Willow DI87-000-A024-C2 Interface relay Datasheet

DI8 series
interface relays
• miniature DIN rail power relay
• up to 16A /230V AC rating
• industry standard style
• cost effective
• RoHS Compliant
Contacts
Contact number & arrangement
SPDT ( 1 C/O), DPDT (2 C/O)
Contact material
AgNi 90/10
Max. switching voltage
AC/DC 440VAC / 125VDC
Min. switching current / voltage
Rated load
5mA / 5VDC
AC1
SPDT: 10A, 250VAC (Sensitive Coil) / 12A, 250VAC / 16A, 250VAC : DPDT: 8A, 250VAC
DC1
SPDT: 10A, 30VDC (Sensitive Coil) / 12A, 30VDC / 16A, 24VDC : DPDT: 8A, 250VAC
Max. inrush current
30A
Initial resistance
100mΩ, max. at 0.1A/6VDC
Coil
Rated voltage
DC 12, 24V
AC 24, 110, 230V
Must release voltage
DC ≥ 0.1Un
AC ≥ 0.15Un
Operating range of supply voltage
Rated power consumption
See coil tables 1 and 2
DC 250mW (10A, Sensitive Coil) / 400mW (standard)
AC 0.75VA
Insulation
Insulation resistance
≤ 1000MΩ at 500VDC, 50%RH
Dielectric strength
coil to contact 5000Vrms, 1min
contact to contact 1000Vrms, 1min
General Data
Operating time (typical)
mS ≤ 7ms
Release time (typical)
mS ≤ 3ms
Electrical Life
ops ≥ 0.7 x 105 (16A), ≥ 1.0 x 105 (10A, 12A)
Mechanical life
ops ≥ 3 x 107
Dimensions
Weight
L x W x H 75.8 x 15.7 x 67 mm (depends on socket and clip choice)
approx 62g with module
Ambient temperature
storage -40 to 85°C
operating -40 to 85°C (DC coil) / -40 to 70°C (AC coil)
Shock resistance
30g
Vibration resistance
10g 10...150Hz
Page 1 of 3
Ref: DI8 070313JHM
www.willow.co.uk Sales Department Tel: +44 1342 717102
Specifications are subject to change without notice. E&OE.
DI8 series
interface relays
Coil Data (standard coil)
Table 1
Coil Resistance (Ω)
±10%
Operate
voltage max.
12VDC
360
24VDC
1440
Coil Voltage Code
Nominal Voltage
D012
D024
Must operate
voltage max.
Must release
voltage min.
18.0VDC
8.4VDC
1.2VDC
36.0VDC
16.8VDC
2.4VDC
A024
24VAC
400
28.8VAC
19.2VAC
3.6VAC
A110
110VAC
8900
132.0VAC
88.0VAC
16.5VAC
A230
230VAC
38500
276.0VAC
184.0VAC
34.5VAC
Coil Data (12VDC sensitive coil)
Table 2
Coil Voltage Code
Nominal Voltage
Coil Resistance (Ω)
±10%
Operate
voltage max.
Must operate
voltage max.
Must release
voltage min.
S012
12VDC
576
15.6VDC
9.00VDC
1.2VDC
Coil specifications at 20°C. AC coils are suitable for 50HZ or 60Hz operation
Operating relays below or above the nominal voltage may prove detrimental to performance.
Ordering codes
Table 2
Relay & Socket Code
D
I
8
Module Code
7
-
4
1
Coil Code
G
-
A
0
2
Socket style
4
-
C
3
N
Contact Style
4
-
DPCO 8A
5
-
SPCO 16A
7
-
SPCO 10A & 12A
see Tables 1 & 2
Module type
000
-
No Module fitted
21P
-
Diode A2+
21N
-
Diode A1+
41G
-
LED (Green) 6-24VDC
41R
-
LED (Red) 6-24VDC
61G
-
LED (Green) 6-24VAC/DC
61R
-
LED (Red) 6-24VAC/DC
63G
-
LED (Green) 110 - 230VAC/DC
63R
-
LED (Red) 110-230VAC/DC
Socket type
C2
-
SPDT: D14-1Z-C2 (standard), or DPDT: D14F-2Z-C2 (standard)
C3N
-
SPDT: D14F-1Z-C3-N (standard), or DPDT: D14F-2Z-C3-N (standard)
C4
-
SPDT: D14F-1Z-C4 (special order*), or DPDT: D14F-2Z-C4 (special order*)
C5
-
SPDT: D14F-1Z-C5 (special order*), or DPDT: D14F-2Z-C5 (special order*)
* Minimum Order Quantities (MOQ’s) may apply.
Page 2 of 3
Ref: DI8 070313JHM
www.willow.co.uk
Sales Department Tel: +44 1342 717102
Specifications are subject to change without notice. E&OE.
DI8 series
interface relays
Interface Relay construction
Table 3
Relay type
Socket type
Ejector Clip
(refer to Ordering
Codes for full number)
Module
DI84
DM84 series
+
D14F-2Z-???
+
+
DM???-BK
DI85
DM85 series
+
D14F-2Z-???*
+
+
DM???-BK
DI87
DM87N
+
D14F-1Z-???
+
+
DM???-BK
DI87
DX87N (Sensitive coil)
+
D14F-1Z-???
+
+
DM???-BK
JH-15PS
* For loads above 12A , terminals must be bridged in pairs, 11 with 21, 12 with 22, 14 with 24 - see Connection diagrams (Fig. 2)
All sockets are supplied with a blank, white, description plate/tab.
??? See Ordering Codes (Table 2, Page 2) for details.
Overall Dimensions
Fig. 1
58 typ.
65 typ.
D14F-1Z-C3-N
D14F-1Z-C2
D14F-2Z-C3-N
D14F-2Z-C2
Dimensions in mm
Connection diagrams
Fig. 2
DI87
DI85
DI84
11 12
21
11
21
11
14
24
14
24
14
A1
A2
A1
A2
A1
22
12
22
12
A2
Notes:
1) For DI85 for loads above 12A, contact terminals must be bridged in pairs, 11 with 21, 12 with 22, 14 with 24.
2) Coil polarity (A1/A2) will depend upon module (if fitted).
Willow Technologies Ltd, Unit 3 Borers Yard, Borers Arms Road, Copthorne, W.Sx, RH10 3LH, England
Page 3 of 3
www.willow.co.uk
Sales Department Tel: +44 1342 717102
Ref: DI8 070313JHM
Specifications are subject to change without notice. E&OE.
Similar pages