Delta DRC-24V10W1AZ Chrome din rail power supply Datasheet

TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 10W 1 Phase (Class II & NEC Class 2) / DRC-24V10W1AZ
Highlights & Features
–
–
–
–
–
–
Protection Class II, Double Isolation
(No Earth connection is required)
Universal AC input voltage without power de-rating
Efficiency > 80.0% @ 115Vac & 230Vac
NEC Class 2 / Limited Power Source (LPS) certified
Overvoltage / Overcurrent / Over Temperature Protections
International safety approvals to ITE and Industrial standard
Safety Standards
CB Certified for worldwide use
Model Number:
DRC-24V10W1AZ
Unit Weight:
0.065 kg
Dimensions (L x W x D): 91 x 18 x 55.6 mm
General Description
The DRC-24V10W1AZ is part of the Chrome DIN Rail Power Supply series, which is designed for use in compact cabinets for home
automations and the food and beverage industry. Delta’s Chrome DIN Rail Power Supply series offers double isolated input. This
means that no Earth connection is required thus resulting in low leakage current. This product provides a universal input voltage range
of 90-264Vac, and a wide temperature range of -25°C to 71°C. The Chrome series is certified to safety standard according to
IEC/EN/UL 60950-1 Information Technology Equipment (ITE) and UL 508 Industrial Control Equipment (ICE). The series is also fully
compliant with RoHS Directive 2011/65/EU for environmental protection. NEC Class 2 and Limited Power Source (LPS) approvals are
available for this product.
Model Information
Chrome DIN Rail Power Supply
Model Number
Input Voltage Range
Output Voltage
Output Current
DRC-24V10W1AZ
90-264Vac (125-375Vdc)
24Vdc
0.42A
Model Numbering
DR
C–
24V
10W
1
A
Z
DIN Rail
Isolation Class II
Power Supply
Output Voltage
Output Power
Single Phase
Chrome Series
Plastic Case
1
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (January 2014, Rev. 00)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 10W 1 Phase (Class II & NEC Class 2) / DRC-24V10W1AZ
Specifications
Input Ratings / Characteristics
Nominal Input Voltage
100-240Vac
Input Voltage Range
90-264Vac
Nominal Input Frequency
50-60Hz
Input Frequency Range
47-63Hz
Nominal DC Input Voltage*
125-375Vdc
Input Current
< 0.30A @ 115Vac, < 0.20A @ 230Vac
Efficiency at 100% Load
> 80.0% @ 115Vac & 230Vac
Max Inrush Current
< 15A @ 115Vac, < 30A @ 230Vac
Power Factor
Conform to EN61000-3-2
Leakage Current
< 0.25mA @ 240Vac
*DC input voltage is not included in the UL approval. Additional testing might be necessary.
Output Ratings / Characteristics
Nominal Output Voltage
24Vdc
Output Voltage Tolerance
± 2% (initial set point tolerance from factory)
Output Current
0.42A
Output Power
10W
Line Regulation
< 1% typ. (@ 90-264Vac, 100% load)
Load Regulation
< 2% typ. (@ 90-264Vac, 100% load)
Residual Ripple / PARD (20MHz)
< 50mVpp / 150mVpp
Rise Time
< 100ms @ nominal input (100% load)
Start-up Time
< 3,000ms @ nominal input (100% load)
Hold-up Time
> 10ms @ 115Vac,
> 30ms @ 230Vac (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 10-100% load
Start-up with Capacitive Loads
3,000µF Max
Mechanical
Case Cover
Plastic
Dimensions (L x W x D)
91 x 18 x 55.6 mm
Unit Weight
0.065 kg
Indicator
Green LED (DC OK)
Cooling System
Convection
Terminal
Input
M4 x 2 Pins (Rated 300V/16A)
Output
M4 x 2 Pins (Rated 300V/16A)
Wire
AWG 26-12
Mounting Rail
Standard TS35 DIN Rail in accordance with EN60715
2
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (January 2014, Rev. 00)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 10W 1 Phase (Class II & NEC Class 2) / DRC-24V10W1AZ
Environment
Surrounding Air Temperature
Operating
-25°C to +71°C
Storage
-25°C to +85°C
Power De-rating
> 55°C de-rate power by 2.5% / °C
Operating Humidity
< 95% RH (Non-Condensing)
Operating Altitude
2,000 Meters
Shock Test (Operating)
IEC 60068-2-27, Half Sine Wave: 4G for a duration of
22ms, 3 shocks for each 3 directions, 9 times in total
Vibration (Operating)
IEC 60068-2-6, Sine Wave: 10-500Hz @ 19.6m/S² (2G
peak); 10 min per cycle, 60 min for all X, Y, Z directions
Pollution Degree
2
Protections
Overvoltage
< 34.8V, SELV Output, Latch-off Mode
Overload / Overcurrent
> 102~108% of rated load current,
Fold Forward Mode (current rises, voltage drops)
Over Temperature
> 75°C Surrounding Air Temperature @ 100% load,
Latch-off Mode
Short Circuit
Hicc-up Mode, Non-Latching
(Auto-Recovery when the fault is removed)
Degree of Protection
IP20
Protection Against Shock
Class II (No PE* connection is required)
*PE: Primary Earth
Reliability Data
MTBF
> 500,000 hrs. as per Telcordia SR-332
Expected Cap Life Time
10 years (115Vac & 230Vac, 50% load @ 40°C)
3
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (January 2014, Rev. 00)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 10W 1 Phase (Class II & NEC Class 2) / DRC-24V10W1AZ
Safety Standards / Directives
Electrical Safety
TUV Bauart to EN60950-1, UL/cUL recognized to
UL60950-1 and CSA C22.2 No. 60950-1, CB scheme to
IEC60950-1, Limited Power Source (LPS)
Industrial Control Equipment
UL/cUL listed to UL508 and CSA C22.2 No. 107.1-01
Class 2 Power Supply
UL/cUL recognized to UL60950-1, CSA C22.2 No.
60950-1
CE
In conformance with EMC Directive 2004/108/EC and
Low Voltage Directive 2006/95/EC
Material and Parts
RoHS Directive 2011/65/EU Compliant
Galvanic Isolation
Input to Output
3.0KVac
EMC
EMC / Emissions
CISPR22, EN55022, FCC Title 47: Class B
Immunity to
Electrostatic Discharge
IEC 61000-4-2
Level 3 Criteria A1)
Air Discharge: 8kV
Contact Discharge: 6kV
Radiated Field
IEC 61000-4-3
Level 3 Criteria A1)
80MHz-1GHz, 10V/M with 1kHz tone / 80% modulation
Electrical Fast Transient / Burst
IEC 61000-4-4
Level 3 Criteria A1)
2kV
Surge
IEC 61000-4-5
Level 3 Criteria A1)
Common Mode2): 2kV
3)
Differential Mode : 1kV
Conducted
IEC 61000-4-6
Level 3 Criteria A1)
150kHz-80MHz, 10Vrms
Power Frequency Magnetic Fields
IEC 61000-4-8
Criteria A1)
1A/Meter
Voltage Dips
IEC 61000-4-11
> 95% dip; 0.5 cycle (10ms)
Low Energy Pulse Test (Ring Wave)
IEC 61000-4-12
Level 3 Criteria A1)
Differential Mode3): 1kV
1) Criteria A: Normal performance within the specification limits
2) Asymmetrical: Common mode (Line to earth)
3) Symmetrical: Differential mode (Line to line)
4
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (January 2014, Rev. 00)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 10W 1 Phase (Class II & NEC Class 2) / DRC-24V10W1AZ
Block Diagram
Device Description
1)
2)
3)
4)
5
Input terminal block connector
Output terminal block connector
DC OK control LED (Green)
Universal mounting system
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (January 2014, Rev. 00)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 10W 1 Phase (Class II & NEC Class 2) / DRC-24V10W1AZ
Dimensions
L x W x D: 91 x 18 x 55.6 mm
Engineering Data
De-rating
Note
1.
2.
3.
4.
5.
Fig. 1
6
De-rating for Vertical Mounting Orientation
> 55°C de-rate power by 2.5% / °C
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (January 2014, Rev. 00)
Power supply components may degrade, or
be damaged, when the power supply is
continuously used outside the shaded region,
refer to the graph shown in Fig. 1.
If the output capacity is not reduced when the
surrounding air temperature >55°C, the
device may run into Over Temperature
Protection. When activated, the output
voltage will go into latch-off mode and
recoverable by AC power recycle.
In order for the device to function in the
manner intended, it is also necessary to keep
a safety distance of 25mm with adjacent units
while the device is in operation.
Depending
on
the
surrounding
air
temperature and output load delivered by the
power supply, the device can be very hot!
If the device has to be mounted in any other
orientation, please do not hesitate to contact
[email protected] for more details.
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 10W 1 Phase (Class II & NEC Class 2) / DRC-24V10W1AZ
Output De-rating VS. Input Voltage

No output power de-rating across the entire
input voltage range
Assembly & Installation
The power supply unit (PSU) can be mounted on 35mm DIN rails in accordance with EN60715. The device should be installed with
input terminal block at the bottom.
Each device is delivered ready to install.
Mounting
Dismounting
Fig. 2.1 Mounting
Fig. 2.2 Dismounting
Snap on the DIN rail as shown in Fig. 2.1:
1. Tilt the unit upwards and insert it onto the DIN rail.
2. Push downwards until stopped.
3. Press against the bottom front side for locking.
4. Shake the unit slightly to ensure that it is secured.
To uninstall, pull or slide down the latch with screw driver as
shown in Fig. 2.2. Then slide the power supply unit (PSU) in
the opposite direction, release the latch and pull out the power
supply unit (PSU) from the rail.
7
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (January 2014, Rev. 00)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 10W 1 Phase (Class II & NEC Class 2) / DRC-24V10W1AZ
Safety Instructions
–
–
–
–
–
–
–
ALWAYS switch mains of input power OFF before connecting and disconnecting the input
voltage to the unit. If mains are not turned OFF, there is risk of explosion / severe damage.
To guarantee sufficient convection cooling, keep a distance of 50mm above and
below the device as well as a lateral distance of 25mm to other units.
Note that the enclosure of the device can become very hot depending on the surrounding
air temperature and load of the power supply. Risk of burns!
DO NOT insert any objects into the unit.
Hazardous voltages may be present for up to 5 minutes after the input mains voltage is
disconnected. Do not touch the unit during this time.
The power supplies unit should be installed in minimum IP54 rated enclosure.
The power supplies are built in units and must be installed in a cabinet or room
(condensation free environment and indoor location) that is relatively free of conductive
contaminants.
Functions
■ Graph illustrating the Start-up Time, Rise Time, and Hold-up Time
Start-up Time
The time required for the output voltage to reach 90% of its set value, after the input voltage is applied.
Rise Time
The time required for the output voltage to change from 10% to 90% of its set value.
Hold-up Time
Hold up time is the time when the AC input collapses and output voltage retains regulation for a certain period of time. The time
required for the output to reach 90% of its set value, after the input voltage is removed.
8
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (January 2014, Rev. 00)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 10W 1 Phase (Class II & NEC Class 2) / DRC-24V10W1AZ
Inrush Current
Overload & Overcurrent Protections
Inrush current is the peak, instantaneous, input current measured
and, occurs when the input voltage is first applied. For AC input
voltages, the maximum peak value of inrush current will occur
during the first half cycle of the applied AC voltage. This peak
value decreases exponentially during subsequent cycles of AC
voltage.
The power supply’s Overload (OLP) and Over current (OCP)
Protections will be activated when output current is >102~108%
of IO (Max load). In such occurrence, the VO will start to droop and
once the power supply has reached its maximum power limit, the
protection is activated and the power supply will go into “Hiccup
mode” (Auto-Recovery). The power supply will recover once the
fault condition of the OLP and OCP is removed and IO is back
within the specifications.
Dynamic Response
Additionally, if the IO is >102~108% for a prolong period of time
(depending on the load), the Over Temperature Protection (OTP)
will be activated due to high temperature on critical components.
The power supply will then go into “Latch-off mode” until the PSU
cools down and the AC power is recycled.
The power supply output voltage will remains within ±5% of its
steady state value, when subjected to a dynamic load from 10 to
100% of its rated current.
Over Temperature Protection
As mentioned above, the power supply also has Over
Temperature Protection (OTP). This is activated when the
overload condition persists for an extended duration and the
output current is below the overload trigger point but >100% load.
In the event of a higher operating condition at 100% load, the
power supply will run into OTP when the surrounding air
temperature is >75°C. When activated, the output voltage will go
into latch-off mode until the component temperature cools down
and the AC power is recycled.
Overvoltage Protection
The power supply’s overvoltage circuit will be activated when its
internal feedback circuit fails. The output voltage shall not exceed
its specifications defined on Page 3 under “Protections”.
9
Short Circuit Protection
The power supply’s output OLP/OCP function also provides
protection against short circuits. When a short circuit is applied,
the output current will operate in “Hiccup mode”, as shown in the
illustration in the OLP/OCP section on this page. The power
supply will return to normal operation after the short circuit is
removed.
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (January 2014, Rev. 00)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 10W 1 Phase (Class II & NEC Class 2) / DRC-24V10W1AZ
Operating Mode
Fig. 3
Redundancy / Parallel Operation Connection Diagram

Redundancy Operation
In order to ensure proper redundancy operation for the power supply unit (PSU), ensure that the output voltage difference between the
two units is kept at 0.45~0.50V for 24V supplies. Follow simple steps given below to verify:
Step 1.
Measure output voltage of PSU 1 and PSU 2. If PSU 1 is the master unit, then VO of PSU 1 must be higher than PSU 2. In order to set
the output voltage, connect the power supply to 50% load and set the PSU 1 and PSU 2 output voltage.
Step 2.
Connect the right DRR module, 20A as per the system requirement to the power supply units PSU 1 and PSU 2 at Vin 1 & Vin 2
respectively.
Step 3.
Connect the system load from Vout. Please note that output voltage Vout from DRR module will be = VO (output voltage of power
supply) – Vdrop* (in DRR module).

Parallel Operation
These DRR modules can also be used for Parallel function in order to increase the output power by N+1 (e.g. 2.5A + 2.5A = 5A or 2.5A
+ 2.5A + 2.5A = 7.5A) or current sharing, and thus increasing the power supply and system reliability. Though the DRC-24V10W1AZ is
not designed for current sharing, a good current sharing between two power supplies can be achieved by following simple steps as
below (Refer to Fig. 3 for the Connection Diagram).
Step 1.
Set output load condition for both supplies at 50% and measure
the output voltages.
Step 2.
Adjust output voltages to the same level or within ±25mV
difference.
Step 3.
Connect PSU 1 and PSU 2 with the DRR-20A module and
measure at Vin 1 & Vin 2 to verify the voltage difference. Ensure
the voltages are within ±25mV.
Step 4.
Output voltage from DRR module Vout will be = VO (output
voltage of power supply) – Vdrop* (in DRR module).
*Vdrop will vary from 0.60V to 0.90V (Typical 0.65V) depending on the load current and surrounding air temperature.
10
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (January 2014, Rev. 00)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 10W 1 Phase (Class II & NEC Class 2) / DRC-24V10W1AZ
Others
Delta RoHS Compliant
Restriction of the usage of hazardous substances
The European directive 2011/65/EU limits the maximum impurity level of homogeneous materials such as lead,
mercury, cadmium, chrome, polybrominated flame retardants PBB and PBDE for the use in electrical and
electronic equipment. RoHS is the abbreviation for “Restriction of the use of certain hazardous substances in
electrical and electronic equipment”.
This product conforms to this standard.
11
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (January 2014, Rev. 00)
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Delta:
DRC-24V10W1AZ
Similar pages