TRACO OrderCode Power supply Datasheet

Industrial Power Supplies
TBL Series, 15 to 150 Watt
CB
Features
Scheme
UL 508
IEC/EN 60950-1
◆ Low profile case, module depth only 55mm
◆ Fits into flat control panels used in
building automation
◆ Safety class ll product
◆ UL 1310 class II, NEC class 2 compliance
(models up to 90 W)
◆
◆
◆
◆
UL 508 listed
5 power ranges from 15 to 150 W
Universal input range 85 to 264 VAC
Operating temperature range:
–25°C to +70°C max.
◆ Adjustable output voltage
◆ Short circuit and overload protection
◆ DC–OK indicator
◆ Easy snap-on mounting on DIN-rail
or with wall mounting bracket (included)
◆ 3-year product warranty
The TBL series is a new range of small DIN-rail mount power supplies which have
been designed particularly with building- and factory automation applications in
mind. The ultra-compact low profile cases fit in the standardized wall mounted control panels used in the building automation industry. The power supplies can be
operated at full load across an ambient temperature range of –25°C to +60°C without need of additional cooling. Universal input voltage range and full compliance
with all important safety and EMC standards qualifies the TBL series power supplies for worldwide markets. For commercial and residential applications requesting
safety class ll the models up to 60 Watt are approved to UL 1310.
Models
Order Code
Output Power
(max.)
Output Voltage*
(nom.)
Output Current
(max.)
Efficiency
(typ.)
TBL 015-105
12 W
5.0 VDC
2.4 A
73 %
TBL 015-112
15 W
12 VDC
1.25 A
79 %
TBL 015-124
15 W
24 VDC
0.63 A
81 %
12 VDC
2.5 A
81 %
TBL 030-112
TBL 030-124
30 W
24 VDC
1.25 A
83 %
TBL 060-112
54 W
12 VDC
4.5 A
83 %
TBL 060-124
60 W
24 VDC
2.5 A
85 %
TBL 090-112
72 W
12 VDC
6.0 A
86 %
TBL 090-124
90 W
24 VDC
3.75 A
86 %
TBL 150-112
120 W
12 VDC
10 A
84 %
TBL 150-124
150 W
24 VDC
6.25 A
87 %
* adjustable
http://www.tracopower.com
Page 1 of 3
Industrial Power Supplies
TBL Series
15 to 150 Watt
Input Specifications
Input voltage
– AC nominal rated
TBL 150 models:
– AC range (designed for)
TBL 150 models:
– DC range (designed for)
– Power derating at low input voltage
100 – 240 VAC; 50/60 Hz
100 – 120 / 220 – 240 VAC; 50/60 Hz
85 – 264 VAC; 47 – 63 Hz
85 – 132 / 187 – 264 VAC; 47 – 63 Hz
120 – 373 VDC (except TLB 150 models)
5% below 90 VAC or 127 VDC
Harmonic limits EN 61000-3-2, Class A
Recommended circuit breaker (characteristic C or slow blow fuse) 6.0 A
Output Specifications
Output voltage adjustable range
Output regulation
5 VDC model: 5.0 – 5.2 VDC
12 VDC models: 12 – 16 VDC
24 VDC models: 24 – 28 VDC
1 %
Ripple and noise (20MHz bandwidth) <100 mV pk-pk
Electronic short circuit protection current limitation at 100 – 150 % typ.
(automatic recovery)
Overvoltage protection, trigger point
5 VDC model:
12 VDC models:
TBL 030-124, TBL 150-124:
TBL 015-124, TBL 060-124, TBL 090-124:
5.5 – 7.5 VDC
16 – 24 VDC
30 – 37 VDC
29 – 44 VDC
Hold-up time 115 VAC
min. 10 ms
230 VAC
min. 20 ms
General Specifications
Temperature ranges
– Operating –25°C to +70°C max.
– Storage –40°C to +85°C max.
Power derating
2.5 %/K above 60°C
Humidity (non condensing) 5 – 95 % rel. H
Temperature coefficient 0.02 %/K
Reliability, calculated MTBF at +25°C acc. to IEC 61709
TBL 015: >1,500 Mio h
TBL 060: >2,100 Mio h
all other models: >1,300 Mio h
Safety standards 15 – 90 W models:
UL 508
UL 1310, class II
IEC/EN 60950-1, UL 60950-1, EN 50178,
EN 60204, EN 61558-2-8
CSA C22.2 No. 60950-1 2003
Safety approvals
– CB report (IEC/EN 60950-1)
www.tracopower.com/products/tbl-cb.pdf
– UL approval UL 508 listed
www.tracopower.com/products/tbl-ul508.pdf
15 – 90 W models: UL 1310 listed
www.tracopower.com/products/tbl-ul1310.pdf
– CSA certification (UL 60950-1, CSA 60950-1-03)www.tracopower.com/products/tbl-csa.pdf
– SIQ certificate (IEC/EN 60950-1) www.tracopower.com/products/tbl-siq.pdf
– Bureau Veritas www.tracopower.com/products/tbl-bv.pdf
Electromagnetic compatibility (EMC), emissions EN 61000-6-3
– Conducted RI suppression on input EN 55022 class B
– Radiated RI suppression EN 55022 class B
Electromagnetic compatibility (EMC), immunity
– Electrostatic discharge (ESD)
– Radiated RF field immunity
– Electrical fast transient / burst immunity
– Surge immunity line – ground – Surge immunity line – line – Surge immunity output – Immunity to conducted RF disturbances
– Mains voltage dips and interruptions
http://www.tracopower.com
EN 61000-6-2
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-5
EN 61000-4-5
EN 61000-4-6
EN 61000-4-11
4 kV / 8 kV
3 V/m
1 kV / 0.5 kV
2 kV
1 kV
0.5 kV
3V
30 % /10 mS, 60 % /100 mS
Page 2 of 3
Industrial Power Supplies
TBL Series
15 to 150 Watt
General Specifications
Protection class class II as per IEC/EN 61140
Case protection IP 20 (IEC 60529)
Environment
– Vibration acc. IEC 60068-2-6; – Shock acc. IEC 60068-2-27
Enclosure material
3 axis, sine sweep, 10 – 55 Hz, 0.075 mm
3 axis, 15 g half sine, 11 ms
plastic FR2010-110C (UL 94V-0 rated)
Mounting DIN-rails as per EN 50022-35x15/7.5
(snap-on with self-locking spring or wall mounting
with bracket) (included)
Connection
screw terminals with combi-type screw heads
for wire size 0.5 – 1.5 mm²
Installation instructions www.tracopower.com/products/tbl-inst.pdf
Environmental compliance
– Reach www.tracopower.com/products/tbl-reach.pdf
– RoHS RoHS directive 2011/65/EU
Case Dimensions
TBL 015
26.3 (1.04)
100 (3.53)
TBL 030
52.5 (2.07)
160 (5.64)
TBL 060
70.0 (2.76
230 (8.11)
TBL 090
105.0 (4.13)
340 (12.0)
TBL 150
175 (6.89)
625 (22.0)
59.5 (2.34)
37.1 (1.46)
21.1 (0.83)
Vadj
89.5 (3.52)
Weigth
g (oz)
69.5 (2.74)
Width (W)
mm (inch)
45.0 (1.77)
Model
54.5 (2.15)
W
Dimensions in [mm], () = Inch
Tolerances: ±0.5 mm (±0.02)
Wall Mounting Bracket
Instead on a DIN-rail, the modules can be also mounted on a chassis or wall with help
of a mounting bracket which is supplied as standard with each power supply
Wiring
Description
Wire size
AC Input
all models: L, N only (2 pin terminal)
AWG 26 – 16 / 1.5 mm² max.
DC Output
15 – 30 W models: single terminal
AWG 26 – 14 / 1.5 mm² max.
DC Output
60 – 150 W models: double terminal
AWG 26 – 14 / 1.5 mm² max.
Specifications can be changed any time without notice.
Rev. 10/12
Jenatschstrasse 1 · CH-8002 Zurich · Switzerland
Tel. +41 43 311 45 11 · Fax +41 43 311 45 45 · [email protected] · www.tracopower.com
Page 3 of 3