Nova CGD3.5K-12-120 Pure-sinewave dc-ac inverter Datasheet

CGD3.5K SERIES
PURE-SINEWAVE DC-AC INVERTERS
» INCLUDES BUILT-IN AUTOMATIC
TRANSFER SWITCH (ATS) WITH AC
INPUT CIRCUIT BREAKER
» PARALLELABLE FOR INCREASED
POWER
» 3 PHASE WYE CONFIGURABLE
» 120/240 CT SPLIT PHASE
CONFIGURABLE
3500W / 3500VA
12 V, 24 V, 48 V INPUT
SIX MODELS FOR
110V 50/60 Hz & 220V 50/60 Hz OUTPUT
APPLICATIONS
Nova Electric’s CGD-Series inverters are intended for commercial and industrial applications wherever
pure sinewave power is needed at 50 or 60 Hz. These inverters are ideal for running electronic loads
such as computers, monitors, printers, telecom systems, radios, fluorescent lamps from batteries,
field generators, and solar electro-voltaic panels. They can also drive hand drills, motors and small
compressors – please consult the factory for proper sizing. These CGD models can also be optionally
ruggedized against shock, vibration, and humidity for military applications including vehicle mounted,
shipboard, submarine, aircraft, and ground fixed shelters.
q COMPUTERS
q SAIL BOATS
q APPLIANCES
q PRINTERS
q PHOTO VOLTAIC
q INSTRUMENTS
q MONITORS
q ELECTRIC TOOLS
q RVs
For more information, please visit us at www.novaelectric.com or email us at [email protected]
STANDARD FEATURES
ELECTRICAL
SAFETY & EMC
Input Voltage: See Table
accurate and stable frequency.
Output Voltage 110V model: 100/110/120 VAC
Compact and light weight, yet rugged and Output Voltage 220V model: 220/230/240 VAC
Output Frequency: 50 or 60 HZ ±0.1% Accuracy
vehicle rated.
Tightly regulated output voltage and frequency Continuous Power Rating: 3500W/3500VA
Switch selectable 50 or 60 Hz output, all models Peak Power (3 seconds): 4500W
Surge Rating: 6000W < 0.2 seconds
Capable of driving highly reactive loads such as
Efficiency: 90% (12V, 24V/120), 91% (24V/220, 48V)
electric tools and appliances.
Output Waveform Sinewave: <3% THD
Capable of driving highly capacitive loads such Output Voltage Regulation: ±3%
as switching power supplies.
Protection: Overload, Short Circuit, Reverse Polarity
Very low harmonic distortion
(Fuse), O.T, Over/Under Input Voltage, Fan Failure
Suitable for vehicle or wall mounting
Output Frequency Regulation: ±0.1%
Synchronous Frequency: 47-57 / 53 - 63 Hz
Standard outputs 110V/60Hz, 230V/50Hz
ATS: Inverter to utility AC: 8 ~ 10ms.
Switch selectable ±10V output change
Utility AC to inverter: 16 ~ 50 ms.
RS-232 communication (RJ11 Connector)
Built in mechanical transfer switch (ATS)
120V: UL458*; FCC Class B
220V: EN60950-1; EN55014-1**, EN55014-2**;
EN61000-3-2, -3-3; EN61204-3;
EN61000-6-1, -6-2, -6-3, -6-4;
IEC61000-4-2, 3,4,5,6,8,11
12V - 120V
24V - 120V
48V - 120V
12V - 220V
24V - 220V
48V - 220V
@12VDC
@24VDC
@48VDC
@12VDC
@24VDC
@48VDC
1.4A
<2.9A
0.5A
<1.4A
0.5A
<0.8A
1.4A
<3.6A
0.5A
<1.8A
0.5A
<1A
• Microprocessor based design with absolutely
•
•
•
•
•
•
•
•
•
•
•
No Load Power Consumption
On Mode @ Save Mode
On Mode @ No Load Mode
ENVIRONMENTAL
• Operating Temp.: -20° to +40°; + 60°C @ 40% Pwr Load
• Storage Temp. Range: -40° to +71°C
• Humidity: To 90% non-condensing
INDICATORS, CONTROL & COMMUNICATIONS
• Input level, Fault Status
• Optional Remote Control
• Optional Ethernet Communications
* UL-458 only support CGD2500W-12-120 and CGD2500W-24-120
** EN55014-1, EN55014-2 Class B: output cable less than 6.5 ft (2 meters)
Fuse
40A x 12
20A x 12
20A x 6
40A x 12
20A x 12
20A x 6
BAT. Low Alarm ±3%
10.5 VDC
21.0 VDC
42.0 VDC
10.5 VDC
21.0 VDC
42.0 VDC
BAT. Low Shut-down ±3%
10.0 VDC
20.0 VDC
40.0 VDC
10.0 VDC
20.0 VDC
40.0 VDC
BAT. Low Restart ±3%
12.5 VDC
25.0 VDC
50.0 VDC
12.5 VDC
25.0 VDC
50.0 VDC
BAT. High Alarm ±3%
15.5 VDC
31.0 VDC
62.0 VDC
15.5 VDC
31.0 VDC
62.0 VDC
BAT. High Shut-down ±3%
16.0 VDC
32.0 VDC
64.0 VDC
16.0 VDC
32.0 VDC
64.0 VDC
BAT. High Restart ±3%
15.0 VDC
30.0 VDC
60.0 VDC
15.0 VDC
30.0 VDC
60.0 VDC
MODEL SELECTION
INPUT
VDC
120 V MODELS
50 Hz or 60 Hz
220 V MODELS
50 Hz or 60 Hz
DIMENSIONS
(L” x W” x H”) [mm]
WEIGHT
10 - 16 V
CGD3.5K-12-120
CGD3.5K-12-220
19.53 x 11.14 x 5.04 [496 x 283 x 128]
22 lbs [10 kg]
20 - 32 V
CGD3.5K-24-120
CGD3.5K-24-220
19.53 x 11.14 x 5.04 [496 x 283 x 128]
22 lbs [10 kg]
40 - 60 V
CGD3.5K-48-120
CGD3.5K-24-220
19.53 x 11.14 x 5.04 [496 x 283 x 128]
22 lbs [10 kg]
MECHANICAL SPECIFICATIONS
GROUND
NOVA ELECTRIC Leader in power conversion technology since 1966
AS 9100
Certificate No: US008267-1