Arch AQF600 Ac-dc switching power supply Datasheet

VER : A_6
update : 2016.03.28
AC-DC Switching Power Supply
AQF600 SERIES
600 Watts
KEY FEATURES







Universal Input: 90-264 VAC
With P.F.C. Function, PF>0.95
Remote ON/OFF Function
Current Share Function
Power Good Function
High Efficiency up to 90~93%
Protections: Over Load / Over Voltage /
.Over Temperature / Short Circuit
 High Power Density
 RoHS Compliant Design
 3-Year Product Warranty
ELECTRICAL SPECIFICATIONS
All specifications valid at normal input voltage, full load and +25°C after warm-up time unless otherwise stated.
Model No.
Max Output Wattage (Convection)
Voltage
Input
Output
Protection
Isolation
Function
Environment
(W)
AQF600-12S
540W
AQF600-24S
600W
AQF600-48S
600W
AQF600-54S
600W
90-264 VAC or 120-370 VDC
Frequency (Hz)
47-63 Hz
Current (Full load)
< 8.0 A max. (115 VAC) / < 3.5 A max. (230 VAC)
Inrush Current (<2ms)
< 15 A max. (115 VAC) / < 30 A max. (230 VAC)
Leakage Current
< 3.5 mA max.(240VAC 63Hz)
Power Factor
PF>0.99 (115 VAC) / PF>0.95 (230 VAC) at Full Load
Voltage (V.DC.)
12V
Trim
±5%
Voltage Accuracy
±2%
Current (Convection) (A) max
45
Line Regulation (LL-HL) (typ.)
±1%
Load Regulation (5-100%) (typ.)
±1%
Minimum Load
1%
Maximum Capacitive Load
60,000 uF
Ripple & Noise (max.)
< 1% Vout
Efficiency (typ.)
90%
Hold-up Time
12 ms min.
Over Power Protection
Auto recovery
Over Voltage Protection
Auto recovery
Over Temperature
Auto recovery
Short Circuit Protection
Latch off
Input-Output (V.AC)
3000VAC or 4242VDC
Input-FG
(V.AC)
1500V
Output-FG
.(V.AC)
500V
24V
48V
54V
25
12.5
11.1
50,000 uF
20,000 uF
10,000 uF
92%
92%
93%
5V Stand by (18CFM FAN)
5VSB: [email protected] ; Tolerance 10% , Ripple & Noise: 100m Vp-p (max.)
DC OK Signal (Power Good)
Turn ON: 3.7~5.7V ; Turn OFF: 0~1V
Remote Control
+RC / -RC: Power ON=open ; Power OFF=short
Current Share
CN4:CS, +V, -V are connected mutually in parallel.
Operating Temperature
-25°C…+70°C (with derating)
Storage Temperature
-25°C…+85°C
Temperature Coefficient
±0.03%/°C ( 0~50°C )
Humidity
95% RH
MTBF
>100,000 h @ 25°C (MIL-HDBK-217F)
Vibration
10~500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes.
http://www.archcorp.com.tw
TEL: +886-2-26989508 FAX: +886-2-26981319
-1-
VER : A_6
update : 2016.03.28
AC-DC Switching Power Supply
AQF600 SERIES
600 Watts
ELECTRICAL SPECIFICATIONS
All specifications valid at normal input voltage, full load and +25°C after warm-up time unless otherwise stated.
Model No.
AQF600-12S
Dimension (L x W x H)
Physical
Safety
EMC
AQF600-24S
9.0 x 4.13 x 1.72 Inches
Weight
1024±50 g
Cooling
Integral fan
Agency Approvals
CE, UL60950-1
AQF600-48S
AQF600-54S
(228.5 x 105.0 x 44.0 mm ) Tolerance 0.5 mm
EMI (Conducted & Radiated Emission)
EN 55022 class B, Radiated Class A
EMS (Noise Immunity)
EN 55024
Surge
1KV L-N, 2KV L N-FG
NOTE
1. Ripple & Noise are measured at 20MHz of bandwidth with 0.1uF & 47uF parallel capacitor.
2. Strongly recommend to conduct this test with DC Voltage. If customer wishes to test with AC Voltage,
please disconnect all Y-Capacitors within Arch power supply.
BLOCK DIAGRAM
DERATING
http://www.archcorp.com.tw
TEL: +886-2-26989508 FAX: +886-2-26981319
-2-
VER : A_6
update : 2016.03.28
AC-DC Switching Power Supply
AQF600 SERIES
600 Watts
MECHANICAL DIMENSION
AC Input Terminal Pin
PIN#
Single
1
AC IN
DC Output Terminal Pin
PIN#
Single
2~4
+DC OUT
5~7
-DC OUT
Connector Pin (CN4)
PIN#
Single
C1
+S
C2
-S
C3
CS
C4
GND
C5
GND
C6
+RC
C7
+PG
C8
+5V-AUX
ASSEMBLY INSTRUCTIONS
*U Case T=2.0mm
Customer is advised to screw into the threads no more than 2.0mm
http://www.archcorp.com.tw
TEL: +886-2-26989508 FAX: +886-2-26981319
-3-
VER : A_6
update : 2016.03.28
AC-DC Switching Power Supply
AQF600 SERIES
600 Watts
FUNCTION DESCRIPITON of CN4
Pin No.
Function
C1
+S
Description
Current Share Function Pin
C2
-S
C3
CS
C4
GND
C5
GND
This pin connects to the negative terminal(-V). Return for DC-OK signal output.
C6
+RC
Turns the output on and off by electrical or dry contact between pin C4 (-RC), Short: Power OFF, Open: Power ON.
C7
+PG
C8
+5V-AUX
This pin connects to the negative terminal(-V). Return for DC-OK signal output.
DC-OK Signal is a DC output, referenced to pinC6(DC-OK GND).
Stand by voltage output ground 4.5~5.5V, referenced to pin C4 or C5(GND). The maximum load current is 0.6A.
FUNCTION MANUAL & APPLICATION NOTE
1. DC-OK Signal
Between DC-OK(pinC5)
and GND(pinC6)
Output
Status
3.7~5.7V
0~1V
ON
OFF
2. Remote Control
It can be turned ON/OFF by using the "Remote Control" function.
Between RC+(pinC3) and
RC-(pinC4)
Output
Status
SW ON (Short)
SW OFF (Open)
OFF
ON
3. Current Share
1. Difference in Vout among parallelled units should be less than +/-1%
2. Output Power at Parallel Operation = Rated Power per Unit x Number of Unit x 80%
3. Connect in parallel no more than 2 units. Please contact Arch for advice if more than 2 is needed.
4. Shorter wiring to each unit is recommended, as well as twisting +S and -S in pairs, as shown below
5. The remote sensing compensates voltage drop on the load wiring up to 5V
http://www.archcorp.com.tw
TEL: +886-2-26989508 FAX: +886-2-26981319
-4-
VER : A_6
update : 2016.03.28
AC-DC Switching Power Supply
AQF600 SERIES
600 Watts
4. 1+1 Redundancy:sing 1 more AQF600 as the redundant unit
5. 1+N Redundancy: Using more AQF600 as the redundant units to increase the reliability
http://www.archcorp.com.tw
TEL: +886-2-26989508 FAX: +886-2-26981319
-5-
Similar pages