Power-One LK4501-7R 150 watt ac-dc converter Datasheet

K Series with PFC
150 Watt AC-DC Converters
Input voltage range from 85...255 V AC
1or 2 isolated outputs up to 48 V DC
4 kV AC I/O electric strength test voltage
LGA
• Rugged electrical and mechanical design
• Integrated power factor correction
• Operating ambient temperature range
–40...71°C with convection cooling
Selection chart
Output 1
Uo nom
Io nom
[V DC]
5.1
12
15
24
24
30
48
12
15
24
[A]
25
12
10
6
6
5
3
6
5
3
Output 2
Uo nom
[V DC]
12
15
24
www.power-one.com
Edition 4/04.2001
Input voltage
Io nom
Ui
[A]
-
[V AC]
85...255
85...255
85...255
85...255
85...255
85...255
85...255
85...255
85...255
85...255
6
5
3
Efficiency
hmin
[%]
78
85
85
86
83
83
84
83
83
84
Type
LK 4003-6R
LK 4301-7R
LK 4501-7R
LK 4601-7R
LK 5320-7R
LK 5540-7R
LK 5660-7R
LK 5320-7R
LK 5540-7R
LK 5660-7R
Options
-9, E, D, V, P, T, B1
-9, E, D, P, T, B1
-9, E, D, P, T, B1
-9, E, D, P, T, B1
-9, E, D, P, T, B1
-9, E, D, P, T, B1
-9, E, D, P, T, B1
-9, E, D, P, T, B1
-9, E, D, P, T, B1
-9, E, D, P, T, B1
1
Cassette Style
K Series with PFC
Input
Input voltage AC
Input frequency
Power factor
Inrush current limitation
wide input range
per IEC/EN 61000-3-2
by thermistor
85...255 V AC
50/60 Hz
>95%
Output
Efficiency
Output voltage setting accuracy
Output voltage switching noise
Line regulation
Load regulation
Minimum load
Current limitation
Operation in parallel
Hold-up time
Ui nom, Io nom
Ui nom, Io nom
IEC/EN 61204, total
Ui min...Ui max, Io nom
Ui nom, 0.1...Io nom, symmetrical output load
not required
rectangular U/I characteristic
by current limitation
Ui nom, Io nom
up to 86%
±0.6% Uo nom
typ. 100 mVpp
typ. ±0.1%
typ. 0.4%
0A
typ. 110...100% Io nom
20 ms
Control and protection
Input fuse
Input undervoltage lockout
Input overvoltage lockout
Input transient protection
Output
Output overvoltage
Overtemperature
Output voltage adjustment
Inhibit
Status indication
not user accessible
varistor
no-load, overload and short circuit proof
suppressor diode in each output
switch-off with auto restart
4 AT
typ. 80% Ui min
typ. 115% Ui max
typ. 130% Uo nom
TC typ. 100°C
0...110% Uo nom
TTL input, output(s) disabled if open circuit
LEDs: OK, inhibit, overload
Safety
Approvals
Class of equipment
Protection degree
Electric strength test voltage
EN 60950, UL 1950, CSA 22.2 No. 950
I/case
I/O
O/case
O/O
class I
IP 30
2 kV AC
4 kV AC
1 kV AC
0.1 kV AC
IEC/EN 61000-4-2, level 4 (8/15 kV)
IEC/EN 61000-4-3, level 3 (10 V/m)
IEC/EN 61000-4-4, level 4 (2/4 kV)
IEC/EN 61000-4-5, level 3 (2 kV)
IEC/EN 61000-4-6, level 3 (10 V)
CISPR 22/EN 55022
criterion A
criterion A
criterion A
criterion A
criterion A
class B
EMC
Electrostatic discharge
Electromagnetic field
Electr. fast transients/bursts
Surge
Conducted disturbances
Electromagnetic emissions
www.power-one.com
Edition 4/04.2001
2
K Series with PFC
150 Watt AC-DC Converters
Environmental
Operating ambient temperature
Operating case temperature TC
Storage temperature
Damp heat
Vibration, sinusoidal
Shock
Bump
Random vibration
MTBF
Ui nom, Io nom, convection cooled
Ui nom, Io nom
–25...71°C
–25...95°C
–40...100°C
56 days
0.35 mm/5 gn
100 gn
40 gn
4.9 gn rms
514'000 h
non operational
IEC/EN 60068-2-3, 93%, 40°C
IEC/EN 60068-2-6, 10...60/60...2000 Hz
IEC/EN 60068-2-27, 6 ms
IEC/EN 60068-2-29, 6 ms
IEC/EN 60068-2-64, 20...500 Hz
MIL-HDBK-217F, GB, 40°C
Options
Extended temperature range
–40...71°C, ambient, operating
Electronic inrush current limitation
Output voltage adjustment
40...100 % Uo nom, excludes feature R and vice versa
Input and/or output undervoltage monitoring, excludes option V
Input and/or output undervoltage monitoring (VME), excludes option D
Current sharing
Cooling plate
-9
E
P
D0…D9
V0, V2, V3
T
B1
Pin allocation
Pin
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
LK 4003
Vo1+
Output 1
Vo1–
Output 1
S+
S–
R
i
D
V
T
N
Sense
Sense
Control of Uo1
Inhibit
Save data
ACFAIL
Current sharing
Protective earth
Input
P
Input
LK 4301, LK 4501, LK 4601
Vo1+
Output 1
Vo1+
Vo1–
Output 1
Vo1–
S+
Sense
S–
Sense
R
Control of Uo1
i
Inhibit
D
Save data
LK 5000
Vo2+
Output 2
Vo2+
Vo2–
Output 2
Vo2–
Vo1+
Output 1
Vo1–
Output 1
R
Control of Uo1
i
Inhibit
D
Save data
T
T
N
N
P
P
Current sharing
Protective earth
Input
Input
N
N
P
P
Current sharing
Protective earth
Input or Neutral
Input or Phase
10001
S10010
Connector type H15
30 26 22 18 14 10 6
32 28 24 20 16 12 8
4
30/32
4/6
Type H15 S2
www.power-one.com
Edition 4/04.2001
3
Cassette Style
K Series with PFC
Mechanical data
Tolerances ±0.3 mm (0.012") unless otherwise indicated.
159 (6.25")
7 TE
111 (3U) (4.37")
6.5 (0.26")
89 (3.50")
4.5 (0.18")
Measuring point of
case temperature TC
50 (1.97")
European
Projection
171.93 (6.77") (DIN 41494)
9 TE
Test jacks
Option P (Uo)
Option D (Uto)
Option D (Uti)
LED i
LED OK
LED IoL
80 (3.15")
168.5 (6.63")
S09002
Accessories
Front panels 19" (Schroff/Intermas)
Mating H15/H15S4 connectors with screw, solder, fast-on or press-fit terminals
Connector retention facilities and code key system for connector coding
Chassis or wall mounting plates for frontal access
Universal mounting brackets for chassis or DIN-rail mounting
www.power-one.com
Edition 4/04.2001
4
Similar pages