Copal C-CT-10 Ac current sensor Datasheet

C-CT
AC CURRENT SENSORS
RoHS compliant
■ FEATURES
■ APPLICATIONS
O Clamp-on type (split core design)
Easy installation to distribution panels
O Compact size and wide measuring range
O Outstanding output linearity at all current ranges
O Direct interface
O Overvoltage protection (zener diode)
O UL94 V-0 flame rating
O To measure or monitor current or power consumption
in smart energy systems such as:
・HEMS (Home Energy Management System)
・BEMS (Building Energy Management System)
・Various power monitoring systems
■ PART NUMBER DESIGNATION
C - CT - 6
Series Name
6:φ 6 mm
16:φ16 mm
Hole Diameter
10: φ 10 mm
24: φ 24 mm
■ LIST OF MODEL NUMBER
Part Number
Rated Primary Current
C-CT-6
AC 0.1 30 A
(50/60 Hz)
AC
C-CT-10
AC 0.1 60 A
(50/60 Hz)
AC 100 Arms continuous
C-CT-16
C-CT-24
AC 0.1 100 A
(50/60 Hz)
AC 0.1 200 A
(50/60 Hz)
Max. Input Current
50 Arms continuous
AC 200 Arms continuous
AC 300 Arms continuous
Output characteristic Example
Size and Weight
AC 100 mV±1 %
(AC30 A RL=10 Ω 50/60 Hz)
19.3×26.4×31 mm,
Approx. 20 gs
AC 200 mV±1 %
(AC60 A RL=10 Ω 50/60 Hz)
AC 333 mV±1 %
(AC100 A RL=10 Ω 50/60 Hz)
AC 666 mV±1 %
(AC200 A RL=10 Ω 50/60 Hz)
26.4×25.5×43.3 mm,
Approx. 40 gs
32.5×30.5×46.2 mm,
Approx. 75 gs
48.4×35.5×69.6 mm,
Approx. 170 gs
C-CT
AC CURRENT SENSORS
■ SPECIFICATIONS
Part Number
C-CT-6
C-CT-10
C-CT-16
C-CT-24
Rated Primary Current
AC 0.1 〜 30 A
(50/60 Hz)
AC 0.1 〜 60 A
(50/60 Hz)
AC 0.1 〜 100 A
(50/60 Hz)
AC 0.1 〜 200 A
(50/60 Hz)
Max. Input Current
AC 50 Arms
continuous
AC 100 Arms
continuous
AC 200 Arms
continuous
AC 300 Arms
continuous
AC 100 mV±1 %
AC 200 mV±1 %
AC 333.3 mV±1 %
AC 666.6 mV±1 %
Output characteristic
Example
(AC30 A RL=10 Ω 50/60 Hz)(AC60 A RL=10 Ω 50/60 Hz)(AC100 A RL=10 Ω 50/60 Hz)
(AC200 A RL=10 Ω 50/60 Hz)
Phase Accuracy
+2.5°±0.5°
(AC30 A RL=10 Ω 50 Hz)
+2.1°±0.5°
(AC30 A RL=10 Ω 60 Hz)
Hole Diameter
φ6 mm
+1.6°±0.5°
+0.9°±0.5°
+0.3°±0.5°
(AC60 A RL=10 Ω 50 Hz)
(AC100 A RL=10 Ω 50/60 Hz)
(AC200 A RL=10 Ω 50/60 Hz)
+1.3°±0.5°
(AC60 A RL=10 Ω 60 Hz)
φ10 mm
φ16 mm
Nominal Current Ratio
3000:1
Applicable Frequency
10 Hz〜5 kHz
Max. Circuit Voltage
Less than AC600 V
(for insulated cable)
Withstanding Voltage
AC 2200 V/1 minute
(between output terminal and outer case)
Insulation Resistance
More than 50 MΩ by 500 V insulation tester
(between output terminal and outer case)
Open Circuit Protection
7.5 V(Zener diode)
Operational Temperature
-20 〜 60 ℃, less than 80 %RH
Without condensation
Storage Temperature
-30 〜 60 ℃, less than 80 %RH
Without condensation
Flame Rating
UL94 V-0
Output Cable lead
AWG24
Approx. L=200 mm
Size and Weight
19.3×26.4×31 mm
Approx. 20 gs
φ24 mm
AWG22
Approx. L=150 mm
26.4×25.5×43.3 mm
Approx. 40 gs
■ PACKAGING SPECIFICATIONS
O Bulk Packing specifications
Individually packaged in a plastic bag (1pc per bag),
it can order from 1pc.
32.5×30.5×46.2 mm
Approx. 75 gs
48.4×35.5×69.6 mm
Approx. 170 gs