ETC2 A13X400-4TA Semiconductor protection fus Datasheet

AMP-TRAP®–Form 101
A13X
SEMICONDUCTOR PROTECTION FUSES
A13X Amp-trap® Form 101 Semiconductor Protection
fuses were designed for the specific protection of
diodes and other semiconductor devices rated
130VAC or less. A13X fuses are very small for their
ampere ratings, especially the hockey-puck type in
the higher ampere ratings.
Features / Benefits
➤ Low l2t minimizes damage to protected components on
short circuit
➤ Controlled arc voltage reduces stress to circuit
components during fuse clearing
➤ Choice of mounting types helps in equipment design
Ratings
HIGHLIGHTS:
➤
Fast Acting
➤ Current Limiting
2
➤ Low l t
➤ Indicator Options
Available
APPLICATIONS:
➤ Protection of heavy
duty devices such
as electrochemical
rectifiers
➤ AC: 1-6000A
130VAC, 8kA I.R.
➤ UL Recognized
Component
➤ DC: 70-2000A
100VDC,10kA I.R.
2500-3000A
100VDC, 20kA I.R.
L/R=10ms
➤ AC: Guide No. JFHR2
(1-25A, 70-2000A)
Amp-trap® Fuse
A
Rated Volts - 130
13
Amperes*
Mounting Types*
Ferrule
Ferrule, midget dims.
(1-1/2” x 13/32”)
Blades, bolt-in
Hockey puck, bolt-in
Single Pole Fuse Blocks for A13X Fuses
FUSE BLOCK
CATALOG
NUMBER
1-30
31-60
61-100
101-200
201-450
500-600
30311
60306J
P243D
P243D
P243D
P243G
➤ DC Tested to UL
Standard198L parameters
(70-3000A)
Catalog Numbering System
Style
FUSE
AMPERE
RATING
Approvals
Integral Blown-Fuse
Indicator
Trigger Indicator
Trigger Actuator
A 13 X 400 - 4 TI
X
400
1
2
4
128
TI
TA
* For ampere ratings and types not listed, consult the factory.
D2
AMP-TRAP®–Form 101
A13X
SEMICONDUCTOR PROTECTION FUSES
Standard Fuse Ampere Ratings, Catalog Numbers
AMPERE
RATING
CATALOG
NUMBER
OUTLINE AMPERE
FIG.
RATING
1
2
3
4
5
6
7
8
10
12
15
20
25
30
35
40
40
45
50
50
55
A13X1-2
A13X2-2
A13X3-2
A13X4-2
A13X5-2
A13X6-2
A13X7-2
A13X8-2
A13X10-2
A13X12-2
A13X15-2
A13X20-2
A13X25-2
A13X30-2
A13X35-1
A13X40-1
A13X40-4TI
A13X45-1
A13X50-1
A13X50-4
A13X55-1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
2
1
60
70
70
80
80
90
100
100
130
130
150
150
150
200
200
250
250
300
300
300
350
CATALOG
NUMBER
OUTLINE AMPERE
FIG.
RATING
A13X60-1
A13X70-4
A13X70-4TI
4A13X80-4
4A13X80-4TI
A13X90-4
A13X100-4
A13X100-4TI
A13X130-4
A13X130-4TI
A13X150-4
A13X150-4TA
A13X150-4TI
A13X200-4
A13X200-4TA
A13X250-4
A13X250-4TI
A13X300-4
A13X300-4TA
A13X300-4TI
A13X350-4
1
2
2
2
2
2
2
2
2
2
2
3
2
2
3
2
2
2
3
2
2
350
400
400
400
450
450
500
500
600
800
800
1000
1000
1000
1000
1000
1200
1200
1200
1500
2000
CATALOG
NUMBER
OUTLINE AMPERE
FIG.
RATING
A13X350-4TI
A13X400-4
A13X400-4TA
A13X400-4TI
A13X450-4
A13X450-4TA
A13X500-4
A13X500-4TA
A13X600-4
A13X600-4TA
A13X800-4
A13X1000-4
A13X1000-4TA
A13X1000-4TI
A13X1000-128
A13X1000-128TA
A13X1200-128
A13X1200-128TA
A13X1500-128
A13X1500-128TA
A13X2000-128
2
2
3
2
2
3
2
3
2
3
2
2
3
2
4
5
4
5
4
5
4
2000
2500
2500
3000
3000
3500
4000
4000
5000
6000
CATALOG
NUMBER
OUTLINE
FIG.
A13X2000-128TA
A13X2500-128
A13X2500-128TA
A13X3000-128
A13X3000-128TA
A13X3500-128
A13X4000-128
A13X4000-128TA
A13X5000-128
A13X6000-128
5
4
5
4
5
6
6
7
8
8
D
For ampere ratings and styles not listed, call Technical Services.
Figure 4
Figure 3
Figure 2
Figure 1
Figure 6
Figure 5
Figure 8
Figure 7
Dimensions
OUTLINE
REF.
MOUNTING
TYPE
FIG.
A13X1 to 30
2
1
A13X35 to 60
1
1
A13X70 to 450
4, 4TA*
2, 3*
A13X500 to 1000
4, 4TA*
2, 3*
A13X1000 to 2000
128
4
A13X2500 to 3000
128, 128TA*
4, 5*
A13X3500 to 4000
128, 128TA*
6, 7*
A13X5000 to 6000
128
8
DIMENSIONS - INCHES (mm)
C
D
E
F
A
B
1.50
(38.1)
2.00
(50.8)
2.66
(67.6)
3.50
(88.9)
.41
(10.4)
.81
(20.6)
1.13
(28.7)
1.50
(38.1)
1.16
(29.5)
1.25
(31.8)
2.19
(55.6)
2.56
(65.0)
1.91
(48.5)
1.94
(49.3)
1.88
(47.8)
1.88
(47.88)
1.88
(47.88)
2.38
(60.5)
2.00
(50.8)
3.00
(76.2)
3.50
(88.9)
5.75
(146)
1.63
(41.4)
1.63
(41.4)
1.63
(41.4)
1.88
(47.7)
1.75
(44.5)
2.50
(63.5)
3.00
(76.2)
5.00
(127)
1.00
(25.4)
1.50
(38.1)
1.06
(27.0)
1.50
(38.1)
* Optional Trigger Actuator (TA)
D3
TAP
G
H
.31
(7.9)
.41
(10.4)
.88
(22.4)
1.00
(25.4)
.19
(4.8)
.25
(6.4)
-
1.06
(27.0)
1.50
(38.1)
-
-
3/8-24-1/2 Deep
1/2-20-1/2 Deep
1/2-20-1/2 Deep
1/2-20-1/2 Deep
-
Current in Amperes
Melting Time – Current Data, 130V Fuses
A13X
Current in Amperes
Melting Time – Current Data, 130V Fuses
AMP-TRAP®–Form 101
SEMICONDUCTOR PROTECTION FUSES
A13X70 to 6000
Time in Seconds
A13X1 TO 60
Time in Seconds
D4
AMP-TRAP®–Form 101
A13X
SEMICONDUCTOR PROTECTION FUSES
Peak Let-Thru Current Data – A13X1 to 6000, 130 Volts AC
Maximum Instantaneous Peak Let-Thru Amperes
130 VAC
Fault
Load
Fault
Load
Fig. A
130 VAC
Fig. B
I2t Data – 130 Volts AC
FUSE
AMPERE
RATING
MELTING
(A2s)
Available Current in RMS Symmetrical Amperes
Watts Loss at Rated Current
AMPERE
RATING
WATTS
LOSS (W)
AMPERE
RATING
WATTS
LOSS (W)
70
80
90
100
130
150
200
250
300
2.7
3.2
3.9
4.1
5.8
6.6
9.1
12
15
350
400
450
500
600
800
1000
1200
1500
18
20
23
20
26
37
44
52
65
AMPERE WATTS
RATING LOSS (W)
2000
2500
3000
3500
4000
4500
5000
6000
92
116
149
178
190
240
280
356
Correction Factor for Watts Loss
Watts Loss Correction vs. Percent Rated Current
Percent Rated Current
D5
1
2
3
4
5
6
7
8
10
12
15
20
25
30
35
40
45
50
55
60
70
80
90
100
130
150
200
250
300
350
400
450
500
600
800
1,000
1,200
1,500
2,000
2,500
3,000
3,500
4,000
5,000
6,000
.02
.10
.18
.50
.75
1.1
1.6
2.9
5.0
6.3
10
34
65
100
85
120
150
240
280
340
840
1,000
1,300
1,600
2,500
3,600
6,400
10,000
14,000
20,000
26,000
32,000
40,000
58,000
100,000
160,000
240,000
360,000
640,000
1,000,000
1,400,000
1,800,000
2,400,000
3,700,000
5,400,000
I2t DATA
CLEARING AT 130V
1 FUSE
2 FUSES IN
(FIG. A) SERIES (FIG. B)
(A2s)
(A2s)
.1
.35
.7
2
3
4
6
10
18
22
35
120
230
350
450
640
800
1,300
1,500
1,800
4,200
5,000
6,500
8,000
12,000
18,000
32,000
50,000
70,000
100,000
130,000
160,000
200,000
290,000
500,000
800,000
1,200,000
1,800,000
3,200,000
5,000,000
7,000,000
9,000,000
12,000,000
18,000,000
27,000,000
.05
.25
.5
1.5
2
3
4
7
12
15
25
80
150
230
300
420
520
840
1,000
1,200
2,100
2,500
3,300
4,000
6,300
9,000
16,000
25,000
35,000
50,000
65,000
80,000
100,000
140,000
250,000
400,000
600,000
900,000
1,600,000
2,500,000
3,500,000
4,500,000
6,000,000
9,000,000
14,000,000
D
Similar pages