100W Single Output Industrial DIN Rail Power Supply DR-100 series Features : Universal AC input / Full range Protections: Short circuit / Overload / Over voltage / Over temperature Cooling by free air convection Can be installed on DIN rail TS-35/7.5 or 15 Isolation class LED indicator for power on No load power consumption<1W 100% full load burn-in test 3 years warranty .. SPECIFICATION MODEL DR-100-12 DR-100-15 DR-100-24 DC VOLTAGE 12V 15V 24V RATED CURRENT 7.5A 6.5A 4.2A CURRENT RANGE 0 ~ 7.5A 0 ~ 6.5A 0 ~ 4.2A RATED POWER 90W 97.5W 100.8W RIPPLE & NOISE (max.) Note.2 120mVp-p OUTPUT INPUT 120mVp-p 150mVp-p 12 ~ 15V 15 ~ 18V 24 ~ 29V VOLTAGE TOLERANCE Note.3 2.0% 1.0% 1.0% LINE REGULATION 1.0% 1.0% 1.0% LOAD REGULATION 1.0% 1.0% 1.0% VOLTAGE ADJ. RANGE SETUP, RISE TIME 2700ms, 80ms/230VAC HOLD UP TIME (Typ.) 50ms/230VAC VOLTAGE RANGE 88 ~ 264VAC FREQUENCY RANGE 47 ~ 63Hz 87% AC CURRENT (Typ.) INRUSH CURRENT (Typ.) 3A/115VAC 1.6A/230VAC COLD START 30A/115VAC 45A/230VAC Note.6 PROTECTION OVER VOLTAGE OVER TEMPERATURE WORKING TEMP. WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY EMC (Note 4) OTHERS 87% 89% 105 ~ 135% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed 16 ~ 20V 19 ~ 23V 30 ~ 35V Protection type : Shut down o/p voltage, re-power on to recover 90 15 (RTH2) detect on heatsink of power transistor Protection type : Shut down o/p voltage, re-power on to recover -20 ~ +60 (Refer to "Derating Curve") 20 ~ 90% RH non-condensing -40 ~ +85 , 10 ~ 95% RH TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS WITHSTAND VOLTAGE I/P-O/P:3KVAC ISOLATION RESISTANCE EMC EMISSION I/P-O/P:>100M Ohms / 500VDC / 25 / 70% RH Compliance to EN61204-3, EN55022 Class B, EN61000-3-2,-3 EMC IMMUNITY MTBF Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A 486K hrs min. MIL-HDBK-217F (25 ) DIMENSION 100*93*56mm (W*H*D) 0.35Kg; 36pcs/13.6Kg/0.89CUFT PACKING NOTE 18ms/115VAC at full load 124 ~ 370VDC EFFICIENCY (Typ.) OVERLOAD SAFETY & 2700ms, 80ms/115VAC at full load 0.03%/ (0 ~ 50 ) Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 UL60950-1, TUV EN60950-1 approved, design refer to EN50178 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. Harmonic current test @ 90% load. 6. Under short circuit or overload >150% conditions, output voltage may shut down for 5 sec. and then go into constant current protection mode. File Name:DR-100-SPEC 2011-06-17 DR-100 100W Single Output Industrial DIN Rail Power Supply Mechanical Specification Case No.970A series Unit:mm 68 45 47 56 27.4 Pin No. 1 2 3,4 3 Terminal Pin No. Assignment Pin No. 5,6 7 8 Assignment AC/L AC/N +V 46.5 Assignment -V LED +V ADJ. 46.5 93 7.5 5 5 5 6 5 4 3 8 7 64.75 100 35 2 1 5 ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15 Block Diagram RECTIFIERS & FILTER EMI FILTER I/P RECTIFIERS & FILTER POWER SWITCHING O.L.P. +V -V DETECTION CIRCUIT PWM CONTROL O.V.P. Derating Curve VS Ambient Temperature 100 Output Derating VS Input Voltage 100 230V AC Input 90 80 80 110V AC Input 70 LOAD (%) LOAD (%) 60 40 20 -20 0 10 20 30 40 45 50 AMBIENT TEMPERATURE ( ) 60 70 (VERTICAL) 60 50 40 88 95 100 110 120 140 160 180 200 220 240 264 INPUT VOLTAGE (VAC) 60Hz File Name:DR-100-SPEC 2011-06-17