Gamewell-FCI INCC-IDT Intelligent network command center Datasheet

INCC and
E3 LOC, INCC CAB-B
Description
Intelligent Network Command Center
The Gamewell-FCI, INCC Intelligent Network Command
Center serves as the point of interface between an operator and the system’s audio evacuation, fire fighter intercom, and building control circuits. It is a component of the
following systems.
• E3 Series® Expandable Emergency Evacuation
• E3 Series Combined Fire and Mass Notification System
• E3 Series Broadband Audio Evacuation System
• NetSOLO® System
The INCC occupies a single node along the E3 Broadband
network and is connected by a single pair of twisted,
unshielded wire, fiber-optic cable or any combination of
the two. Each E3 Broadband node can be spaced along
the network at a maximum distance of 3,000 feet (914.4 m)
or up to an 8dB loss using fiber-optic cable. Built-in isolation at each node permits Style 4, Style 6, and Style 7 network configurations.
The E3 Series Broadband Audio Evacuation System is a
peer-to-peer, self-regenerating, token ring network comprised of up to 64 individual nodes. in addition, the
Addressable Node Expander (ANX) board expands the
network to 122 nodes. The E3 Broadband employs proven
technology and extends it to accomplish emergency voice
evacuation, 2-way fire fighter communications, and building control applications. It is unique in the industry
because it requires only a single pair of wires or a fiberoptic cable connection between nodes to convey all fire
alarm, digital voice, fire fighter communications, paging,
and building control signals.
The typical INCC and E3 LOC, INCC-CAB-B sub-assemblies consist of the following:
• an Intelligent Network Interface-Voice Gateway
(INI-VGC) Module
• one or more Addressable Switch Modules (ASM-16)
• one Network Graphic Touchscreen Annunciator (NGA)
The INCC Command Center’s INI-VGC module also provides connections for an optional emergency Voice Page
Microphone as well as a Fire Fighter Telephone Handset.
The INI-VGC is a fully digital voice/tone generator using
state-of-the-art Digital Signal Processing (DSP) technology to produce the clearest, most audible signal possible.
The INI-VGC provides an output to a local speaker for
message verification and testing. It is ideal for a wide
range of complex System Applications including high-rise
or campus installations.
INCC
Features
• Listed under UL® Standard 864, 9th Edition.
• Listed under UL Standard UL2572 for Mass Notification.
• All communication signals and control-by-event
sequences over twisted, unshielded pair of wires or
fiber-optic cable including:
- Audio Evacuation
- Fan Control & Damper
Shutdown
- Voice Paging
- Door Closures
- Fire Fighter Intercom - Fire Alarm and Control Devices
- Elevator Control
- Horn/Strove Circuit Activation
• Distributed architecture, including Style 7 wiring configurations, allow system components to continue normal
operation with NO loss of function during single line
fault conditions.
• Integrates with INX transponders and additional INCC
command centers to create a complete audio evacuation system with up to 122 nodes.
• Each INI-VGC supports up to 16 ASM-16 switch modules for a total of 256 switches.
• INI-VGC connects to a Voice Page Microphone and
Fire Fighter’s Handset.
• Redundant Command Centers with Microphone and
Fire Fighter’s Handset can be easily configured by
adding additional INCCs.
• Advance Boolean logic-based programming such as
AND, OR, NOT, NOR, time delay, and calendar functions configurable through computer programming.
• Advanced digital signal processor (DSP) technology for
efficient audio compression and filtering. Uses network
data transfer rate at 625K baud.
SIGNALING
MEA
City of
City of
Approved
Chicago
Denver
FDNY
APPROVED
Approved Approved
S1869 3025415 COA # 6077 7165-1703:0125 Class 1
FM
Class 2
High Rise
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0542 Rev. J page 1 of 4
©2013 by Honeywell International Inc. All rights reserved.
Description (Continued)
Each Addressable Switch Module (ASM-16) has 16 pushbutton switches that can be programmed to serve any
function the application demands. An ASM-16 switch can
be programmed as any of the following:
• Speaker Circuit switch
• Fire Fighter Phone switch
• Auxiliary Control switch using a bank of 3 switches
(1 switch can be used for each On-Off-Auto function)
• Switches with the following custom-defined functions”
- System Reset
- All-Call
- System Silence
- Phone Patch
- System Acknowledge
- Lamp Test
- Alarm Tone On
- Manual Select
Each ASM-16 switch also has 3 fully programmable status-indicating LEDs in red, yellow, and green. The NGA
LCD Graphic Annunciator is a powerful, yet attractive component of the Gamewell-FCI Emergency Voice Evacuation
System. The bright, back-lit 1/4” VGA display is supplemented with an intuitive, easy-to-use touch-screen interface that provides the following features:
• Up to 512 user-defined messages may be configured.
• Messages may be up to 77 characters in length.
• Display font and color may be selected for each
message.
Figure 1 INCC with MIC and Handset
The INCC assembly is enclosed in one or more compact
19” wall-mounted enclosures. Its modular construction
provides complete flexibility in system design. Each cabinet can contain the INI-VGC and up to six ASM-16 modules. If more ASM-16 modules are required, they may be
mounted in additional INCC cabinets. As many as six
ASM-16 modules can fit in the INCC cabinet. If a Microphone module is required, it would take the place of 1
ASM-16 position. A Fire Fighter Handset would take the
place of 2 ASM-16 positions. An INI-VGC can support as
many as 16 ASM-16s for a total of 256 completely programmable switches.
The INCC operates on 24 VDC that can be sourced from
the non-resettable auxiliary output of its associated power
supply such as the PM-9 or PM-9G.
Figure 2 INCC with 6 ASM-16s
A complete E3 Series Audio Evacuation System can be
assembled from the following 3 different panels. This modular approach greatly simplifies the design and installation
process and can be configured to meet the exact needs of
the project.
• One or more E3 Series fire alarm control panels.
• One or more INCC Audio Evacuation Command Centers.
• One or more INX Transponders.
• One ACU (Autonomous Control Unit).
• One LOC (remote Local Operating Console).
®
®
E3 Series and NetSOLO are registered trademarks of Honeywell International Inc.
®
UL is a registered trademark of Underwriters Laboratories Inc.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0542 Rev. J page 2 of 4
www.gamewell-fci.com
INCC BACKBOX
WITH INI-VGC
INCC INNER DOOR
SHOWN WITH ASM-16
HANDSET & MICROPHONE
INNER DOOR ASSEMBLY
Figure 3 INCC and E3 LOC, INCC-CAB-B Assemblies
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
www.gamewell-fci.com
9020-0542 Rev. J page 3 of 4
Specifications
Ordering Information
INI-VGC
Description
Part Number
Intelligent Network Command Center
Operating Voltage: 24 VDC (nominal)
Operating
0.150 amp. supervisory and alarm
Current:
Operating
32° to 120° F (0° to 49° C)
Temperature:
Relative Humidity: 0 to 93% (non-condensing)
Protocol
Asynchronous with half-duplex data
flow
Speed
RS-232 up to 64 KBps
RS-485 up to 128 KBps
St connectors
Up to 200 microns (multi-mode),
optimized for 62.5/125 microns.
INI-VGC
ASM-16
INCC-MIC
INCC-TEL
INCC-IDT
INCC-ID
INCC-CAB
Dimensions:
ASM-16
Operating Voltage: 24 VDC (nominal)
Operating
Current:
0.005 amp supervisory
0.005 amp alarm plus 0.003 amp per
LED activated (0.195 amp max.)
Operating
Temperature:
32° to 120° F (0° to 49° C)
Relative Humidity: 0 to 93% (non-condensing)
INCC-CABR
Dimensions:
Command center voice gateway.
Programmable switch module
(occupies 1 single slot on the inner
door).
Paging Microphone module.
Fire Fighter Telephone module.
Inner door with 1 double slot (used for
the INCC-TEL Fire Fighter
Handset) and 4 single slots.
Inner door with 6 single slots.
INCC backbox (black) with black outer
door.
19” W x 19” H x 4” D
(48 W x 48 H x 10 D cm)
INCC backbox (black) with red outer
door
19” W x 19” H x 4” D
(48 W x 48 H x 10 D cm)
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0542 Rev. J page 4 of 4
www.gamewell-fci.com
Similar pages