400 Series™ 4-Wire Duct Smoke Detector A Division of Pittway 3825 Ohio Avenue, St. Charles, IL 60174 1-800-SENSOR2 (736-7672), Fax 630-377-6495 http://www.systemsensor.com Models Available DH400ACDCI Ionization Duct Smoke Detector DH400ACDCA Ionization Detector, ULC Listed DH400ACDCP Photoelectronic Duct Smoke Detector Features • • • • • • • • • • • 24 VAC/DC or 120/220 VAC operation Simple change-out of photo or ion detector heads Air velocity rating from 500 to 4000 FPM Powered outputs for remote LED and sounder Remote test station option Remote sounder option Equipped with a DPDT auxiliary relay (two Form C contacts) Easy and quick mounting to round or rectangular ducts from 1′ – 12′ wide Clear cover for convenient visual inspection UL 268A listed 3-year warranty System Sensor DH400ACDC 4-wire duct housing will accommodate either the 1451DH ionization sensor or the 2451 photoelectronic sensor. The twist-in, twist-out detector heads allow easy removal for quick cleaning and maintenance, or a change in application without removing the duct housing. The DH400ACDC samples air currents passing through a duct and gives dependable performance for management of fans, blowers, and air conditioning systems. WARNING: Duct smoke detectors have specific limitations. DUCT DETECTORS ARE: NOT a substitute for an open area smoke detector, NOT a substitute for early warning detection, and NOT a replacement for a building’s regular fire detection system. Refer to NFPA 72 and 90A for additional duct detector application information. Specifications Length: Width: Depth: Weight: Operating Temperature Range: 14.5 inches (37 cm.) 5 inches (12.7 cm.) 4 inches (10.2 cm.) 4.5 lbs. (2.0 kg.) Operating Humidity Range: Air Duct Velocity: 10% to 93% relative humidity 500 to 4000 ft./min. 32° to 120°F (0° to 49°C) APPROVED © System Sensor 8/96 This document is not intended to be used for installation purposes. A05-201-02 Architectural/Engineering Specifications The air duct smoke detector shall be a System Sensor Model DH400ACDC Series Duct Smoke Detector. The detector housing shall be UL listed per UL 268A specifically for use in air handling systems. The detector shall operate at air velocities of 500 feet per minute to 4000 feet per minute. The detector housing shall be equipped with an integral mounting base capable of accommodating either photoelectronic or ionization detector heads. It shall be capable of local testing via magnetic switch or remote testing using the RTS451KEY Remote Test Station. The duct detector housing shall incorporate an airtight smoke chamber in compliance with UL 268A, Standard for Smoke Detectors for Duct Applications. The housing shall be capable of mounting to either rectangular or round ducts without adapter brackets. An integral filter system shall be included to reduce dust and residue effects on detector and housing, thereby reducing maintenance and servicing. Sampling tubes shall be installed after the housing is mounted to the duct by passing through the duct housing. Terminal connections shall be of the strip and clamp method suitable for 14–18 AWG wiring. DUCT DETECTOR HOUSING CONDUIT HOLES INLET SAMPLING TUBE (SUPPLIED SEPARATELY) FOAM GASKETS TUBE END PLUG PC BOARD INSULATOR DUCT DETECTOR COVER SAMPLING TUBE MOUNTING SCREWS O-RINGS DETECTOR BASE HOUSING MOUNTING SCREWS EXHAUST FILTER ADAPTER DETECTOR HEAD Exploded View of DH400ACDC Duct Detector Components TEST MAGNET SAMPLING TUBE FILTERS Electrical Ratings – DH400ACDC Power Supply Voltage 20 - 29 VDC 24 VAC 50 - 60 Hz 120 VAC 50 - 60 Hz 220/240 VAC 50 - 60 Hz CURRENT REQUIREMENTS (USING NO ACCESSORIES) Max. standby current 25 mA 35 mA RMS 20 mA RMS 20 mA RMS Max. alarm current 95 mA 55 mA RMS 55 mA RMS 30 mA RMS CONTACT RATINGS Alarm initiation contacts (SPST) 2.0A @ 30 VAC/DC (0.6 power factor) Alarm auxiliary contacts (DPDT) 10A @ 30 VDC 10A @ 277 VAC (0.75 power factor) 240 VA @ 240 VAC (0.4 power factor) 1/8 HP @ 120 VAC 1/4 HP @ 240 VAC ACCESSORY CURRENT LOADS AT 24 VDC ALARM STANDBY DEVICE APA451 12mA MAX 30mA MAX PA400 0mA 15mA MAX RA400Z 0mA 7mA MAX RTS451KEY 0mA* 7mA MAX* ANY COMBINATION OF ACCESSORIES MAY BE USED SUCH THAT THE GIVEN CURRENT LOADS TOTAL: 100mA OR LESS IN THE STANDBY STATE, 150mA OR LESS IN THE ALARM STATE. Trouble contacts (SPST) Page 2 0.3A @ 32 VDC (resistive) *NOTE: WHEN INITIATING AN ALARM, THE RTS451 REQUIRES 71mA MAXIMUM IN PRE-ALARM AND 78mA MAXIMUM IN ALARM. NOMINAL STANDBY CURRENT IS 0mA. ALARM CURRENT IS 7mA MAXIMUM WHEN TEST MAGNET IS REMOVED. A05-201-02 DH400ACDC Wiring Guide AVAILABLE POWER INPUTS AVAILABLE POWER INPUTS 1 2 12 13 1 14 120 VAC 24V 2 12 13 120 VAC 24V 220/240 VAC 220/240 VAC 15 N.C. ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. 18 19 16 17 C. N.O. N.O. ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. 15 20 C. N.C. N.C. 16 C. 10 N.O. 19 20 C. FOR WIRING OF AUXILIARY DEVICES, REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS OR CONTACT MANUFACTURER. N.C. 10 TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY. CONTACTS OPEN WHILE DETECTOR HEAD OR POWER IS REMOVED, AND DURING RESET. OPEN CONTACTS SIGNAL TROUBLE CONDITION TO PANEL. 8 8 ALARM INITIATION CONTACTS CONTACTS SHOWN OPEN IN STANDBY. CONTACTS CLOSE IN ALARM. CONTACTS SHOWN OPEN IN STANDBY. CONTACTS CLOSE IN ALARM. 9 9 UL LISTED FIRE ALARM CONTROL PANEL N.O. 11 TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY. CONTACTS OPEN WHILE DETECTOR HEAD OR POWER IS REMOVED, AND DURING RESET. OPEN CONTACTS SIGNAL TROUBLE CONDITION TO PANEL. ALARM INITIATION CONTACTS 18 TROUBLE CONTACTS TROUBLE CONTACTS ALARM INITIATION LOOP 17 ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS. ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS. 11 CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR. SEE SPECIFICATIONS FOR ADDITIONAL POWER SUPPLY INFORMATION. 14 EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER LAST DETECTOR IN THE LOOP DH400ACDC FIRST DETECTOR IN THE LOOP DH400ACDC System Wiring Diagram for DH400ACDC 4-Wire Duct Smoke Detectors Using a UL Listed Control Panel CAUTION: Do not loop wire under terminals. Break wire run to provide supervision of connections. AVAILABLE POWER INPUTS 1 2 SEE SPECIFICATIONS FOR ADDITIONAL POWER SUPPLY INFORMATION. 12 13 14 120 VAC 24V 220/240 VAC ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. 15 FOR WIRING OF AUXILIARY DEVICES, REFER TO MANUFACTURER’S INSTALLATION INSTRUCTIONS OR CONTACT MANUFACTURER. 16 N.C. C. 17 18 N.O. 19 N.O. 20 C. N.C. ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS. ALARM INITIATION CONTACTS 8 9 N.O. TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY. CONTACTS OPEN WHILE DETECTOR HEAD OR POWER IS REMOVED, AND DURING RESET. OPEN CONTACTS SIGNAL TROUBLE CONDITION TO PANEL. 2 1 ALARM 5 COMMON 6 (+) ALARM SIGNAL (–) AUX POWER A78-2353-00 3 Wiring Diagram for DH400ACDC 4-Wire Duct Detector System Equipped Without a Control Panel 5 (+) ALARM SIGNAL (+) AUX POWER (–) 1 ALARM (+) SIGNAL 5 1 6 2 AUX POWER (–) 6 2 4 RESET (–) 3 3 RESET TEST (–) 4 5 TEST AUX POWER (–) 6 DUCT DETECTOR DH400ACDC (–) 4 RA400Z (OPTIONAL) REMOTE (LED) ANNUNCIATOR 3 RESET (–) 5 (+) AUX POWER (–) 6 DUCT DETECTOR DH400ACDC Page 3 4 TEST (–) ALARM SIGNAL (+) (–) PA400 (OPTIONAL) AUDIBLE ALERT DUCT DETECTOR DH400ACDC FIELD INSTALLED JUMPER 3 RESET 5 TEST RTS451 (OPTIONAL) REMOTE TEST STATION FIELD INSTALLED JUMPER 10 POWER 11 APA451 AUDIBLE PIEZO ALERT WITH ALARM AND POWER (TROUBLE) LEDS. FOR STAND ALONE APPLICATIONS ONLY. APA451 RECOMMENDED FOR COMPLIANCE TO NFPA 90A. LOCATE IN NORMALLY OCCUPIED AREA OF PREMISES. 5 ALARM SIGNAL (+) 7 (+) AUX POWER TROUBLE CONTACTS DH400ACDC DUCT DETECTOR SUPERVISORY 11 CONTACTS 10 { AUX POWER (+) 7 DH400ACDC Duct Smoke Detector 6 RTS451KEY Remote Test Station Wiring Diagrams for Optional Accessories A05-201-02 Ordering Information Part No. DH400ACDCI DH400ACDCA DH400ACDCP 1451DH 2451 Accessories ST-1.5 ST-3 ST-5 ST-10 APA451 RTS451 Description 4-wire ionization duct detector Same as above, Canadian model 4-wire photoelectronic duct detector Replacement ionization sensor head Replacement photoelectronic sensor head Metal sampling tube duct widths 1′–2′ Metal sampling tube duct widths 2′–4′ Metal sampling tube duct widths 4′–8′ Metal sampling tube duct widths 8′–12′ Annunciator with piezo alarm and power LEDs (see below) Remote test station RTS451KEY MOD400R PA400 RA400Z CRT400 F36-05-00 M02-04-00 P48-21-00 RS14 RS24 R59-18-00 A2650-01 Remote test station with key (see below) Sensitivity test module Piezo sounder Remote annunciator alarm LED Ion cover removal tool Replacement air filters (two per package) Test magnet End cap for metal sampling tubes Ion replacement screen Photo replacement screen Calibrated test card (for photo units only) Replacement installation kit (mounting hardware) APA451 Annunciator with Piezo Alarm and Power LEDs RTS451 Remote Test Station System Sensor Worldwide Distribution In Canada: System Sensor Canada 6581 Kitimat Road, Unit #7 Mississauga, Ontario Canada L5N 3T5 Telephone: 905-812-0767 Fax: 905-812-0771 Page 4 In the United Kingdom: System Sensor Europe, Ltd. Horsham Gates III, North St. Horsham, West Sussex RH13 5PJ, United Kingdom Telephone: 44-1403-276500 Fax: 44-1403-276501 In India: System Sensor India A-204 Maheshwari Nagar Orkay Mills Lane Andheri East, Mumbai 400093 Telefax: 91-022-8202564 In the Far East: System Sensor Pittway Far East, Ltd. Suite 706, New T&T Centre 7 Canton Road Tsimshatsui, Kowloon, Hong Kong Telephone: 852-2730-9090 Fax: 852-2736-6580 A05-201-02