Electrical data
VPN
VPmax
V̂P
RP
RM
ISN
VC
IC
Vd
Ve
Primary nominal r.m.s. voltage
Primary voltage measuring range
Non-measurable overload
Primary input resistance
Measuring resistance
@ VC=11.4V
@ VC=22.8V
Secondary nominal r.m.s. current
Supply voltage (± 5 %)
Current consumption
R.m.s. voltage for AC isolation test, 50 Hz, 1 min
Max Common mode voltage
and
R.m.s. voltage for partial discharge
extinction @ 10pC
2000
V
± 30001)
V
4500 (1s/h)
VDC
17.8M
Ω
RM min
RM max
0
47
Ω
0
184
Ω
50
mA
DC± 12 .. 24
V
50+IS
mA
6.5
kV
U HT+ + U HT- ≤ 4.2 k V DC
UHT+ - U HT-≤ VPMAX
2.2
kV
Accuracy - Dynamic performance data
XG
XG
XG
ε
Overall Accuracy @ VPN , TA = + 25°C
Overall Accuracy @ VPN , TA = - 25 .. + 70°C
Overall Accuracy @ VPN , TA = - 40 .. + 85°C
Linearity @ TA = 25°C
Offset current @ VP = 0, TA = 25°C
Response time @ 10 % of VPN
Frequency bandwidth (- 3 dB)
L
IO
tr
f
± 0.7
± 1.5
± 1.7
< 0.1
± 0.15
< 12
DC .. 13
%
%
%
%
mA
µs
kHz
Features
• Insulated plastic case recognized
according to UL 94-V0
• Included primary resistor.
Advantages
•
•
•
•
•
•
•
Low power
Excellent accuracy
Very good linearity
Low thermal drift
Low response time
High bandwidth
High immunity to external
interference
• Low disturbance in common mode.
Applications
• AC variable speed drives and servo
motor drives
• Static converters for DC motor drives
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Power supplies for welding
General data
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
Standards
Note :
1)
applications .
- 40 .. + 85
°C
- 50 .. + 90
°C
375
g
EN 50155 (01.12.02)
EN 50124-1 (01.03.01)
NFF16101/2 (01.10.88)
Up to 2200 Vpk, 500 ms every 60 minutes & 2600 Vpk, 500 ms,12
times/year.
030805/2
LEM Components
Dimensions AV 100-2000 (in mm. 1 mm = 0.0394 inch)
Front view
Left view
HT+
HT+
M
-
Secondary terminals
Terminal + : Supply voltage +12 .. 24 V
Terminal M : Measure
Terminal - : Supply voltage - 12 .. 24V
Connection
AV 100-2000
Top view
Mechanical characteristics
Remarks
• General tolerance
• Transducer fastening
• IS is positive when VP is applied on terminal +HT.
• This is a standard model. For different versions, please
± 1 mm
2 holes ∅ 6.5 mm
Distance between holes
124mm
• Fastening & connection of primary 2 x M5
• Fastening & connection of secondary 3 x M5 or 3 Faston
6.35 x 0.8mm
Output connections must be made with screened cables
• Recommended fastening torque
2.2 Nm or 1.62 Lb - Ft.