Littelfuse H215004 Axial lead and cartridge fuses - designed to iec standard Datasheet

Axial Lead and Cartridge Fuses
Designed to IEC Standard
5 x 20 mm Time Lag Fuse (Slo-Blo
®
Fuse) 215 Series
®
®
• Designed to International (IEC) Standards for use globally.
• Meets the IEC 60127-2, Sheet 5 specification for Time Lag Fuses.
• Available in Cartridge and Axial Lead Form.
• Available in ratings of .2 to 12 amperes.
• High breaking capacity.
ELECTRICAL CHARACTERISTICS:
150%
Ampere
Rating
.1-6.3
8-12
Opening
Time
60 minutes, Minimum
30 minutes, Minimum
.1-12
30 minutes, Maximum
210%
275%
400%
1000%
.1-.8
1-12
.1-.8
1– 3.15
4– 6.3
.1-.8
1-12
.25 sec., Min.; 80 sec. Max.
.75 sec., Min.; 80 sec. Max.
.05 sec., Min.; 5 sec. Max.
.095 sec., Min.; 5 sec. Max.
.150 sec., Min.; 5 sec. Max.
.005 sec., Min.; .15 sec., Max.
.010 sec., Min.; .15 sec., Max.
1500 amperes @ 250VAC, 0.7-0.8 power factor.
ORDERING INFORMATION:
Ampere
Rating
.200*
.250*
.315*
.400*
.500*
.630*
.800*
1
1.25
1.6
2
2.5
3.15
4
5
6.3
8*
10*
12*
cycles –65°C to +125°C)
Vibration: MIL-STD-202F Method 201A
Humidity: MIL-STD-202F Method 103B, Test Condition A. high relative
humidity (95%) and elevated temperature (40°C) for 240 hours.
Salt Spray: MIL-STD-202F Method 101D, Test Condition B
PHYSICAL SPECIFICATIONS:
Material: Body: Ceramic
INTERRUPTING RATING:
Cartridge
Catalog
Number
215 .200
215 .250
215 .315
215 .400
215 .500
215 .630
215 .800
215 001.
215 1.25
215 01.6
215 002.
215 02.5
215 3.15
215 004.
215 005.
215 06.3
215 008.
215 010.
215 012.
ENVIRONMENTAL SPECIFICATIONS:
Operating temperature: -55˚C to 125˚C
Thermal Shock: MIL-STD-202F Method 107G, Test Condition B: (5
Voltage
Rating
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
Nominal
Resistance
Cold Ohms
1.840
1.240
0.880
0.583
1.168
0.720
0.468
0.111
0.081
0.056
0.041
0.031
0.022
0.019
0.015
0.011
0.009
0.007
0.006
Nominal
Melting I2t
A2 Sec.
0.341
0.545
0.974
1.324
0.424
0.633
0.974
1.022
1.996
3.798
6.768
10.370
20.644
37.684
80.675
129.022
204.001
351.037
515.500
Cap: Nickel Plated Brass
Leads: Tin Plated Copper
Filler: Sand (500mA – 12A)
Terminal Strength: MIL-STD-202F Method 211A,
Test Condition A
Solderability: Reference IEC 60127 Second Edition 2003-01 Annex A
11
Product Marking: Cap 1: current and voltage rating.
Cap 2: Agency approval markings.
Packaging: Available in Bulk (V=5, H=100, M=1000 pcs/pkg) or on
Tape/Reel (MRET1=1000 pcs/reel).
w w w. l i t t e l f u s e . c o m
AXIAL LEAD AND
CARTRIDGE FUSES
% of Ampere
Rating
11
425
Axial Lead and Cartridge Fuses
Designed to IEC Standard
5 x 20 mm Time Lag Fuse (Slo-Blo ) Fuse 215 Series
®
®
®
Agency Approvals
Agency Approvals
Certificate No.
Certificate No.
Certificate No.
Cartridge
NBK250702-E10480
NBK250702-E10480
Leaded
NBK250702-E10480
NBK250702-E10480
2002010207007593
SU05001-2011
SU05001-2012
Pending
Ampere Range
20+0.5
0215 000
5.2+0.1
-0.2
A & C 1A – 5A
E
6.3A – 12A
5.1+0.6
B & D 1A – 5A
F
6.3A -12A
5.1+0.6
1A – 6.3A
1A – 3.15A
4A – 10A
12A
40
0215.200 XE
to
0215.800 XE
22.5 MAX
6.0 MAX
0.65
Recognised File No. E10480
Guide No.
JDYX2
®
50mA – 12A
File No.
Acc. Class No.
029862
LR1422-30
Licence No.
KM41462
200mA – 6.3A
File No.
403906, 0212085,
0147100
200mA – 10A
40
0215001.XE
to
0215012.XE
22.5 MAX
5.8 MAX
0.65*
All dimensions in mm
200mA – 12A
Notes:
* Ratings above 6.3A
have 0.8 mm dia lead
Average Time Current Curves
0.200A
0.250A
0.315A
0.400A
0.500A
0.630A
0.800A
®
0.1
1
CURRENT IN AMPERES
426
w w w. l i t t e l f u s e . c o m
10
100
Similar pages