MACOM CDSUX-C Cdsux-c series - extended range buffer network Datasheet

Catalog: 1654986
Issue Date: 06.2011
Corcom Facility EMI Filters Product Guide
CDSUX-C Series - Extended Range Buffer Networks
CDSUX-C Series
Features
60 Hz Models Only
• Sealed, constructed of 16 gauge cold rolled steel
• All non-conductive surfaces protected with suitable
painting or electroplating
• Removable input cover for terminal access and field
wiring connection
• Threaded conduit fitting with flexible lead on the load
side
• Knockouts provided on the input side
• Discharge bleeder resistor provided to reduce shock
hazard
• Surge protector provided upon request
Electrical Characteristics
Voltage Drop:
Less than 1% @ unity power factor
Overload:
140% of rated current for 15 minutes
Harmonic Distortion:
Less than 2% @ full rated current
Dielectric Withstanding Voltage:
Per MIL-PRF-15733 and UL1283
D.C. Insulation Resistance:
Per MIL-STD-202, Method 302
Terminal Strength:
Per MIL-STD-202, Method 211, Condition E
Temperature Rise:
Per MIL-PRF-15733 and UL1283
R.F. Radiation:
100 dB minimum shielding effectiveness
Insertion Loss:
100 dB from 14 kHz - 10 GHz per MIL-STD-220A, under
load condition, using extended range buffer networks
over the frequency range of 14 kHZ - 20 MHz
Applicable Publications:
MIL-PRF-15733 — Filters, radio interference
MIL-STD-202 — Test methods for Components
How to Order:
CDSUX 2 030 A6 - C - S
Surge Arrestors (optional)
Conduit Fitting (supplied)
Voltage/Frequency
MIL-STD-220A — Test method of Insertion Loss
MIL-STD-285 — Test method for Shielding Effectiveness
NFPA 70-1987 — National Electric Code
486A - 1983 — Wire Connectors and Lug
UL1283 — UL standard for EMI Filters
1
A6 - 120/208V, 60Hz
B6 - 277/480V, 60Hz
A4 - 120/208V, 400Hz
Current Rating 2
# of Filters
Series
Examples: CDSUX2030A6-C-S, CDSUX1010B6-C
16
Note 1:
Surge Arrestor for A6/A4* Models: V251BA60
Surge Arrestor for B6 Models: V481BA60
Note 2:
Current configuration listed as 3 digits with leading zeros
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric
equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.
USA Cust. Svc.:
Corcom Prods:
1-800-468-2023
1-847-680-7400
te.com
corcom.com
Catalog: 1654986
Issue Date: 06.2011
Corcom Facility EMI Filters Product Guide
CDSUX-C Series - Extended Range Buffer Networks (continued)
A
E
Knockouts for
0.75 (19.05) & 1.0 (25.4)
Conduit
3 Places
Label
B
Label
F
Label
2
D
Corcom Facility EMI Filters — Stand-Alone Filters
1/2 D
C
2.0
50.8
14.0 ± 1.0
355.6 ± 25.4
Ground Stud
& Lug
1.0 (25.4) NPT Supplied
with RF Gasket,
Flange Nut and
Insulating Bushing
Insulated wire
Type THHN
CDSUX
Rated
Current
1010**-C
10A
2010**-C
2 @ 10A
1030**-C
30A
2030**-C
2 @ 30A
1060**-C
60A
1100**-C
100A
1150**-C
150A
1225**-C
225A
Dimensions
A
±.063 [1.6]
21.0
533.4
21.0
533.4
26.0
660.4
26.0
660.4
32.0
812.8
34.0
863.6
41.0
1041.4
41.0
1041.4
B
±.063 [1.6]
4.0
101.6
8.0
203.2
6.0
152.4
12.0
304.8
8.0
203.2
8.0
203.2
10.0
254.0
10.0
254.0
C
±.063 [1.6]
5.0
127.0
5.0
127.0
6.0
152.4
6.0
152.4
6.0
152.4
6.0
152.4
6.0
152.4
6.0
152.4
D
5.0
127.0
5.0
127.0
5.0
127.0
5.0
127.0
6.0
152.4
8.0
203.2
9.0
228.6
9.0
228.6
E
3.0
76.2
5.5
139.7
4.0
101.6
9.0
228.6
5.5
139.7
5.5
139.7
9.0
228.6
9.0
228.6
F
.31 x .50
7.87 x 12.7
.43 x .75
10.9 x 19.1
.31 x .50
7.87 x 12.7
.43 x .75
10.9 x 19.1
.43 x .75
10.9 x 19.1
.43 X .75
10.9 x 19.1
.43 X .75
10.9 x 19.1
.43 X .75
10.9 x 19.1
*400Hz filters available upon request. Will require external power factor correction coil.
Please contact TE Connectivity Application Engineering 1-847-573-6517.
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric
equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.
USA Cust. Svc.:
Corcom Prods:
Wire Gauge
(AWG/mm2)
10
5.26
10
5.26
6
13.20
6
13.20
6
13.20
2
33.6
0
53.5
250 MCM
126.0
Approx. Weight
(Pounds/KG)
15
6.80
30
13.6
30
13.6
60
27.2
60
27.2
70
31.8
90
40.8
120
54.4
Max. Operating Voltage
A6:
120/208V, 60 Hz
B6:
277/480V, 60 Hz
A4*:
120/208V, 400 Hz
1-800-468-2023
1-847-680-7400
17
te.com
corcom.com
Similar pages