EPCOS B84143B0150S021 Emc filter Datasheet

EMC filters
3-line filters
for converters and power electronics
Rated current 150 to 2500 A
Series/Type:
B84143B*S020 … S024
Date:
January 2006
 EPCOS AG 2006. Reproduction, publication and dissemination of this data sheet and the
information contained therein without EPCOS’ prior express consent is prohibited.
3-line filters
B84143B*S020 … S024
for converters and power electronics
Power line filters for 3-phase systems
Rated voltages 530/310, 690/400, 760/440 V AC
Rated current 150 to 2500 A
Alternative version
■ Series B84143B*S080 and B84143B*S081
offers a low-cost solution.
Construction
■ 3-line filter
■ Metal case
Features
■
■
■
■
■
■
Optimized leakage current
Easy to install
Very compact design
Optimized for operation under full load
Low weight
UL, cUL approval
Applications
■
■
■
■
B84143B*S024 for IT mains supply
Frequency converters for motor drives
Wind farms
Power supplies
Terminals
■ Busbars
Marking
Marking on component:
Manufacturer’s logo, ordering code,
rated voltage, rated current, rated temperature,
climatic category, date code
Minimum marking on packaging:
Manufacturer’s logo, ordering code
Please read Cautions and warnings and
Important notes at the end of this document.
2
01/06
3-line filters
B84143B*S020 … S024
for converters and power electronics
Typical circuit diagram
LINE
LOAD
L1
L1’
L2
L2’
L3
L3’
SSB2130-I
Technical data and measuring conditions
Rated voltage VR
Type S020: 530/310 V AC, 50/60 Hz
Type S021: 760/440 V AC, 50/60 Hz
Type S024: 690/400 V AC, 50/60 Hz (Filters for IT mains
supply. See also Chapter “General”, Section 7.4)
Rated current IR
Referred to 40 °C ambient temperature
Test voltage Vtest
Type S020:
2280 V DC, 2 s (line/line)
2690 V DC, 2 s (lines/case)
Type S024:
2980 V DC, 2 s (line/line)
2890 V DC, 2 s (lines/case)
Type S021:
3270 V DC, 2 s (line/line)
2890 V DC, 2 s (lines/case)
Overload capability (thermal)
1.5 · IR for 3 min per hour or
2.5 · IR for 30 s per hour
Leakage current Ileak
At VR, 50 Hz
Climatic category (IEC 60068-1)
25/100/21 (– 25 °C/+100 °C/21 days damp heat test)
Approvals
UL 1283; CSA C22.2 No.8
(Type S020: 500/290 V; Type S021 and S024: 600/350 V)
Please read Cautions and warnings and
Important notes at the end of this document.
3
01/06
3-line filters
B84143B*S020 … S024
for converters and power electronics
Characteristics and ordering codes
VR
AC
V
IR
Ileak
Rtyp
A
mA
µΩ
150
< 20
140
180
< 20
250
Approx.
weight
kg
Ordering code
Approvals
13
B84143B0150S020
×
×
140
13
B84143B0180S020
×
×
< 20
63
15
B84143B0250S020
×
×
320
< 20
67
21
B84143B0320S020
×
×
400
< 20
67
21
B84143B0400S020
×
×
600
< 20
52
22
B84143B0600S020
×
×
1000
< 20
33
28
B84143B1000S020
×
×
1600
< 20
22
34
B84143B1600S020
×
×
2500
< 20
15
105
B84143B2500S020
×
×
Type S020
530/310
500/290 V
Type S021
760/440
600/350 V
150
< 28
140
13
B84143B0150S021
×
×
180
< 28
140
13
B84143B0180S021
×
×
250
< 28
63
15
B84143B0250S021
×
×
320
< 28
67
21
B84143B0320S021
×
×
400
< 28
67
21
B84143B0400S021
×
×
600
< 28
52
22
B84143B0600S021
×
×
1000
< 28
33
28
B84143B1000S021
×
×
1600
< 28
22
34
B84143B1600S021
×
×
2500
< 28
15
105
B84143B2500S021
×
×
Type S024 (Filters for IT mains supply1))
690/400
600/350 V
150
< 905
140
13
B84143B0150S024
×
×
180
< 905
140
13
B84143B0180S024
×
×
250
< 905
63
15
B84143B0250S024
×
×
320
< 905
67
21
B84143B0320S024
×
×
400
< 905
67
21
B84143B0400S024
×
×
600
< 905
52
22
B84143B0600S024
×
×
1000
< 905
33
28
B84143B1000S024
×
×
1600
< 905
22
34
B84143B1600S024
×
×
2500
< 905
15
105
B84143B2500S024
×
×
× = approval granted
1) Filters for IT mains supply. (See also Chapter “General”, Section 7.4)
Please read Cautions and warnings and
Important notes at the end of this document.
4
01/06
3-line filters
B84143B*S020 ... S024
for converters and power electronics
Dimensional drawings
B84143B0150S02*, B84143B0180S02* (150 A, 180 A)
2 x M5 x 5
120±0.3
30
PE M10 x 30
10
10
310±2
141
2
36
81
91
20
ø9
80
140
260
115±0.2
32±1
LINE
LOAD
155±0.2
170
Marking
L3’ L2’ L1’
3
L3 L2 L1
32±1
6.6
SSB2142-7
B84143B0250S02* (250 A)
2 x M6 x 6
110±0.3
30
PE M10 x 30
15
1
36
90
115
25
ø11
15
360±7
80
140
300
240±1
LINE
LOAD
165±1
190
Marking
60
L3’ L2’ L1’
5
L3 L2 L1
60
ø12
40±1
40±1
Please read Cautions and warnings and
Important notes at the end of this document.
SSB2143-F
5
01/06
3-line filters
B84143B*S020 … S024
for converters and power electronics
B84143B0320S02*, B84143B0400S02* (320 A, 400 A)
4 x M6 x 6
30
15
15
360±2
300
240±1
LOAD
L2’
235±1
260
LINE
L3’
L1
L2
5
Marking
L3
60
L1’
60
120
180±0.5
210
2
16
36
91
25
85±0.5
116
PE M10 x 30
ø11
ø12
42±2
42±2
SSB2144-N
B84143B0600S02* (600 A)
15
15
410±2.5
350
290±1
LOAD
L2’
235±1
260
LINE
L3’
L1
L2
5
Marking
L3
60
L1’
60
120
180±0.5
210
ø12
42±3
42±3
Please read Cautions and warnings and
Important notes at the end of this document.
SSB2145-W
6
01/06
2
16
85±0.5
116
30
36
30
4 x M6 x 6
91
PE M10 x 30
ø11
3-line filters
B84143B*S020 … S024
for converters and power electronics
B84143B1000S02* (1000 A)
40
135±0.8
166
4 x M6 x 6
20
20
420±2.5
350
290±1
160
220±0.8
250
65
L2
L2’
Marking
LOAD
L3
L3’
LINE
275±1
300
8
L1
L1’
65
2.5
16
61
40
141
PE M12 x 30
ø14
ø12
52±3
52±3
SSB2146-5
B84143B1600S02* (1600 A)
400
340±1
105
141
105
61
20
160
L3
LOAD
L3
LINE
92±3
275±1
300
L2
L2
Marking
40
220±0.8
250
L1
10
L1
4 x M6 x 6
92±3
ø12
2.5
16
20
550±3
135±0.8
166
50
ø14
40
40
PE M12 x 30
Please read Cautions and warnings and
Important notes at the end of this document.
7
01/06
SSB1210-5
3-line filters
B84143B*S020 … S024
for converters and power electronics
B84143B2500S02* (2500 A)
650
560±1.5
125
191.5
91.5
125
20
200
L3
LOAD
L3
LINE
93±3
355±1
385
L2
L2
Marking
60
286±1
320
L1
15
L1
4 x M6 x 6
93±3
ø14
3.5
16.5
20
810±3.5
40
80
40
40
190±1
221.5
ø14
Please read Cautions and warnings and
Important notes at the end of this document.
PE M16 x 50
8
01/06
SSB1211-D
3-line filters
B84143B*S020 … S024
for converters and power electronics
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Filters for 150 … 250 A (Type S020)
Filters for 320 … 1000 A (Type S020)
100
dB B84143B0150 ... B0250S020
SSB2131-R
α
100
dB B84143B0320 ... B1000S020
SSB2132-Z
α
80
80
60
60
40
40
20
20
0 4
10
10 5
10 6
10 7
0 4
10
Hz 10 8
f
Filters for 1600 and 2500 A (Type S020)
SSB1800-Z
100
B84143B1600S020
B84143B2500S020
dB
α
80
60
40
20
0
10 4
10 5
10 6
10 7
Hz 10 8
f
Please read Cautions and warnings and
Important notes at the end of this document.
9
01/06
10 5
10 6
10 7
Hz 10 8
f
3-line filters
B84143B*S020 … S024
for converters and power electronics
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Filters for 150 … 250 A (Type S021)
Filters for 320 … 1000 A (Type S021)
SSB2133-8
100
dB
α
100
dB B84143B0320 ... B1000S021
SSB2134-G
α
80
80
60
60
40
40
20
20
B84143B0150 ... B0250S021
0 4
10
10 5
10 6
10 7
0 4
10
Hz 10 8
f
Filters for 1600 and 2500 A (Type S021)
SSB1204-V
100
α
B84143B1600S021
B84143B2500S021
dB
80
60
40
20
0
10 4
10 5
10 6
10 7
Hz 10 8
f
Please read Cautions and warnings and
Important notes at the end of this document.
10
01/06
10 5
10 6
10 7
Hz 10 8
f
3-line filters
B84143B*S020 … S024
for converters and power electronics
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Filters for 150 … 250 A (Type S024)
Filters for 320 … 1000 A (Type S024)
100
dB B84143B0150 ... B0250S024
SSB2135-P
α
100
dB
SSB2136-X
α
80
80
60
60
40
40
20
20
0 4
10
10 5
10 6
10 7
B84143B0320 ... B1000S024
0 4
10 5
10 6
10 7
10
Hz 10 8
f
Filters for 1600 and 2500 A (Type S024)
SSB1801-8
100
B84143B1600S024
B84143B2500S024
dB
α
80
60
40
20
0
10 4
10 5
10 6
10 7
Hz 10 8
f
Please read Cautions and warnings and
Important notes at the end of this document.
11
01/06
Hz 10 8
f
EMC filters
Cautions and warnings
Important information
Please read all safety and warning notes carefully before installing the EMC filter and putting it into
operation (see
). The same applies to the warning signs on the filter. Please ensure that the signs
are not removed nor their legibility impaired by external influences.
Death, serious bodily injury and substantial material damage to equipment may occur if the appro­
priate safety measures are not carried out or the warnings in the text are not observed.
Using according to the terms
The EMC filters may be used only for their intended application within the specified values in low­
voltage networks in compliance with the instructions given in the data sheets and the data book.
The conditions at the place of application must comply with all specifications for the filter used.
Warnings
■ It shall be ensured that only qualified persons (electricity specialists) are engaged on work such
■
■
■
■
as planning, assembly, installation, operation, repair and maintenance. They must be provided
with the corresponding documentation.
Danger of electric shock. EMC filters contain components that store an electric charge. Danger­
ous voltages can continue to exist at the filter terminals for longer than five minutes even after
the power has been switched off.
The protective earth connections shall be the first to be made when the EMC filter is installed and
the last to be disconnected. Depending on the magnitude of the leakage currents, the particular
specifications for making the protective-earth connection must be observed.
Impermissible overloading of the EMC filter, such as impermissible voltages at higher frequen­
cies that may cause resonances etc. can lead to destruction of the filter housing.
EMC filters must be protected in the application against impermissible exceeding of the rated
currents by suitable overcurrent protective.
12
01/06
EMC filters
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical
requirements that are often placed on our products in the areas of application concerned. We
nevertheless expressly point out that such statements cannot be regarded as binding
statements about the suitability of our products for a particular customer application. As
a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them
than the customers themselves. For these reasons, it is always ultimately incumbent on the
customer to check and decide whether an EPCOS product with the properties described in the
product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of passive electronic components
or failure before the end of their usual service life cannot be completely ruled out in the
current state of the art, even if they are operated as specified. In customer applications
requiring a very high level of operational safety and especially in customer applications in which
the malfunction or failure of a passive electronic component could endanger human life or health
(e.g. in accident prevention or life-saving systems), it must therefore be ensured by means of
suitable design of the customer application or other action taken by the customer (e.g.
installation of protective circuitry or redundancy) that no injury or damage is sustained by third
parties in the event of malfunction or failure of a passive electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions (e.g.
because they are classed as “hazardous”). Useful information on this will be found in our
Material Data Sheets on the Internet (www.epcos.com/material). Should you have any more
detailed questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order.
We also reserve the right to discontinue production and delivery of products.
Consequently, we cannot guarantee that all products named in this publication will always be
available.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current version
of the “General Terms of Delivery for Products and Services in the Electrical Industry”
published by the German Electrical and Electronics Industry Association (ZVEI).
7. The trade names EPCOS, EPCOS-Jones, Baoke, CeraDiode, CSSP, MLSC, PhaseCap,
PhaseMod, SIFI, SIKOREL, SilverCap, SIMID, SIOV, SIP5D, SIP5K, UltraCap, WindCap are
trademarks registered or pending in Europe and in other countries. Further information will be
found on the Internet at www.epcos.com/trademarks.
13
01/06
Similar pages