Battery BP5-12-T2-RA Vrla rechargeable battery Datasheet

VRLA Rechargeable Battery
Measures
BP5-12
FEATURES
Technology
Values
Innovation
APPLICATION
Maintenance free(no water topping-up required).
No free acid(Non-spillable battery).
Low self-discharge rate, lower than 3% capacity loss per month.
Can be used in any orientation(excluding used inverted).
Absorbent Glass Mat technology for efficient gas recombination.
UPS
Electronic Doorbells
Toy-Cars
Fans
SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
Terminals
Internal Resistance
Max. Discharge Current
Max. Charge Current
12 V
5.0Ah @ 20 hour rate F.V.(1.75V/cell)
1800g(3.97lbs.)
T1 (Faston Tab 187) T2 is optional
27m
(Fully Charged )
75 A (5 sec.)
1.5 A
Charge 0oC~40oC(32oF~104oF)
Discharge -20oC~50oC(-4oF~122oF)
Storage. -20oC~40oC(-4oF~104oF)
Operating Temperature Range
IEC 61056-1
JIS C 8702-1
GB/T 19639.1
Standard: ABS( UL 94-HB) BP5-12
Optional: Flame Retardant ABS(UL 94-V0) BP5-12FR
Container Material
DIMENSION(mm/inch)
OUTER DIMENSIONS
TERMINAL TYPE
Length
Terminal T1
90±1.5 (3.54±0.06)
Width
106 2(4.17 0.08)
Constant power discharge characteristics at 25 oC/77 oF
F.V.
(V/cell)
1.80V
1.75V
1.70V
1.65V
1.60V
1.80V
1.75V
1.70V
1.65V
1.60V
0.8(0.03)
10 Min
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
180.8
133.1
106.6
63.5
36.39
14.57
10.05
5.62
2.96
209.2
144.2
111.5
65.9
37.48
14.87
10.20
5.70
3.00
222.3
149.4
115.0
67.4
38.16
15.00
10.26
5.73
3.01
232.3
152.9
117.6
68.3
38.61
15.10
10.29
5.75
3.02
240.0
156.0
120.0
69.0
39.00
15.20
10.32
5.75
3.02
o
Constant current discharge characteristics at 25 C/77 F
F.V.
(V/cell)
Unit: W
5 Min
o
Discharge
Time
7.95(0.31)
0.8(0.03)
102 1.5(4.02 0.06)
Total Height
106±2.0 (4.17±0.08)
6.35(0.25)
6.35(0.25)
70 1.5(2.76 0.06)
90 1.5(3.54 0.06)
Container Height
102±1.5 (4.02±0.06)
4.75(0.19)
3.2(0.13)
70±1.5 (2.76±0.06)
Discharge
Time
Terminal T2
3.4(0.13)
Unit: A
5 Min
10 Min
15 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
16.3
11.71
9.27
5.38
3.06
1.21
0.837
0.468
0.246
19.2
12.69
9.70
5.58
3.15
1.24
0.850
0.475
0.250
20.4
13.15
10.00
5.71
3.21
1.25
0.855
0.477
0.251
21.3
13.46
10.23
5.79
3.24
1.26
0.858
0.479
0.252
22.0
13.73
10.43
5.85
3.28
1.27
0.860
0.479
0.252
30 Min
All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
A/2
REV. Mar. 2013
Powered by
B.B. Battery Co., Ltd.
Similar pages