Chinfa BS-DRA240 Ac - dc din rail mountable power supply industrial control equipment Datasheet

DRA240* SERIES
FOR DC BACKUP SYSTEM
AC - DC DIN RAIL MOUNTABLE POWER SUPPLY
INDUSTRIAL CONTROL EQUIPMENT
FEATURES
‧PFC FUNCTION AVAILABLE
‧INPUT VOLTAGE 115/230VAC AUTO SELECT
‧SELV COMPONENTS DESIGN
‧3 YEARS WARRANTY
R
R
H H
Class I, Div 2
a
UL 60950-1
IND. CONT. EQ.
UL 508
EN 60950-1
SELECTION CHART
DRA 240 - 24 A *
Wattage
24 : 27.2V OUT
48 : 54.5V OUT
DC Backup System
SCREW TERMINAL
MODEL LIST
MODEL NO.
INPUT
VOLTAGE
DRA240-24A*
115 / 230 VAC
240 WATTS
DRA240-48A*
115 / 230 VAC
240 WATTS
- - ++ Rdy
OUTPUT
CURRENT
EFF.
(min.)
EFF.
(typ.)
+ 27.2 VDC
8.8 A
87%
89%
+ 54.5 VDC
4.4 A
88%
90%
OUTPUT
OUTPUT
WATTAGE
VOLTAGE
Single Output Models
+
- - ++ Rdy
+
Rdy
K1
Rdy
DRA240*
Series
K1
D1
D1
K1
Fuse
LOAD
DRA240*
Series
Fuse
LOAD
Rdy
BATTERY
Rdy
DRA240* Series For DC Backup System Application
K1
BATTERY
DRA240* Series For DC Backup System Application
Note :
1.The suffix "*" is part of the model number, which specifies the product is designed and pre-trim for low-cost DC backup power system with
external Lead-Acid battery, Relay and Fuse.
2.The manufacturer is liable neither for the external components nor the damage to the power supply causing by external components.
3.The total consumption current including loading and battery charging current should not exceed the maximum rated current of power supply.
4.The operation concept of DC backup power system :
A. When AC power alive : The "Rdy" is close circuit to active the external Relay . The power supply feeds current into the external loads and
charges through Relay to the external battery as well.
B. When AC power interrupted : The "Rdy" is remain close circuit to maintain the external Relay remain active, the external battery supply
current to the external loads.
C. When Battery power low : The "Rdy" become open circuit and the external Relay become inactive to disconnect the battery from
external loads.
www.chinfa.com
2015.05.12
[email protected]
P1
FOR DC BACKUP SYSTEM
SPECIFICATION
DRA240* SERIES
o
All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed
GENERAL
Characteristics
typ.
min.
Conditions
max.
unit
Switching frequency
Vi nom, Io nom
Isolation voltage
Input-Output
3,000 / 4,242
VAC / VDC
Input-FG
1,500 / 2,121
VAC / VDC
500 / 710
VAC / VDC
40
Output-FG
Isolation resistance
Ambient temperature
Derating (see derating curve)
Input-Output, @ 500VDC
100
Operating at Vi nom
-40
KHz
MΩ
o
+ 71
o
C
o
Storage temperature
Vi nom, from +61 to +71 C
Non operational
-40
+ 85
Relative humidity
Vi nom, Io nom
20
95
% RH
Temperature coefficient
Vi nom, Io min
± 0.03
%/ C
MTBF
Altitude during operation
Dimension
Cooling
Installation position
%/ C
2.5
o
Bellcore Issue 6 @40 C, GB
24V
459,000
48V
520,000
o
C
o
Hours
Hours
m
5,000
EN 60950-1
Screw terminal type
mm
L124.5 x W83.5 x D123.6
Free air convection
Vertical ( other direction may derating using )
Pollution degree
2
INPUT SPECIFICATIONS
Characteristics
Conditions
Rated input voltage
Io nom
Absolute input max. range
Ta min ... Ta max,
Io nom
min.
unit
VAC
AC in
115 V selected
90
132
VAC
AC in
230 V selected
180
264
VAC
375
VDC
DC in
Vi : 115 / 230 VAC, Io nom
Rated input current
Vi : 90 / 180 VAC, Io nom
Line frequency
Vi nom, Io nom
Inrush current
Vi : 115 / 230 VAC , Io nom
Power dissipation
Vi : 230 VAC, Io nom
Power factor (Passive)
max.
115 / 230 (auto select)
Input current
Leakage current
typ.
210
4.0 / 1.55
47
A
5.4 / 2.2
A
63
Hz
30 / 60
A
24V
35
W
48V
32
W
Input-Output
0.25
mA
Input-FG
3.5
mA
max.
unit
±1
%
Vi : 230VAC, Io nom
0.7
OUTPUT SPECIFICATIONS
Characteristics
Conditions
min.
typ.
Output voltage accuracy
(Adjusted before shipment)
Vi nom, Io max
Minimum load
Vi nom
Line regulation
Io nom, Vi min ...Vi max
± 0.5
%
Load regulation
Vi nom, Io min ...Io nom
±1
%
Voltage trim range
Vi nom, 0.8 Io nom
0
Hold up time
Vi : 115 / 230 VAC , Io nom
Turn on time
Vi nom, Io nom
Vi nom, Io nom
Rise time
with 7000μF CAP
Vi nom, Io nom
Vi nom, Io nom
with 7000μF CAP
Fall time
Vi nom, Io nom
Transient recovery time
Vi nom, 1~0.5 Io nom
www.chinfa.com
2015.05.12
%
24V
22.5
28.5
VDC
48V
47
56
VDC
ms
25 / 30
2,500
ms
2,500
ms
150
ms
500
ms
150
ms
2
ms
[email protected]
P2
FOR DC BACKUP SYSTEM
DRA240* SERIES
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed
OUTPUT SPECIFICATIONS
Characteristics
Vi nom, Io nom, BW = 20MHz
Power back immunity
Vi nom, Io nom
Capacitor load
Vi nom, Io nom
DC ON indicator threshold
at start up (Green LED)
Vi nom, Io nom
DC LOW indicator threshold
after start up (Red LED)
Vi nom, Io nom
typ.
min.
Conditions
Ripple & noise
24V
35
48V
63
max.
unit
100
mV
VDC
VDC
7,000
μF
24V
21.2
22.2
VDC
48V
42.8
43.8
VDC
24V
21.1
22.1
VDC
48V
42.7
43.7
VDC
max.
unit
CONTROL AND PROTECTION
Characteristics
Input fuse
T6.3A / 250VAC internal
Internal surge voltage protection
IEC 61000-4-5
Rated over load protection
Vi nom
Power Rdy
Rdy Close indicator threshold
at start up
24V
48V
Rdy Open indicator threshold
after start up
24V
48V
Power Rdy
typ.
min.
Conditions
Varistor
125
%
21.2
22.2
VDC
42.8
43.8
VDC
21.1
22.1
VDC
42.7
43.7
VDC
105
Electrical isolation
500
VDC
Contact rating at 60VDC
Over voltage protection
Vi nom, 0.8 Io nom (Auto Recovery)
24V
30
48V
60
Output short circuit
Fold forward
Degree of protection
IP20
0.3
A
33
V
66
V
APPROVALS AND STANDARDS
UL / cUL
UL 508 Listed
UL 60950-1 Recognized
ISA 12.12.01(Class I, Division 2, Groups A, B, C and D)
TUV
EN 60950-1
CE
EN 61000-6-3, EN 55022 Class B, EN 61000-3-2 Class D, EN 61000-3-3
EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3
EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3, L / N-FG Level 4
EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11
ENV 50204 Level 2, EN 61204-3
CCC
GB4943.1, GB9254, GB17625.1
Vibration resistance
meet IEC 60068-2-6 (Mounting on rail : 10-500 Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis )
Shock resistance
meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 Faces, 3 times for each Face)
PHYSICAL CHARACTERISTICS
Case size
124.5 x 83.5 x 123.6 mm (4.9x 3.29 x 4.87 inches)
Case material
Metal
Weight
1380 g
Packing
1.5 kg ; 16
www.chinfa.com
2015.05.12
/ 25 kg / 2.01 CUFT
[email protected]
P3
DRA240* SERIES
FOR DC BACKUP SYSTEM
MECHANISM & PIN CONFIGURATION
mm [inch]
CONSTRUCTION
Easy snap-on mounting onto the DIN-Rail
(TS35/7.5 or TS35/15), unit sits safeIy and
firmly on the rail.
116.60 [4.59]
83.5 0 [3.2 9]
6
7.00 [0.30]
- - ++ Rdy
Vout ADJ.
124.50 [4.90]
DC LO
DC ON
DRA240*
L
7
INSTALLATION
Ventilation / Cooling
Normal convection
All sides 25mm free space
For cooling recommended
Connector size range
Screw terminal:
AWG24-10(0.2~4mm2 ) flexible / solid cable,
-Input connector can withstand torque at
maximum9pound-inches.
-Output connector can withstand torque at
maximum5.5pound-inches.
8 m/m stripping at cable end recommends
o
Use copper conductors only, 60 / 75 C
1
N
GENERAL TOLERANCE
0.00[0.00] - 30.00[1.18]
±0.30[0.01]
30.00[1.18] - 120.00[4.72]
±0.50[0.02]
120.00[4.72] - 400.00[15.75]
±0.80[0.03]
9
PIN ASSIGNMENT
Designation
PIN NO.
OUT
1, 2
3, 4
5, 6
Description
RDY
A normal open relay contact for DC ON level control
V+
Positive output terminal
V -
Negative output terminal
Ground this terminal to minimize high-frequency emissions
IN
7
8
OTHER
9
L
Input terminals (phase conductor, no polarity at DC input)
N
Input terminals (neutral conductor, no polarity at DC input)
DC ON
Operation indicator LED
DC LO
DC LOW voltage indicator LED
Vout ADJ.
Trimmer-potentiometer for Vout adjustment
CIRCUIT SCHEMATIC
‧Block diagram for DRA240* series
L
Fuse
Filter
N
Inrush Current
Limiter,
Rectifier and
Auto Select
115 / 230 Vac
Y
Vo +
PFC
Circuit
Smoothing
Circuit
Switching
Device
PWM
Controller
Rectifier
Current
Detection
Vo -
Opto Isolation
Reference &
Error Amp.
Opto Isolation
Over Voltage
Detection
Vout
ADJ.
Output
Level
Detection
DC ON
(Green LED)
DC LOW
(Red LED)
RDY
(Relay Contact)
DERATING CURVE
Power out [ % ]
100
75
Safe Operating Area
0
-40
www.chinfa.com
2015.05.12
61
Temperature [ oC ]
71
[email protected]
P4
Similar pages