XP Power ACM18 Ac-dc power supply Datasheet

ACM18 Series
AC-DC Power Supplies
18 Watt
xxx Series
• Energy Efficiency Level VI
• European CoC Tier 2
• Medical and ITE Approvals
• Interchangeable Mains Connectors
• Optional White Versions
• Output Voltages from 5 V to 24 V
• Class II Construction
• 3 Years Warranty
The ACM18 series of wall plug adaptors comply with the latest energy efficiency level VI standards
with high active mode efficiency and extremely low no load power consumption. Available with a
standard jack plug connector these adaptors suit a wide variety of cost sensitive industrial and
medical applications while maintaining industry leading performance.
Dimensions:
ACM (body only):
3.46 x 1.18 x 1.95” (88.0 x 30.0 x 49.5 mm)
Models & Ratings
Output Power
18 W
Output Voltage
Output Current
Total Regulation(3)
Efficiency(4)
Model Number(1,2,5)
5.0 V
9.0 V
2500 mA
2000 mA
5%
5%
82.5%
86.7%
ACM18US05
ACM18US09
12.0 V
1500 mA
5%
87.5%
ACM18US12
15.0 V
1250 mA
5%
87.5%
ACM18US15
18.0 V
1000 mA
5%
87.5%
ACM18US18
24.0 V
750 mA
5%
87.5%
ACM18US24
Notes
1. Model number is for body only. AC input plugs must be ordered separately, see
AC input plug section.
2. Other output voltages available, contact sales for details.
3. Total regulation includes initial set accuracy, line and load regulation.
4. Typical average value measured at 115 VAC.
5. For white case version add suffix ‘-W’ e.g. ACM18US12-W. MOQ applies,
contact sales for details.
Input
Characteristic
Input Voltage
Input Frequency
Input Current
Inrush Current
Power Factor
No Load Input Power
Input Protection
Minimum
90
47
Typical
Maximum
264
63
0.23
70
Units
VAC
Hz
A
A
75
mW
Maximum
24
5
Units
V
A
s
ms
ms
%
4
% deviation
Ripple & Noise
150
mV pk-pk
Short Circuit Protection
Temperature Coefficient
0.05
%/ ˚C
Notes & Conditions
100 VAC
240 VAC, cold start at 25 °C
EN61000-3-2, class A
Internal fuse in both line and neutral
Output
Characteristic
Output Voltage
Minimum Load
Start Up Delay
Start Up Rise Time
Hold Up Time
Total Regulation
Transient Response
1
Minimum
5
0
Typical
4
30
10
Notes & Conditions
See Models and Ratings table
No minimum load required
Full load and 100 VAC
See Models and Ratings table
Recovery within <1% within 500 µs for a 60% step load
change at 0.15 A/µs
Measured with 20 MHz bandwidth and 10 µF electrolytic in
parallel with 0.1 µF ceramic capacitor
Continuous, trip and restart (hiccup mode) with auto recovery
www.xppower.com
ACM18 Series
AC-DC Power Supplies
General
Characteristic
Minimum
Typical
Efficiency
Maximum
Notes & Conditions
Units
Typical average of efficiencies measured at 25%, 50%, 75%
and 100% load and 115 VAC input
%
87
Energy Efficiency
Level VI
4000
Isolation
Leakage Current
30
Switching Frequency
24
Mean Time Between Failure
250
Input to Output
kHz
kHrs
At 264 VAC, 60 Hz, from output to ground
lb (g)
Body only
µA
100
70
0.18 (80)
Weight
VAC
Variable
MIL-HDBK-217F at 25 °C GB
Environmental
Characteristic
Minimum
Maximum
Units
0
+60
°C
Storage Temperature
-20
+85
°C
Operating Humidity
5
90
%
5000
m
Operating Temperature
Typical
Operating Altitude
Notes & Conditions
Derate from 100% load at 40 °C to 50% load at 60 °C
RH, non-condensing
Cooling
Natural convection
Shock
1 m drop onto concrete on each of 6 axes, non operating
10
Vibration
Hz
300
2 g, 0.3 decades/min, 15 mins for each of 3 axes
EMC: Emissions
Phenomenon
Standard
Test Level
Conducted
EN55022
Level B
Radiated
EN55022
Level B
Harmonic Current
EN61000-3-2
Class A
Voltage Flicker
EN61000-3-3
Notes & Conditions
EMC: Immunity
Phenomenon
Medical Device EMC
Low Voltage PSU EMC
Standard
Test Level
Criteria
IEC60601-1-2
Ed.4.0 : 2014
as below
as below
EN61204-3
High severity level
ESD Immunity
EN61000-4-2
±8 kV contact, ±15 kV air
A
Radiated Immunity
EN61000-4-3
10 V/m
A
A
EFT/Burst
EN61000-4-4
Level 3
Surge
EN61000-4-5
Level 3
A
Conducted Immunity
EN61000-4-6
6V
A
Magnetic Fields
EN61000-4-8
30 A/m
Dip: 100% 10 ms
Dip: 70% 500 ms
A
A
B
Int: 100% 5000 ms
B
Dip: 30% 25 AC Cycles
A
EN61000-4-11
Dips and Interruptions
EN60601-1-2
Int: 100% 0.5 AC Cycle
A
Int: 100% 1 AC Cycle
A
Int.: >95% 5000 ms
B
Notes & Conditions
High Line/Low Line
At 8 angles
Safety Approvals
Safety Agency
UL
Safety Standard
Notes & Conditions
UL60950-1
TUV
EN60950-1
CB
IEC60950-1
CE
LVD
UL
ANSI/AAMI ES 60601-1
CSA
CSA C22.2 No. 60601
TUV
EN60601-1
CB
IEC60601-1
Information Technology
Medical
www.xppower.com
2
ACM18 Series
AC-DC Power Supplies
Mechanical Details
ACM18USXX
1.94 (49.5)
±0.01 (±0.5)
3.46 (88.0) ±0.01 (±0.5)
70.8 (1800.0) ±10%
0.43 (11.0) ±0.01 (±0.5)
1.18 (30.0)
±0.01 (±0.5)
ø0.09 (ø2.5)
ø0.21 (ø5.5)
AC Input Plugs
Black UK Plug: ACM PLUG UK
White UK Plug: ACM PLUG UK W
Black USA Plug: ACM PLUG US
White USA Plug: ACM PLUG US W
1.73 (44.1)
±0.02 (±0.6)
1.25 (32.0)
±0.11 (±0.5)
1
R3
0.15 (3.97)
±0.1 (±0.15)
1.16 (29.5)
±0.11 (±0.5)
1.94 (49.4)
±0.02 (±0.6)
0.05 (1.5) ±0.003 (±0.1)
R3
0.87 (22.2)
±0.1 (±0.15)
0.62 (16.0) ±0.01 (±0.5)
0.24 (6.3)
±0.003 (±0.1)
0.35 (9.0) ±0.11 (±0.5)
0.27 (7.0)
±0.007 (±0.2)
0.5 (12.7)
±0.007 (±0.2)
0.89 (22.7)
±0.01 (±0.5)
0.69 (17.7)
±0.01 (±0.5)
0.03 (4.0)
±0.003 (±0.1)
1.26 (22.25)
±0.007 (±0.2)
0.31 (7.9)
±0.003 (±0.1)
0
1
3
www.xppower.com
0.66 (17.0)
±0.11 (±0.5)
ACM18 Series
DC-DC Converter
AC Input Plugs
Black Australian Plug: ACM PLUG AU
White Australian Plug: ACM PLUG AU W
Black European Plug: ACM PLUG EU
White European Plug: ACM PLUG EU W
0.35 (9.0)
±0.01 (±0.3)
R 0.8 (20.5)
1.16 (29.5)
±0.02 (±0.6)
1.16 (29.5)
±0.02 (±0.6)
1
0.06 (1.6)
±0.1 (±0.003)
1.25 (32.0)
±0.02 (±0.6)
1.26 (32.1) ±0.02 (±0.6)
0.24 (6.3)
±0.1 (±0.003)
0.7 (17.8)
±0.02 (±0.6)
0
0.34 (8.8)
±0.1 (±0.003)
1.40 (35.6)
±0.01 (±0.6)
0.71 (18.2)
±0.01 (±0.5)
0.35 (9.0)
±0.01 (±0.5)
1.16 (29.5)
±0.01 (±0.6)
0.6 (17.0)
0.69 (17.6)
±0.007 (±0.2)
0.55 (14.1)
±0.01 (±0.5)
0.74 (19.0)
±0.01 (±0.5)
1.61 (41.0) ±0.02 (±0.6)
Black China Plug: ACM PLUG CN
White China Plug: ACM PLUG CN W
1.16 (29.5) ±0.01 (±0.5)
0.35 (9.0)
±0.01 (±0.5)
1.25 (32.0)
±0.01 (±0.5)
0.62 (16.0)
±0.01 (±0.5)
0.24 (6.3) ±0.003 (±0.1)
0.05 (1.5)
±0.003 (±0.1)
0.5 (12.7)
±0.007 (±0.2)
www.xppower.com
08 Aug 16