480W Single Output Industrial DIN RAIL with PFC Function DRP-480 series Features : Built-in passive PFC function compliance to EN61000-3-2 High efficiency 89% and low dissipation Protections: Short circuit / Overload / Over voltage / Over temperature Cooling by free air convection Built-in constant current limiting circuit Can be installed on DIN rail TS-35/7.5 or 15 UL 508(industrial control equipment)approved EN61000-6-2(EN50082-2) industrial immunity level 100% full load burn-in test 3 years warranty SPECIFICATION MODEL OUTPUT DRP-480-24 DRP-480-48 DC VOLTAGE 24V 48V RATED CURRENT 20A 10A CURRENT RANGE 0 ~ 20A 0 ~ 10A RATED POWER 480W 480W RIPPLE & NOISE (max.) Note.2 120mVp-p 120mVp-p VOLTAGE ADJ. RANGE 48 ~ 53V 1.0% 24 ~ 28V VOLTAGE TOLERANCE Note.3 1.0% LINE REGULATION 0.5% 0.5% LOAD REGULATION 1.0% 1.0% SETUP, RISE TIME 1200ms, 40ms/230VAC at full load HOLD UP TIME (Typ.) 16ms/230VAC at full load VOLTAGE RANGE 180 ~ 264VAC FREQUENCY RANGE 47 ~ 63Hz POWER FACTOR (Typ.) INPUT 89% AC CURRENT (Typ.) INRUSH CURRENT (Typ.) 4A/230VAC COLD START 40A/230VAC OVERLOAD PROTECTION OVER VOLTAGE OVER TEMPERATURE WORKING TEMP. WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS SAFETY & WITHSTAND VOLTAGE ISOLATION RESISTANCE EMC (Note 4) EMC EMISSION <3.5mA / 240VAC 105 ~ 150% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed 54 ~ 60V 30 ~ 36V Protection type : Shut down o/p voltage, re-power on to recover 100 5 (TSW : detect on heatsink of power switch) Protection type : Shut down o/p voltage, recovers automatically after temperature goes down -20 ~ +70 (Refer to "Derating Curve") 20 ~ 90% RH non-condensing -20 ~ +85 , 10 ~ 95% RH 0.03%/ (0 ~ 50 Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 UL508, UL60950-1, TUV EN60950-1 approved I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3 EMC IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (EN50082-2), heavy industry level, criteria A MTBF 180.9Khrs min. MIL-HDBK-217F (25 227*125.2*100mm (W*H*D) 2.4Kg; 6pcs/15Kg/1.75CUFT DIMENSION PACKING NOTE 0.7 EFFICIENCY (Typ.) LEAKAGE CURRENT OTHERS 250 ~ 370VDC ) 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. File Name:DRP-480-SPEC 2011-06-17 DRP-480 series 480W Single Output Industrial DIN RAIL with PFC Function Mechanical Specification Case No.930 227 125.2 100 Unit:mm TB1 3 2 1 TB2 LED 4 3 2 1 +V ADJ. Terminal Pin No. Assignment (TB1) Pin No. 1 2 3 35 ADMISSIBLE DIN-RAIL: TS35/7.5 OR TS35/15 Assignment AC/L(DC+) AC/N(DC-) FG Terminal Pin No. Assignment (TB2) Pin No. 1,2 3,4 Assignment DC OUTPUT +V DC OUTPUT -V Block Diagram fosc : 70KHz EMI FILTER I/P RECTIFIERS & FILTER PASSIVE PFC RECTIFIERS & FILTER POWER SWITCHING +V -V DETECTION CIRCUIT FG O.L.P. O.T.P. CURRENT LIMIT PWM CONTROL Derating Curve O.V.P. Output Derating VS Input Voltage 100 100 90 80 80 70 LOAD (%) LOAD (%) 60 40 20 -20 0 10 20 30 40 50 AMBIENT TEMPERATURE ( ) 60 70 (VERTICAL) 60 50 40 180 190 200 264 INPUT VOLTAGE (V) 60Hz File Name:DRP-480-SPEC 2011-06-17