EPCOS B84144A0120R000 4-line emc filter Datasheet

4-line EMC filters
Series/Type:
B84144*
The following products presented in this data sheet are being withdrawn.
Ordering Code
Substitute Product
B84144G0250S000 B84144B*S120,
B84144B*S121
B84144G0500S000 B84144B*S120,
B84144B*S121
B84144G1000S000
Date of
Withdrawal
2009-03-13
Deadline Last
Orders
2009-06-30
Last Shipments
2009-09-30
2009-03-13
2009-06-30
2009-09-30
2009-03-13
2009-06-30
2009-09-30
Ordering Code
B84144G1600S000
Substitute Product
Date of
Withdrawal
2009-03-13
Deadline Last
Orders
2009-06-30
Last Shipments
2009-09-30
For further information please contact your nearest EPCOS sales office, which will also support
you in selecting a suitable substitute. The addresses of our worldwide sales network are
presented at www.epcos.com/sales.
4-line filters
B84144A*R, B84144G*S
for converters and power electronics
Power line filters for 3-phase systems
Rated voltage 440/250 V AC, 50/60 Hz
Rated current 16 to 1600 A
Alternative version
■ Series B84144A*R120
and B84144B*S120/S121
offer a low-cost solution.
Construction
■ 4-line filter
■ Metal case
■ Threaded bushes at end faces for
RF-tight installation
Features
Optimized leakage current
Easy to install
Degree of protection up to 180 A: IP 201)
Space-saving design
Design complies with
EN 133200, UL 1283, CSA C22.2 No.8
■ UL approval
■
■
■
■
■
Applications
■
■
■
■
General applications for power electronics
UPS
Wind farms
For machine tools, textile and packaging machines
Terminals
■ Finger-safe terminal blocks for filters up to 180 A
■ Busbars for filters 250 to 1600 A
Marking
Marking on component:
Manufacturer’s logo, ordering code,
rated voltage, rated current,
climatic category, date code
Minimum marking on packaging:
Manufacturer’s logo, ordering code
1) To IEC 60529
Please read Cautions and warnings and
Important notes at the end of this document.
2
01/06
4-line filters
B84144A*R, B84144G*S
for converters and power electronics
Typical circuit diagram
LINE
LOAD
L1
L1’
L2
L2’
L3
L3’
N
N’
PE
PE
SSB1076-F
Technical data and measuring conditions
Rated voltage VR
440/250 V AC, 50/60 Hz
Rated current IR
Referred to 40 °C ambient temperature
Test voltage Vtest
1770 V DC, 2 s (line/line)
2700 V DC, 2 s (lines/case), for 16 … 50 A
2550 V DC, 2 s (lines/case), for 80 …180 A
2121 V DC, 2 s (lines/case), for 250 … 1600 A
Overload capability (thermal)
1.5 · IR for 3 min per hour or
2.5 · IR for 30 s per hour
Leakage current Ileak
At 400 V AC, 50 Hz
Climatic category (IEC 60068-1)
25/100/21 (–25 °C/+100 °C/21 days damp heat test)
Approvals
UL 1283
Please read Cautions and warnings and
Important notes at the end of this document.
3
01/06
4-line filters
B84144A*R, B84144G*S
for converters and power electronics
Characteristics and ordering codes
VR
AC
V
440/250
IR
Ileak
Terminal
cross section
mA
mm2
A
Rtyp
Approx.
weight
kg
mΩ
Ordering code
Approvals
16
4
< 3.5
10
2.2
B84144A0016R000
×
25
10
< 3.5
6
3.7
B84144A0025R000
×
36
10
< 3.5
3.5
3.7
B84144A0036R000
×
50
10
<6
1.3
4.0
B84144A0050R000
×
80
25
<6
0.7
120
50
<6
0.5
9.5
10
B84144A0080R000
×
B84144A0120R000
×
150
50
<6
0.35
10
B84144A0150R000
×
180
95
<6
0.25
13
B84144A0180R000
×
250
Busbars
×
<6
0.095
32
B84144G0250S000
500
<6
0.060
53
B84144G0500S000
–
1000
<6
0.030
140
B84144G1000S000
–
1600
<6
0.020
185
B84144G1600S000
–
× = approval granted
Not for new design. Substitute B84144B*S120/S121.
Please read Cautions and warnings and
Important notes at the end of this document.
4
01/06
4-line filters
B84144A*R, B84144G*S
for converters and power electronics
Dimensional drawings
30±1
55±0.4
12.5±0.4
1±0.1
81 max.
38±1
20.5±0.5
B84144A0016R000 (16 A)
PE M6 x 22.5
163 max.
60±0.4
12.5±1
86 max.
70±0.2
Marking
LINE LOAD
5.5±0.1
113 max.
N L3’ L2’ L1’
100±0.3
N L3 L2 L1
4 x M5 x 6
Terminal blocks 4 mm 2
Tightening torque 0.6 ... 0.8 Nm
141 max.
SSB2221-Q-E
30±1
65±0.4
12.5±0.4
1±0.1
91 max.
46±1
31±0.5
B84144A0025R000, B84144A0036R000, B84144A0050R000 (25 A, 36 A, 50 A)
PE M6 x 25
216 max.
100±0.4
22.5±1
126 max.
80±0.2
LINE
LOAD
6.6±0.2
166 max.
140±0.3
156 max.
Marking
N L3’ L2’ L1’
N L3
L2 L1
4 x M6 x 6
Terminal blocks 10 mm 2
Tightening torque 1.5 ... 1.8 Nm
Please read Cautions and warnings and
Important notes at the end of this document.
5
01/06
SSB1078-W-E
4-line filters
B84144A*R, B84144G*S
for converters and power electronics
55±1
110±0.4
15±0.4
PE M10 x 32
1.0±0.1
18±1
141 max.
83±1
48.5±0.5
B84144A0080R000 (80 A)
300 max.
110±0.4
141 max.
115±0.2
4 x M6 x 6
93.1
L2’
LOAD
171 max.
LINE
N
N
L3
L3’
L2
Marking
155±0.3
L1
L1’
6.6±0.2
Terminal blocks 25 mm 2
Tightening torque 4 ... 4.5 Nm
221 max.
SSB2222-Y-E
54±0.5
B84144A0120R000, B84144A0150R000 (120 A, 150 A)
55±1
1.0±0.1
15±0.4
PE M10 x 32
110±0.4
141 max.
87±1
18±1
348 max.
110±0.4
141 max.
115±0.2
4 x M6 x 6
LOAD
261 max.
Please read Cautions and warnings and
Important notes at the end of this document.
96.8
171 max.
LINE
155±0.3
Marking
N L3’ L2’ L1’
N L3 L2 L1
6.6±0.2
Terminal blocks 50 mm 2
Tightening torque 6 ... 8 Nm
6
01/06
SSB2223-7-E
4-line filters
B84144A*R, B84144G*S
for converters and power electronics
PE M10 x 35
404 max.
301 max.
62±0.8
120±0.4
1.2±0.1
110±0.4
141 max.
LOAD
100
6.6±0.2
Terminal blocks 95 mm 2
Tightening torque 15 ... 20 Nm
165±0.4
Please read Cautions and warnings and
Important notes at the end of this document.
171 max.
LINE
N
L3’
L2
Marking
155±0.3
L2’
L1
L1’
4 x M6 x 6
L3
N
16±0.5
10±0.4
141 max.
105±1
74±0.5
B84144A0180R000 (180 A)
7
01/06
SSB1087-V-E
4-line filters
B84144A*R, B84144G*S
for converters and power electronics
B84144G0250S000 (250 A)
4 x M8 x 7
190±0.5
N
4
120
24
PE M10 x 30
PE M10 x 30
200±1
30
ø12
ø10.5
L3
LINE
LOAD
285
L2’/
N’
260±1
L2/
N
230+2
Marking
24±1
L1’
L1
L3’
15 _ 3
=
370±3
=
460±6
Please read Cautions and warnings and
Important notes at the end of this document.
SSB0996-A
8
01/06
110
171_ 4
N
89.5
4.5±0.5
N
L2 L3
105±0.5
L1
48
350+3
34
4 x M8 x 7
4-line filters
B84144A*R, B84144G*S
for converters and power electronics
B84144G0500S000 (500 A)
4 x M8 x 7
210±0.5
150±0.5
N
N
L2
L1
N
6
PE M10 x 30
60
26
PE M10 x 30
L3
150
280±1
30
ø12
L3
L2’/
N’
LOAD
LINE
305
L2/
N
250
L1’
Marking
280±1
L1
30+3
ø11
L3’
15 +1
=
510±3
=
590±3
Please read Cautions and warnings and
Important notes at the end of this document.
SSB0997-I
9
01/06
134.5
198 _ 4
6±0.5
500
56.5
101.5
4 x M8 x 7
4-line filters
B84144A*R, B84144G*S
for converters and power electronics
B84144G1000S000 (1000 A)
4 x M8 x 7
360±0.8
11±0.5
650+4
240±0.8
L3
N
N
PE M12 x 30
65
38
PE M12 x 30
28
8
N
L2
L1
78
163
211
290 _ 3
4 x M8 x 7
262
320±1
40
ø12
L1
L1’
Marking
L2/
N
LINE
50+10
400+3
440±1
465
ø14
L2’/
N’
LOAD
L3
L3’
40
=
660±3
840±3
Please read Cautions and warnings and
Important notes at the end of this document.
20+1
=
SSB0998-R
10
01/06
4-line filters
B84144A*R, B84144G*S
for converters and power electronics
B84144G1600S000 (1600 A)
4 x M8 x 7
360±0.8
11±0.5
680+4
240±0.8
L3
N
N
PE M12 x 30
65
38
PE M12 x 30
28
8
N
L2
L1
78
163
211
290 _ 3
4 x M8 x 7
262
340±1
40
ø12
L1
L1’
Marking
L2/
N
LINE
50+10
400+3
440±1
465
ø14
L2’/
N’
LOAD
L3
L3’
40
=
690±3
870±3
Please read Cautions and warnings and
Important notes at the end of this document.
20 +1
=
SSB0999-Z
11
01/06
4-line filters
B84144A*R, B84144G*S
for converters and power electronics
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Filters for 16 … 36 A
100
α
dB
Filters for 50 A
SSB1677-Q
α
80
dB
60
40
40
20
20
10 5
10 6
10 7
100
dB
0
10 4
Hz 10 8
f
Filters for 80 A
SSB1090-F
10 6
10 7
Hz 10 8
f
80
80
70
60
60
50
50
40
40
30
30
20
20
10
10
10 7
0
10 4
Hz 10 8
f
Please read Cautions and warnings and
Important notes at the end of this document.
12
B84144A0120R000
B84144A0150R000
dB
70
10 6
SSB1091-N
100
α
10 5
10 5
Filters for 120 and 150 A
B84144A0080R000
0
10 4
SSB1678-Y
B84144A0050R000
80
60
0
10 4
α
100
B84144A0016 ... A0036R000
01/06
10 5
10 6
10 7
Hz 10 8
f
4-line filters
B84144A*R, B84144G*S
for converters and power electronics
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Filters for 180 A
100
α
dB
Filters for 250 to 1600 A
SSB1092-W
SSB1000-K
100
B84144A0180R000
B84144G*S000
dB
α
80
80
70
60
60
50
40
40
30
20
20
10
0
10 4
10 5
10 6
10 7
0 4
10
Hz 10 8
f
Please read Cautions and warnings and
Important notes at the end of this document.
13
01/06
10 5
10 6
10 7
Hz 10 8
f
EMC filters
Cautions and warnings
Important information
Please read all safety and warning notes carefully before installing the EMC filter and putting it into
operation (see
). The same applies to the warning signs on the filter. Please ensure that the signs
are not removed nor their legibility impaired by external influences.
Death, serious bodily injury and substantial material damage to equipment may occur if the appropriate safety measures are not carried out or the warnings in the text are not observed.
Using according to the terms
The EMC filters may be used only for their intended application within the specified values in lowvoltage networks in compliance with the instructions given in the data sheets and the data book.
The conditions at the place of application must comply with all specifications for the filter used.
Warnings
■ It shall be ensured that only qualified persons (electricity specialists) are engaged on work such
■
■
■
■
as planning, assembly, installation, operation, repair and maintenance. They must be provided
with the corresponding documentation.
Danger of electric shock. EMC filters contain components that store an electric charge. Dangerous voltages can continue to exist at the filter terminals for longer than five minutes even after
the power has been switched off.
The protective earth connections shall be the first to be made when the EMC filter is installed and
the last to be disconnected. Depending on the magnitude of the leakage currents, the particular
specifications for making the protective-earth connection must be observed.
Impermissible overloading of the EMC filter, such as impermissible voltages at higher frequencies that may cause resonances etc. can lead to destruction of the filter housing.
EMC filters must be prot ected in the application against impermissible excee ding of the rated
currents by suitable overcurrent protective.
14
01/06
EMC filters
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas o f a pplication. T hese statements are bas ed on o ur know ledge of typical
requirements that are often placed on our products in the areas of application concerned. We
nevertheless expres sly point out that su ch st atements can not b e reg arded as b inding
statements about the suitability of our products for a particular customer application. As
a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them
than t he customers t hemselves. For t hese reasons , it is always ult imately incum bent on t he
customer to check and decide whether an EPCOS product with the properties described in the
product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of passive electronic components
or failure before the end of their usual service life cannot be completely ruled out in the
current sta te o f the art, even if th ey are o perated as specified. I n customer appli cations
requiring a very high level of operational safety and especially in customer applications in which
the malfunction or failure of a passive electronic component could endanger human life or health
(e.g. in accident prevention or life-saving systems), it must therefore be ensured by means of
suitable design of t he c ustomer a pplication or ot her ac tion t aken by t he cu stomer (e. g.
installation of protective circuitry or redundancy) that no injury or damage is sustained by third
parties in the event of malfunction or failure of a passive electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order t o sat isfy c ertain technical requirem ents, some of t he products describ ed in t his
publication may co ntain substances subject to restrictions in certain jurisdictions (e.g.
because they are classed as “hazardous”). Useful information on this will be found in our
Material Data Sheets on the I nternet (www. epcos.com/material). S hould you hav e any more
detailed questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may ch ange from time to time. The same is t rue of the corresponding product
specifications. Pleas e chec k t herefore to what ext ent product descriptions and specifications
contained in this publication are still applicable before or when you place an order.
We a lso reserve the ri ght t o discontinue p roduction a nd d elivery of p roducts.
Consequently, we cannot guarantee that all pr oducts named in this publication will always be
available.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current version
of the “General Terms of Delivery for Products and Services in the Electrical Industry”
published by the German Electrical and Electronics Industry Association (ZVEI).
7. The t rade nam es EPCOS, EPCOS-Jones, Baoke, C eraDiode, CSSP, ML SC, Phas eCap,
PhaseMod, SIFI, SIKOREL, SilverCap, SIMID, SIOV, SIP5D, SIP5K, UltraCap, WindCap are
trademarks registered or pending in Europe and in other countries. Further information will be
found on the Internet at www.epcos.com/trademarks.
15
01/06
Similar pages