Holt AN-551 Bus connections for test configuration Datasheet

MIL-STD-1553 Bus Connections for Test
Configurations
April 2016
AN‐571 Rev. New
Holt Integrated Circuits
This page Intentionally Blank
AN‐571 Rev. New
Holt Integrated Circuits
1 INTRODUCTION
There are several important factors to consider when configuring a test bus for the development and
testing of MIL‐STD‐1553 systems. It is possible to use either fully compliant MIL‐STD‐1553 buses or
alternatively a "simulated bus" can be developed as a resistor network. It is important to properly
terminate the test bus regardless of which configuration is used. Proper termination is necessary to
minimize transmission line reflections, overshoots, ringing, and oscillations that can result in data errors.
This application note provides methods to minimize data errors and avoid violating any 1553 component
specifications.
2 PROPER BUS TERMINATION
In order to prevent data errors or possible over‐voltages, it is advisable that all test setups and
embedded environments ensure proper terminations are used on the MIL‐STD‐1553 buses. It is
important that proper bus terminations be used in both development and test environments as well as
on deployable platforms.
Unless the 1553 transmitters within the test equipment are very low impedance voltage sources, they
will provide higher voltages to un‐terminated buses than to properly terminated buses. Moreover,
operation on un‐terminated 1553 buses can result in transmission line reflections, leading to
overshoots, oscillations, and ringing. The use of properly terminated buses will prevent these anomalies,
thus eliminating the possibility of over‐voltages or data errors due to improper bus configuration.
Figures 2 through 9 show various configurations that may be used including both fully compliant MIL‐
STD‐1553 buses, along with resistive “simulated bus” networks. These include the various combinations
of transformer and direct coupling for the 1553 interface components and the test equipment.
For the simulated bus resistor networks shown, the load impedance on both the 1553 interface
components’ and the test equipment’s transmitters will be the same as if they were driving a fully
compliant 1553 bus. These impedances will be approximately 78 ohms for transformer‐coupled
connections and approximately 39 ohms for direct coupled connections.
The simulated bus networks will deliver approximately the same stub voltages that will be received on a
compliant 1553 bus, assuming a short bus with relatively low cable attenuation. That is, about 7 volts
peak‐to‐peak to the stubs for direct coupled receiving terminals, and about 5 volts peak‐to‐peak to the
stubs for transformer‐coupled receiving terminals.
Holt's recommendation is to use the configuration shown in Figures 1 and 2. This diagram shows a fully
compliant MIL‐STD‐1553 bus with bus couplers. Transformer coupling is used for both the 1553
interface component and the test equipment. Transformer coupling provides the following advantages
over direct coupling and the simulated bus configurations:
1. The coupling transformer’s 1.4:1.0 turns ratio doubles the impedance of the
1553 interface component’s or test equipment’s stub presented to the
1553 bus. This reduces the peak voltages resulting from transmission line
reflections (and therefore data errors) and allows the use of longer stub
3
Holt Integrated Circuits
lengths.
2. Transformer coupling provides a matched impedance (70 to 85 ohms) to the
1553 interface component’s and test equipment’s transmitters, further
reducing reflections.
3. The resistors in the bus couplers, in conjunction with the capacitance of the
coupling and isolation transformers, stub cables, and transceivers, provide
filtering and attenuation of any reflections that occur.
4. The use of transformer coupling provides a reduction in any common mode
noise from the main bus.
When connecting to a compliant MIL‐STD‐1553 bus, the recommendations for maximum stub lengths in
MIL‐STD‐1553B should be met. The maximum stub length for direct coupled terminals is 1ft. The
maximum stub length for direct coupled terminals is 20 ft.
If one of the simulated bus configurations is used, then the cable lengths between
the “simulated bus” resistor(s) and the 1553 interface component, and the “simulated
bus” resistor(s) and the test equipment should also be minimized.
Figure 1 ‐ Typical MIL‐STD‐1553 Bus with Transformer Coupled Stubs
4
Holt Integrated Circuits
MIL-STD-1553 Bus
Bus Coupler
Bus Coupler
Z0
Z0
0.75*Z0
0.75*Z0
1.4:1.0
0.75*Z0
0.75*Z0
1.4:1.0
Transformer
Coupled
Test Equipment
Holt
1553 IC
Transformer
Coupled
Figure 2 ‐ Transformer‐Coupled 1553 interface component and transformer‐coupled test
equipment using a fully compliant MIL‐STD‐1553 bus and bus couplers.
Figure 3 ‐ Transformer‐Coupled 1553 interface component and transformer‐coupled test
equipment using a resistive simulated bus configuration.
5
Holt Integrated Circuits
Figure 4 ‐ Direct Coupled 1553 Interface Component and direct coupled test equipment using
a fully compliant MIL‐STD‐1553 bus.
Figure 5 ‐ Direct Coupled 1553 Interface component and direct coupled test equipment using
a resistive simulated bus configuration.
6
Holt Integrated Circuits
Figure 6 ‐ Transformer coupled 1553 interface component and direct coupled test equipment
using a fully compliant MIL‐STD‐1553 bus with bus coupler.
Figure 7 ‐ Transformer coupled 1553 interface component and direct coupled test equipment
using a resistive simulated bus configuration.
7
Holt Integrated Circuits
Bus Coupler
Z0
Z0
Stub Length <
12 Inches
0.75*Z0
0.75*Z0
1.4:1.0
55Ω
55Ω
Transformer
Coupled
Test Equipment
Holt
1553 IC
Direct Coupled
Figure 8 ‐ Direct coupled 1553 interface component and transformer coupled test equipment
using a fully compliant MIL‐STD‐1553 bus.
55Ω
Holt
1553 IC
13.5Ω
69Ω
55Ω
13.5Ω
20Ω
63Ω
20Ω
Transformer
Coupled
Test Equipment
Direct Coupled
Figure 9 ‐ Direct coupled 1553 interface component and transformer coupled test equipment
using a resistive simulated bus configuration.
8
Holt Integrated Circuits
3 MIL‐STD‐1553 TEST CIRCUITS
MIL‐STD‐1553B and the RT Validation Test Plan define the test circuits to be used for measuring various
terminal characteristics. Figures 10 and 11 below show the data bus connections as defined in MIL‐STD‐
1553. The coupling transformer shown in Figure 10 is required and the transformer shall have a turns
ratio of 1:1.41 ±3.0% with the higher turns on the isolation resistor side of the stub. The series isolation
resistors in Figure 11 shall have a value of 55.0Ω ±2.0%.
BUS SHIELD
Bus Coupler
DATA BUS
WIRE PAIR
SHIELDING
0.75*Z0
0.75*Z0
COUPLING
TRANSFORMER
N:1
STUB OF SPECIFIED
LENGTH
A
ISOLATION
TRANSFORMER
Transmitter/
Receiver
Terminal
Figure 10 ‐ Data Bus Interface Using Transformer Coupling IAW MIL‐STD‐1553B
Figure 11 ‐ Data Bus Interface Using Direct Coupling IAW MIL‐STD‐1553
9
Holt Integrated Circuits
Figure 12 ‐ Direct coupled 1553 interface component test circuit used for RT validation and
MIL‐STD‐1553 electrical validation tests.
Figure 13 ‐ Transformer coupled 1553 Interface component test circuit used for RT validation
and MIL‐STD‐1553 electrical validation tests.
3.1 Databus Transmission Methods
The following parameters are measured at point A in Figure 10 or Figure 11:
1. BC Inter‐message Gap Time
2. RT Response Time
3. Minimum no‐response time‐out
3.2 Cable Stub Measurements
Every data bus shall be designed such that all stubs at point A of Figure 10 shall have a peak‐to‐peak
amplitude, line‐to‐line within the range of 1.0 and 14.0 V for a transmission by any terminal on the bus.
Similarly, every data bus shall be designed such that all stubs at point A of Figure 11 shall have a peak‐
to‐peak amplitude, line‐to‐line within the range of 1.4 and 20.0 V for a transmission by any terminal on
the bus.
3.3 Terminal Input Characteristics
The following parameters are measured at point A in Figure 10 or 11 for transformer or direct coupled
connections respectively:
1. Input Waveform Compatibility
a. Zero Crossing Deviation
b. Receive Threshold
2. Common mode rejections
3. Input impedance
4. Noise Rejections
10
Holt Integrated Circuits
3.4 Terminal Output Characteristic Measurements:
Direct coupled terminals are to be measured at point A in the test circuit shown in Figure 12. The
following measurements are taken with 35 Ohm ± 2.0% resistive load:
1. Output Voltage Amplitude
2. Output Waveform
a. Zero Crossing Deviation
b. Rise/Fall Times
c. Distortion (Overshoot/Ringing)
3. Output Noise
4. Output Symmetry
Similarly, for transformer coupled terminals, the terminal I/O characteristics are to be measured using a
test circuit as shown in Figure 13 with a 70 Ohm ± 2.0% resistive load.
3.5 Other Measurements
3.5.1 Power on/off noise
A terminal shall limit any spurious output during a power‐up or power‐down sequence. The maximum
allowable output noise amplitude shall be ±250 mV peak, line‐to‐line for transformer coupled stubs and
±90 mV peak, line‐to‐line for direct coupled stubs, measured at point A of Figures 12 or 13.
3.5.2 Electrical Isolation
All terminals shall have a minimum of 45 dB isolation between data buses. Isolation here means the
ratio in dB between the output voltage on the active data bus and the output voltage on the inactive
data bus. Each data bus shall be alternately activated with all measurements being taken at point A on
Figure 12 or 13 for each data bus.
11
Holt Integrated Circuits
4 ADDITIONAL RESOURCES






12
Holt Evaluation Kits are available for most devices that include complete and easy to use
demonstration software, documentation, schematics, and Bills of Materials. Versions
are available with low level sample software and API level software.
HI‐6130 / HI‐6131 / HI‐6132 MIL‐STD‐1553 / MIL‐STD‐1760 3.3V BC / MT / RT Multi‐
Terminal Device Datasheet
MAMBATM: HI‐6135 3.3V MIL‐STD‐1553 / MIL‐STD‐1760 Compact Remote Terminal with
SPI Host Interface Datasheet
MIL‐STD‐1553B Notice 4
MIL‐HDBK‐1553A
SAE AS4111 ‐ Validation Test Plan for the Digital Time Division Command/Response
Multiplex Data Bus Remote Terminals
Holt Integrated Circuits
5 Revision History
Revision
AN‐551, Rev. New
13
Date
04/20/16
Description of Change
Initial Release
Holt Integrated Circuits
Similar pages