Emerson Network Power NLP250R-96S12J Active pfc and en61000-3-2 compliant Datasheet

Embedded Power for
Business-Critical Continuity
Rev.10.1.09_1
NLP250 Series
of 4
NLP250 Series
Single Output
Total Power:
250 W
Input Voltage: 85 - 264 Vac
# of Outputs: Single
Special Features
• Active PFC and EN61000-3-2
compliant
• 250 W on main channel with
forced air
• Low profile fits 1U applications
• U-Channel for maximum thermal
performance
• Optional cover (CJ suffix)
• 5 V standby output
• 12 V fan output
• Integrated ORing diode
• Active current sharing
• Integrated control and
monitoring features
• Overcurrent, overvoltage and
overtemperature protection
• Compliance to EN55022-B
conducted noise standard
• RoHS compliant
• 2 year warranty
Safety
• VDE0805/EN60950-1
IEC950/IEC60950-1
File No. 1177400-3336-0759
• UL/cUL 60950-1
CSA-C22.2 60950-1
File No. E135734
• Certificate No. 40014041
• CB Ref DE1-32468
Electrical Specifications
Input
Input voltage range:
Universal input
Input frequency range:
85 - 264 Vac
47 - 63 Hz
Input surge current:
264 Vac (cold start)
40 A max.
Safety ground leakage current:
Input current:
264 Vac, 50 Hz
120 Vac @ 250 W
230 Vac @ 250 W
1 mA
2.78 A rms
1.36 A rms
Input fuse:
UL/IEC127
T6.3 AH, 250 Vac
200 LFM forced air
250 LFM with cover
Main output
250 watts
Main output
Auxiliary outputs
@ 120 Vac Input
Main output
50 - 100%
Step at 0.5 A/µs
± 2.0%
Output
Maximum power:
Adjustment range:
Total regulation:
(line and load)
Turn-on delay:
Transient response:
Temperature coefficient:
± 5%
± 5.0%
2.0 s max.
5.0% or 250 mV
max. dev., 1 ms max
recovery to 1%
±0.02%/°C
Overvoltage protection:
Main output
115%, ± 5%
Short circuit protection:
Cyclic operation
Continuous
Minimum output current:
Auxiliary outputs:
(See Note 8)
Singles
5 Vsb
12 V (fan)
0A
5 V @ 1.0 A
12 V @ 0.3A
All specifications are typical at nominal input, full load at 25 °C unless otherwise stated
Embedded Power for
Business-Critical Continuity
Rev.10.1.09_1
NLP250 Series
of 4
EMC Characteristics (5)
Conducted emissions:
EN55022, FCC part 15
Level B
Harmonic current correction:
EN61000-3-2
Compliant
Voltage flicker:
EN61000-3-3
Compliant
ESD air:
EN61000-4-2
Level 3
ESD contact:
EN61000-4-2
Level 3
Radiated immunity:
EN61000-4-3
Level 3
Fast transients:
EN61000-4-4
Level 3
Surge:
EN61000-4-5
Level 3
Conducted immunity:
EN61000-4-6
Level 3
Hold-up time:
85 Vac @ 50 Hz
20 ms @ 250 W
Efficiency:
115 Vac @ 250 W
230 Vac @ 250 W
84% typ.
86% typ.
Isolation voltage:
Input/output
Input/chassis
3000 Vac
1500 Vac
Safety approvals (see note 6):
UL/cUL UL60950-1, VDE EN60950-1, CAN/CSA22.2 No. 60950-1
General Specifications
Weight:
MTBF (@25 ºC):
650g (22 oz)
Telcordia SR-332
MIL-HDBK-217F
317,000 hours min.
158,000 hours min.
Environmental Specifications
Thermal performance:
Operating ambient,
0 °C to +70 °C
(See derating curve)
Non-operating
-40 °C to +85 °C
0 °C to 50 °C ambient,
250 W
200 LFM forced air
250 LFM with cover
0 °C to 50 °C ambient,
0 °C to 40 °C with cover
175 W
Convection cooled
50 °C to 70 °C ambient,
Derate linearly
Convection cooled
to 50% load
Relative humidity:
Non-condensing
5 - 95% RH
Altitude:
Operating
10,000 feet max.
Non-operating
30,000 feet max.
Vibration:
(See Note 7)
5-500 Hz
2.5 G rms peak
Shock:
Per MIL-STD-810E
516.4 Part IV
Embedded Power for
Business-Critical Continuity
Rev.10.1.09_1
NLP250 Series
of 4
Ordering Information
Output Voltage
12 V
24 V
48 V
Output Current
Min
0A
0A
0A
Max (free air) (1,4) Max (forced air) (2,4)
14.6 A
7.3 A
3.65 A
21 A
10.5 A
5.25 A
Notes
1
2
3
4
Ripple (3)
Total Regulation
Model Numbers (9, 10)
120 mV
240 mV
480 mV
± 2.0%
± 2.0%
± 2.0%
NLP250R-96S12J
NLP250R-96S24J
NLP250R-96S48J
No external filtering required during conducted emissions testing but some
applications may require additional filtering to achieve system compliance. Compliance with radiated EMI specifications may require mounting in a
suitable enclosure.
6 This product is only for inclusion by professional installers within other
equipment and must not be operated as a stand alone product.
7 Three orthogonal axes, random vibration 10 minutes for each axes, 2.4 G
8 5 Vsb (standby) output is available whenever AC is present, regardless of
remote ON/OFF signal status. 12 V (fan) present when main output is present.
9 The ‘J’ suffix indicates that these parts are Pb-free (RoHS 6/6) compliant. “CJ” suffix indicates covered RoHS version.
10 NOTICE: Some models do not support all options. Please contact your local
Emerson Network Power representative or use the on-line model number
search tool at http://www.PowerConversion.com to find a suitable alternative.
5
Free air convection. Maximum continuous output power not to exceed 175 W. Refer to Figure 1 for the derating curve.
200 LFM (250 LFM with cover) forced air cooling from the longer side.
Maximum continuous output power not to exceed 250 W.
Figure is peak-to-peak for room temperature rating. Output noise
measurements are made across a 20 MHz bandwidth using a 6 inch twisted
pair, terminated with a 10 µF tantalum capacitor and a 0.1 µF ceramic
capacitor.
CAUTION: Allow a minimum of 1 second after disconnecting line power
when making thermal measurements. For optimum reliability no part of the
heatsink should exceed 115 °C and no semi-conductor case temperature
should exceed 120 °C.
Mechanical Drawing
CUSTOMER MOUNTING HOLES
MAX. SCREW PENETRATION 0.08IN
6-32
JP1
VR7
J4
J2
1
5.850 (148.59)
1
0.25 (6.35)
7.000 [177.80]
M3.0
6.250 (158.75)
M3.0
4 PLACES
6-32
4 PLACES
4.700 (119.38)
1.500 [38.10]
5.500 (139.70)
BOTTOM VIEW
2.500 (63.50)
J3
0.750 (19.05)
1.140
(28.96)
1
E
L
N
4.000 [101.60]
J1
Embedded Power for
Business-Critical Continuity
­Americas
Derating Curve With Cover
Output Power (Watts)
Derating Curve
Output
(Watts)
DERATING CURVE
Output Power
Power (Watts)
All Models
Forced Air
All Models
Forced Air
250 W
24 V Free Air 250 W
200 LFM (1.0 m/s)
FORCED AIR COOLING
24/48 V Free Air
250 LFM (1.25 m/s)
FORCED AIR COOLING
12 V Free Air
175 W
12 V Free Air
175 W
125 W
125 W
87 W
75 W
NATURAL FREE AIR
CONVECTION COOLING
NATURAL FREE AIR
CONVECTION COOLING
0W
75 W
0W
0C
10 C
20 C
30 C
40 C
50 C
60 C
70 C
0C
10 C
20 C
30 C
40 C
50 C
60 C
Rev.10.1.09_1
NLP250 Series
of 4
5810 Van Allen Way
Carlsbad, CA 92008
USA
Telephone: +1 760 930 4600
Facsimile: +1 760 930 0698
Europe (UK)
Waterfront Business Park
Merry Hill, Dudley
West Midlands, DY5 1LX
United Kingdom
Telephone: +44 (0) 1384 842 211
Facsimile: +44 (0) 1384 843 355
70 C
Asia (HK)
Connector and Mating Connector Types
Connector
Type
Mating Connector Type
14/F, Lu Plaza
2 Wing Yip Street
Kwun Tong, Kowloon
Hong Kong
Telephone: +852 2176 3333
Facsimile: +852 2176 3888
J1
Molex 09-65-2058 (5273 series)void pins Molex 09-50-8051 or equivalent with Molex 08-52-0113 or
2 and 4 or equivalent
equivalent crimp terminals
J2
Molex 22-23-2021 (6373 series) or
equivalent
Molex 22-01-3027 (2695 series) or equivalent with Molex
08-50-01113 (2759 series) or equivalent crimp terminals
For global contact, visit:
J3
Molex terminal block 387007504 or
equivalent
Terminal block contains #6-32 screw with clamp
washer suitable for wire size 12-22 awg (0.5-2.5 mm2).
Max Torque tp 1.36 Nm (12 in.lb)
techsupport.embeddedpower
@emerson.com
J4
Molex 22-23-2091 (6373 series) or
equivalent
Molex 22-01-3097 (2695 series) or equivalent with Molex
08-50-0113 (2759 series) or equivalent crimp terminals
Pin Connections
J1
Pin Connections Continued
J2
Pin 1
Ground/Earth
Pin 2
Live
Pin 3
Neutral
Pin 1
+12 V
Fan Voltage
Pin 2
SGND
Return
Pin 1
Vo
+ Main Output
Pin 2
Vo
+ Main Output
Pin 3
RTN
Main Return
Pin 4
RTN
Main Return
Pin 1
+S
+Vo Remote Sense
Pin 2
-S
Vo Remote Sense
Pin 3
LS
Load Share Signal
Pin 4
PS OFF
Remote ON/OFF signal NO
Pin 5
PS ON
Remote ON/OFF signal NC
Pin 6
SGND
Signal Common
Pin 7
PW OK
Power Good
J3
J4
Pin 8
5 Vsb
Stand-by Voltage
Pin 9
DC OK
DC Power Good Signal
www.PowerConversion.com
While every precaution has been taken to ensure
accuracy and completeness in this literature, Emerson
Network Power assumes no responsibility, and disclaims
all liability for damages resulting from use of this
information or for any errors or omissions.
Emerson Network Power.
The global leader in enabling
business-critical continuity.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
EmersonNetworkPower.com
Emerson Network Power and the Emerson
Network Power logo are trademarks and
service marks of Emerson Electric Co. ©2009 Emerson Electric Co.
Similar pages