard orientation. As a rule, only non-silicon precipitating materials are used. The unit conforms to the LABS criteria and is suitable for use in paint shops. Tested according to ISA-71.04-1985, Severity Level G3 and IEC 60068-2-60 Test Ke Method 4 for a service life of minimum 10years in these environments. Some audible noise may be emitted from the power supply during no load, overload or short circuit. Storage temperature Output de-rating Humidity Atmospheric pressure Altitude Over-voltage category Degree of pollution Vibration sinusoidal Shock LABS compatibility Corrosive gases Audible noise Fig. 17-1 Output current vs. ambient temp. Fig. 17-2 Output current vs. altitude Allowed Output Current at 24V Allowed Output Current at 24V 24A B A 20A 24A D 20A C B A 16A 16A 12A 12A 8A 4A 0 -25 0 20 40 A... Tamb < 60°C B... Tamb < 50°C C... Tamb < 45°C D... Short term 8A A...90 to 264Vac, continuous B... short term 4A 60 70°C Ambient Temperature Altitude 0m AP*) 110kPa 2000m 80kPa 4000m 62kPa 6000m 47kPa *) Atmospheric pressure Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 20/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 18. SAFETY AND PROTECTION FEATURES Isolation resistance Min. 500MOhm Min. 500MOhm Min. 500MOhm Min. 500MOhm PE resistance Max. 0.1Ohm Output over-voltage protection Typ. Max. 30.5Vdc 32Vdc In case of an internal defect, a redundant circuit limits the maximum output voltage. The output shuts down and automatically attempts to restart. I According to IEC 61140 A PE (Protective Earth) connection is required IP 20 According to EN/IEC 60529 Included Output shut-down with automatic restart. Temperature sensors are installed on critical components inside the unit and turn the unit off in safety critical situations, which can happen e.g. when ambient temperature is too high, ventilation is obstructed or the de-rating requirements are not followed. There is no correlation between the operating temperature and turn-off temperature since this is dependent on input voltage, load and installation methods. MOV (Metal For protection values see chapter 16 (EMC). Oxide Varistor) Included Not user replaceable slow-blow high-braking capacity fuse 0.12mA / 0.31mA At 100Vac, 50Hz, TN-,TT-mains / IT-mains 0.18mA / 0.45mA At 120Vac, 60Hz, TN-,TT-mains / IT-mains 0.30mA / 0.76mA At 230Vac, 50Hz, TN-,TT-mains / IT-mains 0.16mA / 0.38mA At 110Vac, 50Hz, TN-,TT-mains / IT-mains 0.23mA / 0.55mA At 132Vac, 60Hz, TN-,TT-mains / IT-mains 0.39mA / 0.94mA At 264Vac, 50Hz, TN-,TT-mains / IT-mains 5mm in diameter E.g. screws, small parts Class of protection Degree of protection Over-temperature protection Input transient protection Internal input fuse Touch current (leakage current) Penetration protection Typ. Typ. Typ. Max. Max. Max. Max. At delivered condition between input and output, measured with 500Vdc At delivered condition between input and PE, measured with 500Vdc At delivered condition between output and PE, measured with 500Vdc At delivered condition between output and DC-OK contacts, measured with 500Vdc Resistance between PE terminal and the housing in the area of the DIN-rail mounting bracket. Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 21/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 19. DIELECTRIC STRENGTH The output voltage is floating and has no ohmic connection to the ground. Type and routine tests are conducted by the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all input-terminals together as well as all output poles before conducting the test. When testing, set the cut-off current settings to the value in the table below. Type test 60s A 2500Vac Routine test 5s 2500Vac 2500Vac 500Vac 500Vac 2000Vac 2000Vac 500Vac 500Vac > 10mA > 10mA > 20mA > 1mA Fig. 19-1 Dielectric strength Input DC-ok *) B L N B A Field test 5s Cut-off current setting for field test D Output Earth, PE C + - B 3000Vac C 1000Vac D 500Vac We recommend that either the + pole, the – pole or any other part of the output circuit shall be connected to the protective earth system. This helps to avoid situations in which a load starts unexpectedly or can not be switched off when unnoticed earth faults occur. B*) When testing input to DC-OK ensure that the maximal voltage between DC-OK and the output is not exceeded (column D). We recommend connecting DC-OK pins and the output pins together when performing the test. Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 22/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 20. APPROVALS EC Declaration of Conformity The CE mark indicates conformance with the - EMC directive, - Low-voltage directive and the - ATEX directive CB Scheme, Information Technology Equipment IEC 60950-1 2nd Edition (except for CP20.242) UL 508 (except for CP20.242) IND. CONT. EQ. UL 60950-1 2nd Edition (except for CP20.242) ANSI / ISA 12.12.01 Class I Div 2 pending EN 60079-0, EN 60079-7 ATEX (except for CP20.242) IEC 60079-0, IEC 60079-7 (except for CP20.242) Listed for use as Industrial Control Equipment; U.S.A. (UL 508) and Canada (C22.2 No. 107-1-01); E-File: E198865 Recognized for use as Information Technology Equipment, Level 5; U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950-1); E-File: E137006 Applicable for altitudes up to 2000m. Hazardous Location Class I Div 2 T4 Groups A,B,C,D systems; U.S.A. (ANSI / ISA 12.12.01) and Canada (C22.2 No. 213) Approval for use in hazardous locations Zone 2 Category 3G. Number of ATEX certificate: EPS 17 ATEX 1 089 X II 3G Ex ec nC II T4 Gc IECEx EAC TR Registration (except for CP20.241-V1 and CP20.242) Suitable for use in Class 1 Zone 2 Groups IIa, IIb and IIc locations. Number of IECEx certificate: EPS 17.0046X Registration for the Eurasian Customs Union market (Russia, Kazakhstan, Belarus) 21. OTHER FULFILLED STANDARDS RoHS Directive REACH Directive IEC/EN 61558-2-16 (Annex BB) Safety Isolating Transformer Directive 2011/65/EU of the European Parliament and the Council of June 8th, 2011 on the restriction of the use of certain hazardous substances in electrical and electronic equipment. Directive 1907/2006/EU of the European Parliament and the Council of June 1st, 2007 regarding the Registration, Evaluation, Authorisation and Restriction of Chemicals (REACH) Safety Isolating Transformers corresponding to Part 2-6 of the IEC/EN 61558 Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 23/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 22. PHYSICAL DIMENSIONS AND WEIGHT Width Height Depth Weight DIN-Rail Housing material Installation clearances CP20.241 CP10.241-C1 CP10.242 48mm 1.89’’ 124mm 4.88’’ 127mm 5.0’’ The DIN-rail height must be added to the unit depth to calculate the total required installation depth. 830g / 1.83lb Use 35mm DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm. Body: Aluminium alloy Cover: zinc-plated steel See chapter 2 Fig. 22-1 Front view CP20.241-S1 CP20.241-S2 Fig. 22-2 Side view CP20.241-V1 All Dimensions in mm All Dimensions in mm Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 24/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 CP-Series 24V, 20A, 480W, SINGLE PHASE 23. ACCESSORIES 23.1. UF20.241 BUFFER MODULE This buffer unit is a supplementary device for DC 24V power supplies. It delivers power to bridge typical mains failures or extends the Power Buffer hold-up time after turn-off of the AC power. In Load AC Supply Unit(s) times when the power supply provides sufficient voltages, the buffer unit stores + DC energy in integrated electrolytic capacitors. In case of mains voltage fault, this energy is released again in a regulated process. One buffer module can deliver 20A additional current. The buffer unit does not require any control wiring. It can be added in parallel to the load circuit at any given point. Buffer units can be added in parallel to increase the output ampacity or the hold-up time. 23.2. YR40.241/242 - REDUNDANCY MODULES The YR40.241 and YR40.242 redundancy modules are equipped with two input channels (each 20A), which are individually decoupled by utilizing MOSFET technology. The output current can be as high as 40A. Using MOSFETs instead of diodes reduces the heat generation and the voltage drop between input and output. The modules do not require an additional auxiliary voltage and are self-powered even in case of a short circuit across the output. Due to the low power losses, the units are very slender and only require 36mm width on the DIN-rail. The YR40.241 can be used in combination with any power supply while the YR40.242 is optimized for use in combination with power supplies featured with the HiccupPLUS overload behavior. The terminal arrangement of the YR40.242 is reversed to the YR40.241. Further information and wiring configurations can be found in chapter 24.5. 23.3. YR40.245 - REDUNDANCY MODULES The YR40.245 is a 40A single channel redundancy module, which is equipped with a plug connector on the output. The plug connector allows replacing the power supply or the redundancy module while the system is running. The plug connector avoids that the output wires can touch and short the load circuit. The YR40.245 is very slender and only requires 46mm width on the DIN-rail. It also utilizes MOSFET technology instead of diodes for low heat generation and a minimal voltage drop between input and output. It does not require an additional auxiliary voltage and is selfpowered even in case of a short circuit across the output. Further information and wiring configurations can be found in chapter 24.5. Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 25/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 23.4. ZM5.WALL – WALL/PANEL MOUNT BRACKET This bracket is used to mount the devices on a wall/panel without utilizing a DIN-Rail. It is suitable for CP20.241, CP20.241-C1, CP20.241-V1, CP20.241-S1 and CP20.241-S2. The bracket can be mounted without detaching the DIN-rail brackets. Fig. 23-1 Isometric view (Picture shows the CP20.241) Fig. 23-4 Wall/panel mounting, front view (Picture shows the CP20.241) Fig. 23-3 Isometric view (Picture shows the CP20.241) Fig. 23-2 Isometric view(Picture shows the CP20.241) Fig. 23-5 Hole pattern for wall mounting Fig. 23-6 Wall/panel mounting, side view (Picture shows the CP20.241) Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 26/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 24. APPLICATION NOTES 24.1. PEAK CURRENT CAPABILITY The unit can deliver peak currents (up to several milliseconds) which are higher than the specified short term currents. This helps to start current demanding loads. Solenoids, contactors and pneumatic modules often have a steady state coil and a pick-up coil. The inrush current demand of the pick-up coil is several times higher than the steady-state current and usually exceeds the nominal output current (including the PowerBoost). The same situation applies when starting a capacitive load. The peak current capability also ensures the safe operation of subsequent circuit breakers of load circuits. The load branches are often individually protected with circuit breakers or fuses. In case of a short or an overload in one branch circuit, the fuse or circuit breaker need a certain amount of over-current to open in a timely manner. This avoids voltage loss in adjacent circuits. The extra current (peak current) is supplied by the power converter and the built-in large sized output capacitors of the power supply. The capacitors get discharged during such an event, which causes a voltage dip on the output. The following three examples show typical voltage dips for resistive loads: Fig. 24-1 40A peak current for 50ms, typ. (2x the nominal current) Fig. 24-2 100A peak current for 5ms, typ. (5x the nominal current) 24V Output Voltage 24V Output Voltage 17V 100A 16V Output Current 40A Output Current 0A 0A 10ms/DIV 1ms/DIV Fig. 24-3 60A peak current for 12ms, typ. (3x the nominal current) 24V 20V 60A Output Voltage 12ms Output Current 0A Please note: The DC-OK relay might trigger when the voltage dips more than 10% for longer than 1ms. Peak current voltage dips Typ. Typ. Typ. from 24V to 16V from 24V to 21V from 24V to 17V At 40A for 50ms, resistive load At 100A for 2ms, resistive load At 100A for 5ms, resistive load Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 27/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 24.2. OUTPUT CIRCUIT BREAKERS Standard miniature circuit breakers (MCB’s or UL 1077 circuit breakers) are commonly used for AC-supply systems and may also be used on 24V branches. MCB’s are designed to protect wires and circuits. If the ampere value and the characteristics of the MCB are adapted to the wire size that is used, the wiring is considered as thermally safe regardless of whether the MCB opens or not. To avoid voltage dips and under-voltage situations in adjacent 24V branches which are supplied by the same source, a fast (magnetic) tripping of the MCB is desired. A quick shutdown within 10ms is necessary corresponding roughly to the ride-through time of PLC's. This requires power supplies with high current reserves and large output capacitors. Furthermore, the impedance of the faulty branch must be sufficiently small in order for the current to actually flow. The best current reserve in the power supply does not help if Ohm’s law does not permit current flow. The following table has typical test results showing which B- and C-Characteristic MCBs magnetically trip depending on the wire cross section and wire length. Fig. 24-4 Test circuit Power Supply AC MCB + Wire length DC S1... Fault simulation switch *) Load + S1 - Maximal wire length*) for a fast (magnetic) tripping: 0.75mm² 1.0mm² 1.5mm² 2.5mm² C-2A 31 m 37 m 63 m 98 m C-3A 28 m 34 m 51 m 78 m C-4A 18 m 25 m 38 m 58 m C-6A 9m 11 m 18 m 26 m C-8A 6m 7m 12 m 14 m C-10A 4m 6m 11 m 13 m C-13A 2m 2m 4m 7m B-6A B-10A B-13A B-16A B-20A B-25A 23 m 11 m 7m 5m 1m 28 m 14 m 11 m 6m 1m 46 m 19 m 16 m 8m 2m 66 m 32 m 29 m 15 m 4m 1m Don’t forget to consider twice the distance to the load (or cable length) when calculating the total wire length (+ and – wire). Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 28/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 24.3. SERIES OPERATION Power supplies of the same type can be connected in series for higher output voltages. It is possible to connect as many units in series as needed, providing the sum of the output voltage does not exceed 150Vdc. Voltages with a potential above 60Vdc are not SELV any more and can be dangerous. Such voltages must be installed with a protection against touching. Unit A Input + Output Avoid return voltage (e.g. from a decelerating motor or battery) which is applied to the output terminals. + Unit B Load Input - + - Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power supplies on top of each other. Do not use power supplies in series in mounting orientations other than the standard mounting orientation (input terminals on bottom of the unit). Output Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies. 24.4. PARALLEL USE TO INCREASE OUTPUT POWER Power supplies can be paralleled to increase the output power. The output voltage of all power supplies shall be adjusted to the same value (±100mV) in “Single use” mode with the same load conditions on all units, or the units can be left with the factory settings. After the adjustments, set the unit to “Parallel use” mode, in order to achieve load sharing. The “Parallel use” mode regulates the output voltage in such a manner that the voltage at no load is approx. 4% higher than at nominal load. See also chapter 6. If more than three units are connected in parallel, a fuse or circuit breaker with a rating of 30A or 32A is required on each output. Alternatively, a diode or redundancy module can also be utilized. Unit A Input + Output + Unit B Load Input + - - Output Energize all units at the same time to avoid the overload HiccupPLUS mode. It also might be necessary to cycle the input power (turn-off for at least five seconds), if the output was in HiccupPLUS mode due to overload or short circuits and the required output current is higher than the current of one unit. Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power supplies on top of each other. Do not use power supplies in parallel in mounting orientations other than the standard mounting orientation (input terminals on bottom of the unit) or in any other condition where a derating of the output current is required (e.g. altitude, above 60°C, …). Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies. Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 29/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 24.5. PARALLEL USE FOR REDUNDANCY Please note that there are variants with built-in redundancy are available in the CP20 series. Check CP20.241-Rx units. 1+1 Redundancy: Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case one power supply unit fails. The simplest way is to put two power supplies in parallel. This is called a 1+1 redundancy. In case one power supply unit fails, the other one is automatically able to support the load current without any interruption. It is essential to use a redundancy module to decouple power supplies from each other. This prevents that the defective unit becomes a load for the other power supplies and the output voltage cannot be maintained any more. Recommendations for building redundant power systems: - Use separate input fuses for each power supply. Use separate mains systems for each power supply whenever it is possible. Monitor the individual power supply units. Therefore, use the DC-OK signal of the power supply. It is desirable to set the output voltages of all units to the same value (± 100mV) or leave it at the factory setting. Set the power supply into “Parallel use” mode. Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies. N+1 Redundancy: Redundant systems for a higher power demand are usually built in a N+1 method. E.g. four power supplies, each rated for 20A are paralleled to build a 60A redundant system. Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies. Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power supplies on top of each other. Do not use power supplies in parallel in mounting orientations other than the standard mounting orientation or in any other condition, where a de-rating of the output current is required. Wiring examples for 1+1 and n+1 redundancy: Fig. 24-5 1+1 Redundant configuration for 20A load current with a dual redundancy module Fig. 24-6 N+1 Redundant configuration for 60A load current with multiple power supplies and redundancy modules Failure Monitor Failure Monitor + + - - Output 24V,20A DCOK Power Supply - + - + + Redundancy Module - - + + Output 24V,20A DCOK YR40.241 - - Output 24V,20A o o DCOK Power Supply Power Supply o o + - + - + + DCOK YR40.241 Redundancy Module - - + + Output 24V,20A Input Input 2 1 Power Supply - - Output 24V,20A o o DCOK Power Supply o o + - + - + + DCOK YR40.241 Redundancy Module - - Output 24V,20A Input Input 2 1 Output Input Input Output Input Input Output Input - L N PE L N PE - L N PE L N PE - L N PE 20A Load I I L optional Input + + o o Power Supply L N PE optional I o o + Input Input 2 1 + 60A Load I I I L N N PE PE Alternatively, the YR40.242 redundancy module can be used but has the input and output terminals reversed. Alternatively, the YR40.242 redundancy module can be used but has the input and output terminals reversed. Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 30/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 24.6. CHARGING OF BATTERIES The power supply can be used to charge lead-acid or maintenance free batteries. Two 12V SLA or VRLA batteries are needed in series connection. Instructions for charging batteries: a) b) Set output voltage (measured at no load and at the battery end of the cable) very precisely to the end-of-charge voltage. End-of-charge voltage 27.8V 27.5V 27.15V 26.8V Battery temperature 10°C 20°C 30°C 40°C Use a 30A or 32A circuit breaker (or blocking diode) between the power supply and the battery. c) Ensure that the output current of the power supply is below the allowed charging current of the battery. d) Ensure that the ambient temperature of the power supply stays below 40°C. e) Use only matched batteries when putting 12V types in series. f) The return current to the power supply (battery discharge current) is typ. 3.5mA when the power supply is switched off (except in case a blocking diode is utilized). 24.7. OPERATION ON TWO PHASES Power Supply 240V +10% max. L1 The power supply can also be used on two-phases of a three-phasesystem. Such a phase-to-phase connection is allowed as long as the supplying voltage is below 240V+10%. L3 24.8. USE IN A TIGHTLY SEALED ENCLOSURE AC L N PE L2 DC When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher than outside. In such situations, the inside temperature defines the ambient temperature for the power supply. The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure. The power supply is placed in the middle of the box, no other heat producing items are inside the box Enclosure: Load: Input: Temperature inside enclosure: Temperature outside enclosure: Temperature rise: Rittal Typ IP66 Box PK 9519 100, plastic, 180x180x165mm 24V, 16A; (=80%) load is placed outside the box 230Vac 51.7°C (in the middle of the right side of the power supply with a distance of 2cm) 25.9°C 25.8K Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 31/32 PRELIMINARY CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 24.9. MOUNTING ORIENTATIONS Mounting orientations other than all terminals on the bottom require a reduction in continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous operation can be found below: Curve A1 Curve A2 Recommended output current. Max allowed output current (results in approximately half the lifetime expectancy of A1). Fig. 24-7 Mounting Orientation A (Standard orientation) Output Current 24A OUTPUT A1 18 Power Supply 12 6 Ambient Temperature 0 INPUT 10 Fig. 24-8 Mounting Orientation B (Upside down) 20 30 50 40 60°C Output Current 24A A1 INPUT 18 A2 Power Supply 12 6 Ambient Temperature OUTPUT 0 10 Fig. 24-9 Mounting Orientation C (Table-top mounting) 20 30 50 40 60°C Output Current 24A A1 18 A2 12 6 Ambient Temperature 0 10 50 40 60°C 24A OUTPUT Power Supply 18 A1 12 A2 6 Ambient Temperature 0 10 20 30 40 50 60°C Output Current 18 INPUT Power Supply 24A OUTPUT Fig. 24-11 Mounting Orientation E (Horizontal ccw) 30 Output Current INPUT Fig. 24-10 Mounting Orientation D (Horizontal cw) 20 A1 12 A2 6 Ambient Temperature 0 10 20 30 40 50 60°C Jan. 2018 / Rev. 0.5 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 32/32