Mean Well HRP-200-12 200w single output with pfc function Datasheet

HRP-200
200W Single Output with PFC Function
series
Features :
Universal AC input / Full range
Built-in active PFC function, PF>0.95
High efficiency up to 89%
Withstand 300VAC surge input for 5 seconds
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Built-in constant current limiting circuit
1U low profile 38mm
Built-in remote sense function
5 years warranty
SPECIFICATION
MODEL
OUTPUT
HRP-200-3.3
HRP-200-5
HRP-200-7.5
HRP-200-12
HRP-200-15
HRP-200-24
HRP-200-36
HRP-200-48
DC VOLTAGE
3.3V
5V
7.5V
12V
15V
24V
36V
48V
RATED CURRENT
40A
35A
26.7A
16.7A
13.4A
8.4A
5.7A
4.3A
CURRENT RANGE
0 ~ 40A
0 ~ 35A
0 ~ 26.7A
0 ~ 16.7A
0 ~ 13.4A
0 ~ 8.4A
0 ~ 5.7A
0 ~ 4.3A
RATED POWER
132W
175W
200.3W
200.4W
201W
201.6W
205.2W
206.4W
RIPPLE & NOISE (max.) Note.2 80mVp-p
90mVp-p
100mVp-p
120mVp-p
150mVp-p
150mVp-p
250mVp-p
250mVp-p
VOLTAGE ADJ. RANGE
4.3 ~ 5.8V
2.0%
6.8 ~ 9V
2.0%
10.2 ~ 13.8V
1.0%
13.5 ~ 18V
1.0%
21.6 ~ 28.8V
1.0%
28.8 ~ 39.6V
1.0%
40.8 ~ 55.2V
1.0%
VOLTAGE TOLERANCE Note.3
2.8 ~ 3.8V
2.0%
LINE REGULATION
0.5%
0.5%
0.5%
0.3%
0.3%
0.2%
0.2%
0.2%
LOAD REGULATION
1.5%
1.0%
1.0%
0.5%
0.5%
0.5%
0.5%
0.5%
SETUP, RISE TIME
1000ms, 50ms/230VAC
HOLD UP TIME (Typ.)
16ms/230VAC
16ms/115VAC at full load
Note.5 85 ~ 264VAC
VOLTAGE RANGE
FREQUENCY RANGE
47 ~ 63Hz
INPUT
120 ~ 370VDC
POWER FACTOR (Typ.)
PF>0.95/230VAC
EFFICIENCY (Typ.)
80%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
2.2A/115VAC
35A/115VAC
LEAKAGE CURRENT
<1.2mA / 240VAC
OVERLOAD
PROTECTION OVER VOLTAGE
2500ms, 50ms/115VAC at full load
PF>0.99/115VAC at full load
84%
86%
88%
88%
88%
89%
89%
1.1A/230VAC
70A/230VAC
105 ~ 135% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
6 ~ 7V
9.4 ~ 10.9V
14.4 ~ 16.8V 18.8 ~ 21.8V 30 ~ 34.8V
41.4 ~ 48.6V
3.96 ~ 4.62V
57.6 ~ 67.2V
Protection type : Shut down o/p voltage, re-power on to recover
95
5
(TSW1) detect on heatsink of power transistor
OVER TEMPERATURE
105
WORKING TEMP.
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
-30 ~ +70 (Refer to output load derating curve)
5
(TSW2) detect on main power output choke
20 ~ 90% RH non-condensing
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH
TEMP. COEFFICIENT
0.03%/ (0 ~ 50
VIBRATION
10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
SAFETY STANDARDS
WITHSTAND VOLTAGE
SAFETY &
EMC
(Note 4)
O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
EMS IMMUNITY
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, heavy industry level, criteria A
MTBF
209.4K hrs min.
DIMENSION
199*98*38mm (L*W*H)
0.77Kg; 18pcs/14.9Kg/0.81CUFT
PACKING
NOTE
I/P-FG:1.5KVAC
ISOLATION RESISTANCE
HARMONIC CURRENT
OTHERS
I/P-O/P:3KVAC
MIL-HDBK-217F (25
)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
File Name:HRP-200-SPEC 2010-05-12
HRP-200
200W Single Output with PFC Function
Mechanical Specification
Case No.902E
series
Unit:mm
3.5
9
7
197
1
9.5
2
80
5
8.2
85.5
4
98
3
6
7
Assignment
Pin No.
DC OUTPUT -V
4,5
DC OUTPUT +V
6,7
4-
M
3
57.5
4.5
120
199
6.5
9.5
Mating Housing
18.5
Pin No. Assignment
NC
1
2
NC
3
NC
4
NC
+S
5
-S
6
190
9
Connector Pin No. Assignment (CN100) :
HRS DF11-6DP-2DS or equivalent
Terminal
5
18
3.
13max.
150.75
M3
28
3-
HRS DF11-6DS HRS DF11-**SC
or equivalent
or equivalent
Block Diagram
fosc :70KHz
+S
ACTIVE
INRUSH
CURRENT
LIMITING
EMI
FILTER
I/P
38
Assignment
AC/L
AC/N
FG
LED
CN100
SVR1
3.5
3.5
28.5
Pin No.
1
2
3
1 5
2 6
Terminal Pin No. Assignment
RECTIFIERS
&
PFC
POWER
SWITCHING
O.T.P.
O.L.P.
RECTIFIERS
&
FILTER
Derating Curve
-S
DETECTION
CIRCUIT
FG
PFC
CONTROL
+V
-V
O.V.P.
PWM
CONTROL
Output Derating VS Input Voltage
Ta = 25
100
125
100
90
80
80
70
LOAD(%)
LOAD (%)
60
40
20
-30
0
10
20
30
40
50
AMBIENT TEMPERATURE ( )
60
70 (HORIZONTAL)
60
50
40
90
100
125
135
155
264
INPUT VOLTAGE (V) 60Hz
File Name:HRP-200-SPEC 2010-05-12
Similar pages