Cooper EP3M23012GCC Coordination module Datasheet

Meeting The New
Selective Coordination
Code Requirements
Is Easy
The Cooper Bussmann
Coordination Module™
All-In-One Solution
Saves You Time & Money
®
• Meets Code Requirements
Helps comply with the NEC® Selective Coordination
Requirements for Emergency, Legally Required Standby,
Healthcare, Essential Electrical and Critical Operation Power
Systems (COPS) per 700.27, 701.18, 517.26, and 708.54.
Per the NEC®: Coordination (Selective) is the localization of an
overcurrent condition to restrict outages to the circuit
or equipment affected, accomplished by the choice of
overcurrent protective devices and their ratings or settings.
• Increases Safety
The objective of the selective coordination requirements is to
ensure system uptime with the goal of safety of human life
during emergencies, or for essential health care functions.
The Coordination Module™ meets this objective by providing
reliable current-limiting operation to minimize the effects of an
outage to the smallest portion of the system as possible.
• Saves Time
The Coordination Module provides a fast and easy solution to
meeting selective coordination Code requirements. Simply
utilize published fuse selective coordination ratios to select
the correct upstream fuse ratings. In addition, locate open
fuses fast with the easyID™ neon indicator.
• Saves Money
Offers significant savings compared to other fused panels
and selectively coordinated circuit breaker systems.
Coordination Module™ Specifications
Series
EP2M23012GCC
EP2M23024GCC
EP2M23036GCC
EP2M23042GCC
EP3M23012GCC
EP3M23024GCC
EP3M23036GCC
EP3M23042GCC
EP4M23012GCC
EP4M23024GCC
EP4M23036GCC
EP4M23042GCC
Voltage
Rating
Short-Circuit
Current Rating
120/208V
120/208V
120/208V
120/208V
120/240V
120/240V
120/240V
120/240V
277/480V
277/480V
277/480V
277/480V
100kA*
100kA*
100kA*
100kA*
100kA*
100kA*
100kA*
100kA*
100kA**
100kA**
100kA**
100kA**
Dimensions – in
W
H
D
28
28
28
28
28
28
28
28
28
28
28
28
36
36
48
48
36
36
48
48
36
36
48
48
Branch Circuit
Amp Rating
Number of
Circuits
30
30
30
30
30
30
30
30
30
30
30
30
12
24
36
42
12
24
36
42
12
24
36
42
5.75
5.75
5.75
5.75
5.75
5.75
5.75
5.75
5.75
5.75
5.75
5.75
* When protected by upstream LPN-RK 100A max, LPJ 200A max or JJN 200A max, otherwise 10kA.
** When protected by upstream LPS-RK 200A max, LPJ 200A max or JJS 200A max, otherwise 14kA.
Main breaker option may impact selective coordination. Coordination must be verified analyzing time current curves and available current.
Feed-through lugs available upon request. See data sheet 1149 for more information.
Coordination Module™ Catalog Numbering System
EP 2 M 2 30 42 G CC
Main
Prefix
EP = Emergency
Panel
Branch Circuit
Amperage
M = MLO
*B =Breaker
Voltage
2 = 120/208V 3P, 4W
3 = 120/240V 1P, 3W
4 = 277/480V 3P, 4W
*Main breaker drops assembly SCCR
to 10kA.
Number of
Circuits
30A Max
General
Purpose
Enclosure
12
24
36
42
Main Amperage
(200 Amps Max)
Type of
Branch Circuit
Fuses
TYPE 1 only
CC Fuses
Example:
1 = 100A
1.5 = 150A
2 = 200A
1
1
NEMA Type 1 enclosure
with surface mount trim.
2
Ground Bar bolted with set screw
terminations.
3
120/208V or 277/480V Main lugs
with AWG 6-300Kcmil terminations.
4
Full-Sized neutral bar with set-screw
terminations.
5
6
12 to 42 Circuits.
7
Branch circuit breakers
provide circuit isolation.
8
200A Copper main bus.
7
4
2
Class CC fuse holders with
easyID™ neon indicator
Provides ease of coordination with
superior overcurrent protection and
open fuse indication.
5
Additional main configurations available, see data sheet 1149 for more information.
©2008 Cooper Bussmann
St. Louis, MO 63178
636-394-2877
w w w. c o o p e r b u s s m a n n . c o m
Reorder # 3115 10-08-5M
3
Printed in USA
6
8