ADAM-6015 ADAM-6017 ADAM-6018 ADAM-6015 7-ch Isolated RTD Input Modbus TCP Module 8-ch Isolated Analog Input Modbus TCP Module with 2-ch DO 8-ch Isolated Thermocouple Input Modbus TCP Module with 8-ch DO ADAM-6017 RoHS COMPLIANT 2002/95/EC Specifications Analog Input Analog Input Channels Input Impedance Channels 7 (differential) Input Impedance > 10 MΩ Input Connections 2 or 3 wire Input Type Pt, Balco and Ni RTD RTD Types and Temperature Ranges Pt 100 -50°C ~ 150°C 0°C ~ 100°C 0°C ~ 200°C 0°C ~ 400°C -200°C ~ 200°C Pt 1000 -40°C ~ 160°C Supports both IEC 60751 ITS90 (0.03851 W/W/°C) and JIS C 1604 (0.03916 W/W/°C) Balco 500 -30°C ~ 120°C Ni 518 -80°C ~ 100°C 0°C ~ 100°C Accuracy ± 0.1 % Span Drift ± 25 ppm/°C Zero Drift ± 6 μV/°C Resolution 16-bit Sampling Rate 10 sample/ second (total) CMR @ 50/60 HZ 90dB NMR @ 50/60 HZ 60dB Wire Burn-out Detection Ordering Information ADAM-6015 COMPLIANT 2002/95/EC Specifications lnput Type lnput Range Accuracy Span Drift Zero Drift Resolution Sampling Rate Power Dissipation 2, open collector to 30 V, 100 mA max. load 300 mW for each module Ordering Information ADAM-6017 RoHS COMPLIANT 2002/95/EC Specifications Analog Input 8 (differential) > 10 MΩ (voltage) 120 Ω (current) mV, V, mA ±150 mV, ±500 mV, ±1 V ±5 V, ±10 V, 0-20 mA, 4-20 mA ±0.1% (voltage) ±0.2% (current) ±25 ppm/°C ±6 μV/°C 16-bit 10 sample/ second (total) CMR @ 50/60 HZ 90dB NMR @ 50/60 HZ 67CMR @ 50/60 HZ 90dBdB Digital Output Channels ADAM-6018 RoHS 8-ch Isolated AI with 2-ch DO Modbus TCP Module Channels 8 (differential) Input Impedance > 10 MΩ lnput Type Thermocouple Thermocouple Type and Range: J K T E 0 ~ 760°C 0 ~ 1,370°C -100 ~ 400°C 0 ~ 1,000°C R S B 500 ~ 1,750°C 500 ~ 1,750°C 500 ~ 1,800°C Accuracy Span Drift Zero Drift Resolution Sampling Rate ±0.1% ±25 ppm/°C ±6 μV/°C 16-bit 10 sample/ second (total) CMR @ 50/60 HZ 90dB NMR @ 50/60 HZ 60dB Wire Burn-out Detection Digital Output Channels Power Dissipation 8, open collector to 30 V, 100 mA max. load 300 mW for each module Ordering Information ADAM-6018 7-ch Isolated RTD Input Modbus TCP Module 8-ch Isolated Thermocouple Input Modbus TCP Module w/ 8-ch DO Common Specifications General LAN 10/100Base-T(X) Power Consumption 2 W @ 24 VDC Connectors 1 x RJ-45 (LAN), Plug-in screw terminal block (I/O and power) Watchdog System (1.6 second) and Communication (programmable) Power Input 10 ~ 30 VDC Supports Peer-to-Peer Supports GCL Supports Modbus/TCP, TCP/IP, UDP and HTTP Protocols Protection Over Voltage ±35 VDC Protection Isolation Protection 2,000 VDC Built-in TVS/ESD Protection Power Reversal Protection Environment Operating -10 ~ 70°C (14 ~ 158°F) Temperature Storage Temperature -20 ~ 80°C (-4 ~ 176°F) Operating Humidity 20 ~ 95% RH (non-condensing) Storage Humidity 0 ~ 95% RH (non-condensing) Ethernet I/O Modules All product specifications are subject to change without notice Last updated : 19-Mar-2014