Chinfa AMR4-05 Ac - dc din rail mountable power supply industrial control equipment Datasheet

AMR4 SERIES
AC - DC DIN RAIL MOUNTABLE POWER SUPPLY
INDUSTRIAL CONTROL EQUIPMENT
FEATURES
‧UNIVERSAL INPUT 90~264VAC
‧SHORT CIRCUIT PROTECTION
‧INTERNAL INPUT FILTER
‧LOW PROFILE FOR BUILDING AUTOMATION
R
R
R
H H H
Class I, Div 2
MODEL LIST
a
UL 60950-1
UL 1310
IND. CONT. EQ.
UL 508
EN 60950-1
OUTPUT
CURRENT
EFF.
(min.)
EFF.
(typ.)
+ 5 VDC
7000 mA
78%
80%
54 WATTS
+ 12 VDC
4500 mA
82%
84%
60 WATTS
+ 15 VDC
4000 mA
83%
85%
60 WATTS
+ 24 VDC
2500 mA
84%
86%
MODEL NO.
INPUT
VOLTAGE
AMR4-05
90~264 VAC
35 WATTS
AMR4-12
90~264 VAC
AMR4-15
90~264 VAC
AMR4-24
90~264 VAC
OUTPUT
OUTPUT
WATTAGE
VOLTAGE
Single Output Models
SPECIFICATION
o
All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed
GENERAL
Characteristics
Vi nom, Io nom
Input-Output
Isolation resistance
Ambient temperature
Input-Output, @ 500VDC
Operating at Vi nom
Derating (see derating curve)
Storage temperature
Relative humidity
o
55
100
2.5
Vi nom, Io nom
Vi nom, Io min
unit
KHz
VAC / VDC
MΩ
+ 71
-40
Vi nom, from +56 C to +71 C
Non operational
Bellcore Issue 6 @40 oC, GB
Installation position
Pollution degree
max.
o
MTBF
Dimension
Cooling
typ.
45
3000/4242
Temperature coefficient
Altitude during operation
min.
Conditions
Switching frequency
Isolation voltage
-40
+ 85
20
95
± 0.03
o
C
% / oC
o
C
% RH
% / oC
5V model
595000
Hours
12V model
15V model
582000
Hours
582000
Hours
24V model
608000
IEC 60068-2-13
4850
Hours
m
mm
L91 x W71x D56.5
Free air convection
Vertical ( other direction may derating using )
2
INPUT SPECIFICATIONS
Characteristics
min.
Conditions
Rated input voltage
Absolute input max. range
Io nom
Ta min ... Ta max, Io nom
Input current
Vi : 115 / 230 VAC,
Io nom
5V model
12V, 15V, 24V models
Vi : 90 VAC, Io nom
5V model
12V, 15V, 24V models
Rated input current
Line frequency
Vi nom, Io nom
Inrush current
Power dissipation
Vi : 115 / 230 VAC , Io nom
www.chinfa.com
2011.01.28
Vi : 230 VAC, Io nom
AC in
100
90
DC in
120
typ.
max.
VAC
VAC
375
VDC
0.7 / 0.43
A
1.1 / 0.6
A
1.0
47
5V model
8.8
12V model
10.2
unit
240
264
A
1.5
A
63
30 / 60
Hz
A
W
W
[email protected]
P1
AMR4 SERIES
SPECIFICATION
o
All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed
INPUT SPECIFICATIONS
Characteristics
Power dissipation
Leakage current
min.
Conditions
Vi : 230 VAC, Io nom
typ.
15V model
10
24V model
9.9
max.
unit
W
W
Input-Output
0.25
mA
OUTPUT SPECIFICATIONS
Characteristics
Conditions
min.
Output voltage accuracy
(Adjusted before shipment)
Vi nom, Io max
0
Minimum load
Line regulation
Vi nom
Io nom, Vi min ...Vi max
0
Load regulation
Vi nom, Io min ...Io nom
Vi nom,
0.8 Io nom
Voltage trim range
Rated continuous loading
Vi nom,
Turn on time
Rise time
Vi nom, Io nom
Vi nom, Io nom
Vi nom, Io nom
Vi nom, Io nom
14
16.5
24V model
5V model
24
DC ON indicator threshold
at start up (Green LED)
Vi nom, Io nom
ms
1000
ms
1500
ms
150
ms
500
ms
150
ms
2
50
ms
Vi nom, Io nom
mV
7.5
VDC
12V model
15V model
18
VDC
22
35
VDC
3500
VDC
μF
5V model
3.5
4.5
VDC
12V model
15V model
9
10.8
VDC
11
13.5
VDC
24V model
5V model
19.2
21.6
VDC
3.5
4.5
VDC
12V model
15V model
9
10.8
VDC
11
13.5
VDC
24V model
Efficiency
ms
5V model
24V model
Vi nom, Io nom
VDC
2.5A @ 24VDC / 2.1A @ 28VDC
Vi nom, 1~0.5 Io nom
Capacitor load
VDC
4A @ 15VDC / 3.6A @ 16.5VDC
with 3500μF CAP
Vi nom, Io nom
VDC
28
7A @ 5VDC / 6.3A @ 5.5VDC
with 3500μF CAP
Power back immunity
%
4.5A @ 12VDC / 3.8A @ 14VDC
12 / 60
Vi nom, Io nom, BW = 20MHz
VDC
12
13.5
15V, 24V models
Ripple & noise
%
12V model
15V model
16 / 60
Vi nom, Io nom
DC LOW indicator threshold
after start up (Red LED)
%
±1
5
5V, 12V models
Fall time
Transient recovery time
%
+1
5V model
24V model
Vi : 115 / 230 VAC,
Io nom
unit
max.
±1
5.5
12V model
15V model
Hold up time
typ.
Vi nom, Io nom, Po / Pi
VDC
19.2
21.6
Up to 86%, See model list and typ efficiency curve
CONTROL AND PROTECTION
Characteristics
min.
Conditions
Input fuse
Internal surge voltage protection
Rated over load protection
Over voltage protection
typ.
max.
IEC 61000-4-5
Vi nom (see typ current limited curve)
Vi nom, Io nom
(Auto Recovery)
Varistor
110
150
%
5V model
5.75
6.5
VDC
12V model
15V model
15
16.5
VDC
18
20
VDC
24V model
30
33
VDC
Output short circuit
Fold forward
Degree of protection
IP20
www.chinfa.com
2011.01.28
unit
T2A / 250VAC internal
[email protected]
P2
AMR4 SERIES
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed
APPROVALS AND STANDARDS
UL / cUL
UL 508 Listed
UL 60950-1, UL 1310 Class 2 Power (only 5V w/o Class 2) Recognized
ISA 12.12.01(Class I, Division 2, Groups A, B, C and D)
TUV
EN 60950-1, CB scheme
CE
EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3
EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3
EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3
EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11
ENV 50204 Level 2, EN 61204-3
Vibration resistance
meet IEC 60068-2-6 (Mounting by rail : 10-500 Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis )
Shock resistance
meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 Faces, 3 times for each Face)
PHYSICAL CHARACTERISTICS
Case size
91 x 71 x 56.5 mm (3.58 x 2.8 x 2.22 inches)
Case material
Plastic
Weight
250g
Packing
0.31kg ; 48
/ 16kg / 2.28CUFT
MECHANISM & PIN CONFIGURATION
mm [inch]
CONSTRUCTION
Easy snap-on mounting onto the DIN-Rail
(TS35/7.5 or TS35/15), unit sits safely and
firmly on the rail; no tools required even to remove
71.00 [2.80]
INSTALLATION
12. 00 [0. 47]
45. 00 [1. 77]
N
5
6
56.50 [2.22]
51.50 [2.02]
L
49.85 [1.96]
Vout ADJ.
DC LO
DC ON
91.00 [3.58]
11. 00 [0. 43]
32.45 [1.28]
4 3 2 1
+ +
91. 00 [3. 58]
Ventilation / Cooling
Normal convection
All sides 25m/m free space
For cooling recommended
Connector size range
AWG24-12 (0.2~2.5mm2) flexible / solid cable
-Connector can withstand torque at maximum
6 pound-inches.
7m/m stripping at cable end recommends.
Use copper conductors only, 60/75 oC
GENERAL TOLERANCE
0.00[0.00] - 30.00[1.18]
±0.30[0.01]
30.00[1.18] - 120.00[4.72]
±0.50[0.02]
PIN ASSIGNMENT
Designation
1
-
Negative output terminal
2
-
Negative output terminal
+
Positive output terminal
4
+
Positive output terminal
5
L
Input terminals (phase conductor, no polarity at DC input)
N
Input terminals (neutral conductor, no polarity at DC input)
Vout ADJ.
Trimmer-potentiometer for Vout adjustment
DC ON
Operation indicator LED
DC LO
DC Low indicator LED
OTHER
6
IN
3
OUT
PIN NO.
www.chinfa.com
2011.01.28
Description
[email protected]
P3
AMR4 SERIES
CIRCUIT SCHEMATIC
‧Block diagram for AMR4 series
Fuse
L
Line
Filter
N
Vo +
Inrush Current
Switching
Limiter and
Device
rectifier
Rectifier
Vo -
PWM
Controller
Opto Isolation
Reference &
Error Amp.
Opto Isolation
Over Voltage
Detection
Vout
ADJ.
Output Level
Detection
DC ON
(Green LED)
DC LO
(Red LED)
TYP. CURRENT LIMITED CURVE
Output Voltage [ % ]
AMR4-24
100
75
230 Vac
115 Vac
50
25
0
100
110
120
130
140
150
160
Power out [ % ]
DERATING CURVE
TYP. EFFICIENCY CURVE
AMR4-24
87
EFFICIENCY [ % ]
Power out [ % ]
100
62.5
85
83
81
79
230 Vac
115 Vac
77
75
73
0
-40
www.chinfa.com
2011.01.28
56
Temperature [ oC ]
71
10
25
50
75
100
Power out [ % ]
[email protected]
P4
Similar pages