Littelfuse AF0500 The af0500 is a microprocessor-based arc-flash relay that limits arc-fault damage by detecting the light from an arc flash and rapidly tripping the feeder breaker Datasheet

Protection Relays and Controls
Arc-Flash Monitoring
AF0500 SERIES
Arc-Flash Relay
Description
The AF0500 is a microprocessor-based arc-flash relay that
limits arc-fault damage by detecting the light from an arc flash
and rapidly tripping the feeder breaker. The unit is well suited
for switchgear, transformer and power converter applications.
Sensors, inputs, and connections are health monitored
to ensure fail-safe operation. A secondary solid-state trip
circuit provides a redundant trip path. A USB port is used for
configuration and access to event logs.
AF0500 includes an Ethernet interface and supports Modbus®
TCP communication. Zone tripping, upstream breaker tripping
and tie breaker tripping applications can be easily configured.
A number of control inputs allows interconnection of multiple
AF0500 units to form a system.
Features & Benefits
FEATURES
BENEFITS
Optical Sensors
4 arc sensor inputs
Supports both point and fiber sensors
Arc-Flash trip time <1ms
Limits arc-flash damage and risk of injury
2 IGBT high speed trip outputs
Supports applications such as upstream
breaker tripping or tie breaker tripping
The AF0500 accepts both PGA-LS10 point sensors and
PGA-LS20/PGA-LS30 fiber-optical sensors. Thus any
combination of fiber or point sensors is supported.
Universal Power Supply
100-240 Vac, 24-48 Vdc, or 110-250
Vdc supply
Fail-safe system
Continuous monitoring of optical sensors
and inputs ensures protection
LED indication
(on unit and each sensor)
Trip and sensor status indicated both on
relay and sensors
Discrete wire networking
Multiple AF0500 units can be
interconnected to form a system
USB interface
Data logging and configuration software
uses a USB interface with no drivers or
software installation
Data logging
On-board event recorder for system
diagnostics (2048 log lines)
Ethernet interface
Modbus® TCP communication
Ordering Information
ORDERING NUMBER
DESCRIPTION
AF0500-00
Arc-Flash Relay
AF0500-00-CC
Arc-Flash Relay, Conformally Coated
ACCESSORIES
REQUIREMENT
PGA-LS10
Required*
PGA-LS20, PGA-LS30
Required*
PGA-1100
Optional
© 2016 Littelfuse Protection Relays & Controls
Littelfuse.com/ArcFlash
For fast fault location, front-panel and sensor LEDs indicate
sensor health and which sensor detected an arc fault.
Sensor Placement
The AF0500 Arc-Flash Relay and sensors are easily installed
in retrofit projects and new switchgear with little or no
re-configuration. Simple applications work straight out of the
box with no need of PC configuration. More complex systems
with multiple power sources are configured using the relay’s
built-in USB interface software.
Generally, it is recommended to mount 1 or 2 sensors per
cubicle to cover all horizontal and vertical bus bars, breaker
compartments, drawers, and anywhere that there is a
risk for an arc fault. Threading a fiber-optic sensor through
the cabinets and in areas where point-sensor coverage is
uncertain results in complete coverage and an added level
of redundancy. Even if policy is to only work on de-energized
systems, all maintenance areas should be monitored to
prevent potential damage and additional cost.
Arc Flash
Fiber-Optic Sensor
Point Sensors
Rev: 1-C-050516
Based on Manual 0-D-040816
Protection Relays and Controls
Arc-Flash Monitoring
AF0500 SERIES
Incoming
Feeder
Sensor
Upstream Breaker Tripping
In case of failure of the local circuit breaker to open, another
trip command is sent after a short delay to an upstream
breaker to clear the fault.
Sensor
Sensor
Sensor
Sensor
Bus Tie
Sensor
Sensor
Sensor
Zone 2
Sensor
Sensor
Zone 1
Incoming
Feeder
Sensor
Zone Tripping
AF0500 can trip 2 separate zones. Sensors can be assigned
to the zones individually through PC configuration.
Tie Breaker Tripping
In case of an arc in one section of the switchboard, the
AF0500 can trip both the incoming feeder and the tie breaker
simultaneously. Thus the affected part of the switchboard is
isolated from the non-affected part.
Sensor
Applications
Incoming
Feeder
Upstream Breaker
Local Breaker
Accessories
PGA-LS10 Point Sensor
Line-of-sight light sensor detects an arc as small
as 3 kA within a 2-m half-sphere. Includes Sensor
health and trip indication.
PGA-LS20/PGA-LS30 Fiber-Optic Sensor
360° light sensor to run along bus bars. Sensor
health and trip indication.
Sensor
Sensor
Sensor
Sensor
PGA-1100 Diode Logic Unit
This module allows multiple arc-flash relays to
trip a common breaker, for example a tie-breaker.
Specifications
Power Supply
Universal
Low Voltage
Sensor Inputs
Trip Outputs
UL Rating
Supplemental Rating
Make/Carry
Voltage Rating
Current Rating
100 to 240 Vac (+10%, -15%) 50/60 Hz, 20 VA,
110 to 250 Vdc (+10%, -20%) 8 W
24 to 48 Vdc (+10%, -20%), 4 W
4 light sensor inputs for PGA-LS10, PGA-LS20
and PGA-LS30 sensors
2 IGBT switches
120/240 Vac, 1800 VA, 0.75 A maximum continuous,
125/250 Vdc, 138 VA, 0.75 A maximum continuous
Communication
Dimensions
Shipping Weight
Operating Temp.
Approvals
Warranty
Mounting
Ethernet, 2 ports with internal Ethernet switch,
Modbus® TCP
H 130 mm (5.1”); W 200 mm (7.9”); D 54 mm (2.1”)
0.9 kg (2 lb)
–40°C to +70°C (–40°F to 158°F)
UL Listed (UL508), CE, RCM, FCC, CSA
5 years
Surface, DIN (with optional D0050 adapter clips)
30 A for 0.2s
24 to 300 Vac, 24 to 300 Vdc
20 A for 2 s, 10 A for 5 s
© 2016 Littelfuse Protection Relays & Controls
Littelfuse.com/ArcFlash
Rev: 1-C-050516
Based on Manual 0-D-040816