Bussmann® Safety J Fuseholders Class J (Finger-Safe) Fuseholders JT60030 JTN60030 (w/Indication) JT60060 JTN60060 (w/Indication) For use with Bussmann Class “J” fuses - (Bussmann LPJ, JKS) Catalog Numbers: JT60030 and JT60060 - Non-Indicating; JTN60030 and JTN60060 - Indicating (Neon) Construction: Thermoplastic, UL Flammability; 94VO Voltage Ratings: 600Vac or less, 600Vdc or less Amperage Rating: JT(N) 60030 - 30A, JT(N)60060 - 60A Withstand Rating: 200,000A RMS Sym. (Self Certified at 300,000A using Bussmann LPJ_SP fuses) Agency Information: Listed to UL 512: 30 - 60A (Guide IZLT, File 14853) CSA Certified: 30 - 60A (Class 6225-01, File 47235) Dim. = 10-4-02 in. (mm.) SB02295 CE Mark: Molded into product Indication: Min. voltage: 90Vac, 115 dc; Neon Lamp “ON” when fuse opens, voltage source and current path are present. Touch Safe: IP20 per IEC 529 Terminations: Dual Port (30A) Torque 20 lb. in., Single Port (60A) Torque 45 lb. in., Terminal Construction, Tin plated Copper Alloy Wire Size: JT(N)60030 - Rated for #18-#8; 75°C, CU only, JT(N)60060 - Rated for #14-#4; 75°C, CU only (Note: For JT(N)60030 use both stranded or solid, in a variety of dual wire combinations of same wire size and type.) Packaging: 12 in a carton JT60030 JTN60030 Form No. Safety J Page 1 of 2 Data Sheet: 1152 Safety J Fuseholders Bussmann® Class J (Finger-Safe) Fuseholders JT(N)600 Series fuseblocks can be ganged together to provide two and three pole block configurations. JT60030 - JTN60030 BUSS BUSS JT60030 0 – 30A 600VAC JT60030 0 – 30A 600VAC DO NOT REMOVE UNDER LOAD DO NOT REMOVE UNDER LOAD USE CLASS J FUSES USE CLASS J FUSES 2.42 (61.3) JT60060 - JTN60060 BUSS BUSS BUSS JT60030 0 – 30A 600VAC JT60030 0 – 30A 600VAC JT60030 0 – 30A 600VAC DO NOT REMOVE UNDER LOAD DO NOT REMOVE UNDER LOAD DO NOT REMOVE UNDER LOAD USE CLASS J FUSES USE CLASS J FUSES USE CLASS J FUSES BUSS BUSS BUSS BUSS BUSS JT60060 35 – 60A 600VAC JT60060 35 – 60A 600VAC JT60060 35 – 60A 600VAC JT60060 35 – 60A 600VAC JT60060 35 – 60A 600VAC DO NOT REMOVE UNDER LOAD DO NOT REMOVE UNDER LOAD DO NOT REMOVE UNDER LOAD DO NOT REMOVE UNDER LOAD DO NOT REMOVE UNDER LOAD USE CLASS J FUSES 3.60 (91.4) USE CLASS J FUSES USE CLASS J FUSES USE CLASS J FUSES USE CLASS J FUSES 2.96 (75.2) 4.40 (111.7) 1.31 (33.3) 1.25 (31.8) 3.10 (78.7) .10 (2.6) 3.06 (77.7) Dim. = 1.52 (38.1) JT60060 JTN60060 in. (mm.) The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this Data Sheet are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. 10-4-02 SB02295 Form No. Safety J Page 2 of 2 Data Sheet: 1152