LEM DK200-B10 Dc current transducer dk-b5/10 Datasheet

DC Current transducer DK-B5/10
A split core transducer for the electronic measurement DC current,
with galvanic isolation between the primary (High power) and the
secondary circuits (Electronic circuit) with voltage output.
Electrical data
Primary Nominal Current
IPN (A.t)
50,75,100
100,150,200
150,225,300
200,300,400
50,75,100
100,150,200
150,225,300
200,300,400
Vc
RL
Vd
f
Ic
Features
Analogue Output Signal 1)
VOUT (V)
0-5
0-5
0-5
0-5
0-10
0-10
0-10
0-10
Supply voltage
Load resistance (max)
Isolation voltage
Frequency
Current consumption (max)
Type
DK 100 B5
DK 200 B5
DK 300 B5
DK 400 B5
DK 100 B10
DK 200 B10
DK 300 B10
DK 400 B10
22-26
250
3000
DC
100
V AC/ DC
kΩ
V AC
mA
Accuracy - Dynamic performance data
X
εL
tr
Accuracy @ IPN, TA=25°C
Linearity
Response time @ 90% of I PN
±1
± 0.75
< 300
%
%
mS
General data
TA
TS
m
IPN = 50..400A
Ambient operating temperature (0-95% RH)
Ambient storage temperature
Mass
- 20 .. + 50
- 20 .. + 85
120
°C
°C
g
• DC Measurement
• Split core box
• Voltage output
• Jumper selectable ranges
• Panel mounting
• Extended measuring range
Advantages
• Large aperture
• High isolation between primary and
secondary circuits
• Easy to mount
• No insertion losses
Applications
• Battery Banks
- Monitors load current.
- Monitors charging current.
- Verifies operation.
• Transportation
Measures traction power or auxiliary
loads.
• Electric Heating Elements
Faster response than temperature
sensors.
Options on request
• DIN mounting
Note :
1)
For 0-3 V output model, no saturation output up to 3.5 V
for 0-5 V output model, no saturation output up to 5.75 V
and for 0-10 V output model, no saturation output up to 11.5 V
LEM Components
040405/5
w w w .lem.com
Dimensions
DK-B5/10
(unit : mm, 1mm = 0.0394 inch)
3.2
57.2
13
21.7
61
13
30
21.7
89.7
61
4.5
77.3
Mechanical characteristics
• General tolerance
• Primary aperture
• Panel mounting
Distance between holes
Output
output in %
± 1 mm
21.7 mm sq.
2 holes ∅ 4.5mm
77.3 mm
100
- IP
+ IP
Connections
22-38VAC/DC
VAC
22-26
• 2 x UNC8 Cylindric Head
Range Jumper
1(-) 2(+) 3(-) 4(+)
Output
Power
- Dead front captive screw terminals
- 12-22AWG solid or stranded
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.