Gamewell-FCI AOM-2SF Addressable output supervised control module Datasheet

Velociti® Series
AOM-2SF
Description
Addressable Output Relay
Supervised Control Module
The Gamewell-FCI Velociti® Series addressable output
supervised control module (AOM-2SF) allows an
Gamewell-FCI analog addressable fire alarm control to
switch an external power supply, such as a DC supply or
audio amplifier (up to 80 VRMS) to notification appliances.
The AOM-2SF notification appliance circuit can be wired
either Class A (Style Z) or Class B (Style Y). It also supervises the wiring to the connected loads and reports their
status to the panel as NORMAL, OPEN or SHORT CIRCUIT. The module contains a panel controlled LED.
AOM-2SF
•
The Velociti® Series use a communication protocol that
substantially increases the speed of communication
between the sensors and certain Gamewell-FCI analog
addressable fire alarm controls. These devices operate in
a grouped fashion. If one of the devices in the group has a
status change, the panel’s microprocessor stops the group
poll and concentrates on the single device. The net effect
is response speed up to five times greater than earlier
designs.
The module is UL Listed as suitable for releasing device
service and FM Approved for deluge and preaction service. Refer to the Gamewell-FCI Compatibility Addendum,
P/N 9000-0427, for a list of approved, compatible solenoids. The AOM-2SF module is designed for installation in
the signaling line circuit of any Gamewell-FCI analog
addressable control panel. The signaling line circuits of
Gamewell-FCI analog addressable control panels are
designed to accommodate up to 159 modules per circuit.
The AOM-2SF is designed to mount in a 4” (10.16 cm)
square junction box 2 1/8” (5.5 cm) deep.
Relay Contact Ratings
Current
Rating
3A
2A
0.9A
0.5A
0.5A
1A
0.5A
0.7A
Maximum
Voltage
30 VDC
30 VDC
110 VDC
125 VAC
30 VDC
30 VDC
125 VAC
75 VAC
Load
Application
Description
Resistive
Non-Coded
Resistive
Coded
Resistive
Non-Coded
Resistive
Non-Coded
Inductive (L/R=5ms) Coded
Inductive (L/R=2ms) Coded
Inductive (PF=.35) Non-Coded
Inductive
Non-Coded
Features
• Compact Size allows easy installation
• Class A, Style Z, or Class B, Style Y notification
appliance circuit
• Will accommodate audio amplifiers up to 80 VRMS
• Listed as suitable for releasing device service
• Bicolor LEDS flash green whenever the module is
addressed, and lights steady red on alarm*
*Note: Only the red LED is operative in panels that do not operate in
Velociti® mode.
Specifications
Supervisory Current: .000375 amps.
Alarm Current:
.0065 amps.
Operating
Temperature:
32° to 120° F (0° to 49° C)
Relative Humidity:
10 to 93% relative humidity
(non-condensing)
Dimensions:
4 1/2” H x 4” W x 1 1/4” D
(11.4 H x 10.2 W x 3.2 D cm)
Ordering Information
Model
AOM-2SF
Description
Addressable output supervised
control module
An ISO 9001-2000 Company
SIGNALING
Velociti® is a registered trademark of Honeywell International Inc.
UL® is a registered trademark of Underwriters Laboratories Inc.
FM
S1949
MEA
Approved
3023594 227-03-E Vol.IV 07300-0694:178
APPROVED
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0627 Rev. C2 page 1 of 1
©2008 Honeywell International Inc. All rights reserved.
Similar pages