3-Line Filters B84143-B*-R110 for Converters and Power Electronics B84143-B*-R112 Power line filters for three-phase systems Rated voltage 480/275 and 520/300 V~, 50/60 Hz Rated current 8 to 200 A Construction ■ Three-line filter ■ Metal case ■ Book size Features ■ ■ ■ ■ ■ ■ ■ Very high insertion loss Low leakage current Optimized footprint saves space Litz wires on the load side reduce mounting time Low weight Degree of protection: IP 201) Design based on EN 133 200, UL 1283, CSA 22.2 No.8 1986 ■ Optimized for long motor cables and operation under full load ■ UL and CSA approval pending Applications ■ Frequency converters for motor drives, e.g. – elevators – pumps – traction systems – conveyor systems – HVAC systems (heating, ventilation and air conditioning) ■ Wind farms ■ Power supplies Terminals ■ Line: Safe-to-touch terminal blocks ■ Load: Litz wires Marking Marking on component: Manufacturer’s logo, ordering code, rated voltage, rated current, rated temperature, date code Minimum marking on packaging: Manufacturer’s logo, ordering code 1) In accordance with IEC 60529:1989; EN 60529:1991; DIN VDE 0470-1 246 03/01 3-Line Filters B84143-B*-R110 for Converters and Power Electronics B84143-B*-R112 Typical circuit diagrams B84143-B8 … B16-R110 LINE LOAD L1 L1’ L2 L2’ L3 L3’ SSB1526-A B84143-B25 … B200-R11* LINE LOAD L1 L1’ L2 L2’ L3 L3’ SSB1527-I 247 03/01 3-Line Filters B84143-B*-R110 for Converters and Power Electronics B84143-B*-R112 Technical data Rated voltage V R 480/275 V~, 50/60 Hz (type -R110) 520/300 V~, 50/60 Hz (type -R112) Rated current I R Referred to 40 °C ambient temperature Test voltage V P 1770 V–, 2 s (line/line) 2700 V–, 2 s (lines/case) Overload capability 1,5 · IR for 3 min per hour or 2,5 · IR for 30 s per hour Leakage current I leak at 480 V~, 50 Hz Climatic category 25/100/21 (– 25 °C/+ 100 °C/21 days damp heat test) in accordance with EN 60068-1 Characteristics and ordering codes IR Terminal cross section load side: line side: terminal blocks litz wires mm2 mm2 I leak typ1) R typ Approx. weight kg Ordering code mA mΩ 8 4 1,5 < 14 26 1,5 B84143-B8-R110 16 4 2,5 < 14 13 1,5 B84143-B16-R110 25 6 4 < 14 10 2,7 B84143-B25-R11* 36 6 6 < 14 6,5 3,2 B84143-B36-R11* 50 16 10 < 14 4,3 3,7 B84143-B50-R11* 66 25 16 < 14 2,7 4,3 B84143-B66-R11* A 90 25 25 < 14 2,0 7,7 B84143-B90-R11* 120 50 35 < 14 1,4 8,3 B84143-B120-R11* 150 50 35 < 14 0,9 9,7 B84143-B150-R11* 200 95 70 < 14 0,5 13,5 B84143-B200-R11* Compilation of ordering code Replace the asterisk * by the code number for the required version: 0 = 480 / 275 V 2 = 520 / 300 V 1) At rated operation 248 03/01 3-Line Filters B84143-B*-R110 for Converters and Power Electronics B84143-B*-R112 Dimensional drawings B84143-B8-R110, B84143-B16-R110 50 300±10 200 Litz wire Litze PE M6 x 25 1 0,5 31 15 40 80 Terminal Anschlussblocks 44 mm klemmen mm 2 L3’ L2’ L1’ PE Wire end ferrule Aderendhülse Litz wire markings Litzenbezeichnung L1 L2 L3 25±0,3 46 6,5 230 215±0,5 Marking LINE LOAD SSB1291-1 B84143-B25-R11*, B84143-B36-R11* 60 250 400±10 Terminal Anschlussblocks klemmen6 6mm mm22 Litz wire Litze L3’ 150 L2’ Wire end ferrule Aderendhülse Litz wire markings Litzenbezeichnung 280 265±0,5 Marking LINE LOAD 56 L1 L2 L3 35±0,3 6,5 PE M6 x 25 PE 1 0,5 60 30 75 L1’ SSB1292-9 249 03/01 3-Line Filters B84143-B*-R110 for Converters and Power Electronics B84143-B*-R112 B84143-B50-R11* 60 300 500±10 Litzewire Litz Terminal Anschlussblocks 16 klemmen 16mm mm22 150 L3’ L2’ 1 0,5 52 30 75 L1’ PE PE M6 x 25 Wire end ferrule Aderendhülse Litz wire markings Litzenbezeichnung 6,5 Marking LINE LOAD 56 L1 L2 L3 35±0,3 330 315±0,5 SSB1293-H B84143-B66-R11* 80 300 500±10 Litze Litz wire Terminal Anschlussblocks klemmen2525mm mm22 150 L3’ L2 L3 Marking LINE LOAD 1 76 L1 Wire end ferrule Aderendhülse Litzenbezeichnung Litz wire markings 55±0,3 330 315±0,5 PE 6,5 PE M10 x 35 0,5 52 35 75 L2’ L1’ SSB1562-6 250 03/01 3-Line Filters B84143-B*-R110 for Converters and Power Electronics B84143-B*-R112 B84143-B90-R11* 80 300 500±10 Litz wire Litze Terminal Anschlussblocks klemmen2525mm mm22 200 L3’ L2’ PE 1 Wire end ferrule Aderendhülse Litz wire markings Litzenbezeichnung PE M10 x 35 6,5 330 315±0,5 55±0,3 L1 Marking LINE LOAD L2 L3 76 30 0,5 52 100 L1’ SSB1546-P B84143-B120-R11*, B84143-B150-R11* 90 350 500±10 AnschlussTerminal blocks klemmen 50 mm22 50 mm Litz wire Litze 200 L3’ L1’ PE Aderendhülse Wire end ferrule Litz wire markings Litzenbezeichnung 380 365±0,5 L2 Marking LINE LOAD 86 L1 65±0,3 6,5 PE M10 x 35 1 40 0,5 78 100 L2’ L3 SSB1561-X 251 03/01 3-Line Filters B84143-B*-R110 for Converters and Power Electronics B84143-B*-R112 B84143-B200-R11* 2 mm2 Terminal blocks Anschlussklemmen 95 mm95 LitzLitze wire 400 110 Wire end ferrule Aderendhülse 500±10 220 L1’ L2’ PE M10 x 35 1 30 0,5 79 110 L3’ PE Litz wire markings Litzenbezeichnung 430 Marking LINE LOAD 106 L1 L2 L3 85±0,3 6,5 415±0,5 SSB1563-E 252 03/01 3-Line Filters B84143-B*-R110 for Converters and Power Electronics B84143-B*-R112 Insertion loss (typical values at Z = 50 Ω) unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) B84143-B8-R110, B84143-B16-R110 SSB1528-R 120 dB αe B84143-B25-R11*, B84143-B36-R11* αe 100 100 90 90 80 80 70 70 60 60 50 50 40 40 30 30 20 20 10 10 0 4 10 10 5 10 6 10 7 SSB1529-Z 120 dB 0 4 10 Hz 10 8 10 5 10 6 10 7 B84143-B50-R11* B84143-B66-R11* SSB1530-3 120 dB αe 100 90 90 80 80 70 70 60 60 50 50 40 40 30 30 20 20 10 10 10 5 10 6 10 7 Hz 10 8 SSB1531-B 120 dB αe 100 0 4 10 Hz 10 8 f f 0 4 10 f 10 5 10 6 10 7 Hz 10 8 f 253 03/01 3-Line Filters B84143-B*-R110 for Converters and Power Electronics B84143-B*-R112 Insertion loss (typical values at Z = 50 Ω) unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) B84143-B90-R11*, B84143-B120-R11* 120 dB αe B84143-B150-R11*, B84143-B200-R11* SSB1532-J αe 100 100 90 90 80 80 70 70 60 60 50 50 40 40 30 30 20 20 10 10 0 4 10 10 5 10 6 10 7 Hz 10 8 SSB1533-S 120 dB 0 4 10 10 5 10 6 10 7 Hz 10 8 f f 254 03/01 Herausgegeben von EPCOS AG Marketing Kommunikation, Postfach 80 17 09, 81617 München, DEUTSCHLAND EPCOS AG 2000. Alle Rechte vorbehalten. Vervielfältigung, Veröffentlichung, Verbreitung und Verwertung dieser Broschüre und ihres Inhalts ohne ausdrückliche Genehmigung der EPCOS AG nicht gestattet. Mit den Angaben in dieser Broschüre werden die Bauelemente spezifiziert, keine Eigenschaften zugesichert. Bestellungen unterliegen den vom ZVEI empfohlenen Allgemeinen Lieferbedingungen für Erzeugnisse und Leistungen der Elektroindustrie, soweit nichts anderes vereinbart wird. Diese Broschüre ersetzt die vorige Ausgabe. Fragen über Technik, Preise und Liefermöglichkeiten richten Sie bitte an den Ihnen nächstgelegenen Vertrieb der EPCOS AG oder an unsere Vertriebsgesellschaften im Ausland. Bauelemente können aufgrund technischer Erfordernisse Gefahrstoffe enthalten. Auskünfte darüber bitten wir unter Angabe des betreffenden Typs ebenfalls über die zuständige Vertriebsgesellschaft einzuholen. Published by EPCOS AG Marketing Communications, P.O. Box 80 17 09, 81617 Munich, GERMANY EPCOS AG 2000. All Rights Reserved. Reproduction, publication and dissemination of this brochure and the information contained therein without EPCOS’ prior express consent is prohibited. The information contained in this brochure describes the type of component and shall not be considered as guaranteed characteristics. Purchase orders are subject to the General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry recommended by the ZVEI (German Electrical and Electronic Manufacturers’ Association), unless otherwise agreed. This brochure replaces the previous edition. For questions on technology, prices and delivery please contact the Sales Offices of EPCOS AG or the international Representatives. Due to technical requirements components may contain dangerous substances. For information on the type in question please also contact one of our Sales Offices. 1