Mean Well DR-100-15 100w single output industrial din rail power supply Datasheet

100W Single Output Industrial DIN Rail Power Supply
DR-100
series
Features :
Universal AC input / Full range
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
Isolation class
LED indicator for power on
No load power consumption<1W
100% full load burn-in test
3 years warranty
..
SPECIFICATION
MODEL
DR-100-12
DR-100-15
DR-100-24
DC VOLTAGE
12V
15V
24V
RATED CURRENT
7.5A
6.5A
4.2A
CURRENT RANGE
0 ~ 7.5A
0 ~ 6.5A
0 ~ 4.2A
RATED POWER
90W
97.5W
100.8W
RIPPLE & NOISE (max.) Note.2 120mVp-p
OUTPUT
INPUT
120mVp-p
150mVp-p
12 ~ 15V
15 ~ 18V
24 ~ 29V
VOLTAGE TOLERANCE Note.3
2.0%
1.0%
1.0%
LINE REGULATION
1.0%
1.0%
1.0%
LOAD REGULATION
1.0%
1.0%
1.0%
VOLTAGE ADJ. RANGE
SETUP, RISE TIME
2700ms, 80ms/230VAC
HOLD UP TIME (Typ.)
50ms/230VAC
VOLTAGE RANGE
88 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
87%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
3A/115VAC
1.6A/230VAC
COLD START 30A/115VAC
45A/230VAC
OVERLOAD
105 ~ 135% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
16 ~ 20V
19 ~ 23V
30 ~ 35V
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
EMC
(Note 4)
OTHERS
87%
89%
Protection type : Shut down o/p voltage, re-power on to recover
90
15
(RTH2) detect on heatsink of power transistor
Protection type : Shut down o/p voltage, re-power on to recover
-20 ~ +60 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50 )
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL60950-1, TUV EN60950-1 approved, design refer to EN50178
I/P-O/P:3KVAC
ISOLATION RESISTANCE
I/P-O/P:>100M Ohms/500VDC 25 70%RH
EMI CONDUCTION & RADIATION Compliance to EN61204-3, EN55022 ClassB
Compliance to EN61000-3-2,-3
HARMONIC CURRENT
EMS IMMUNITY
Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
MTBF
486K hrs min. MIL-HDBK-217F (25
100*93*56mm (W*H*D)
0.35Kg; 36pcs/13.6Kg/0.89CUFT
DIMENSION
PACKING
NOTE
18ms/115VAC at full load
124 ~ 370VDC
EFFICIENCY (Typ.)
PROTECTION OVER VOLTAGE
SAFETY &
2700ms, 80ms/115VAC at full load
)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Harmonic current test @ 90% load.
File Name:DR-100-SPEC 2007-08-09
DR-100
100W Single Output Industrial DIN Rail Power Supply
Mechanical Specification
Case No.970A
series
Unit:mm
68
45
47
56
27.4
Pin No.
1
2
3,4
3
Terminal Pin No. Assignment
Pin No.
5,6
7
8
Assignment
AC/L
AC/N
+V
46.5
Assignment
-V
LED
+V ADJ.
46.5
93
7.5 5 5 5
6
5
4
3
8
7
64.75
100
35
2
1
5
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
Block Diagram
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
RECTIFIERS
&
FILTER
POWER
SWITCHING
O.L.P.
+V
-V
DETECTION
CIRCUIT
PWM
CONTROL
O.V.P.
Derating Curve VS Ambient Temperature
Output Derating VS Input Voltage
Ta=25
100
100
230V AC Input
90
80
80
110V AC Input
70
LOAD (%)
LOAD (%)
60
40
20
-20
0
10
20
30
40 45 50
AMBIENT TEMPERATURE ( )
60
70 (VERTICAL)
60
50
40
88
95
100
110
120
140
160
180
200
220
240
264
INPUT VOLTAGE (VAC) 60Hz
File Name:DR-100-SPEC 2007-08-09
Similar pages