Delta DRP-24V240W2BN Compact and corrosion resistant aluminium casing Datasheet

TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 240W 2 Phase / DRP-24V240W2BN
Highlights & Features
•
•
•
•
•
•
•
Designed for single phase input 180-305Vac (for L-N) or
2 of 3-Phase system 2 x 180-550Vac (for L-L) or 254-780Vdc
Compact and corrosion resistant aluminium casing
Up to 90.0% efficiency and Power Boost of 120% for 3
seconds
Wide operating temperature range from -30°C to +70°C
Built-in constant current and hiccup during overload
protection
Built-in DC OK Contact
Conformal coating on PCBAs to protect against common
dust and chemical pollutants
Safety Standards
CB Certified for worldwide use
Model Number:
DRP-24V240W2BN
Unit Weight:
0.81 kg (1.79 lb)
Dimensions (L x W x D): 124 x 60 x 117 mm
(4.88 x 2.36 x 4.61 inch)
General Description
The CliQ II DIN rail power supply series with a new model offering two phase 2 x 180-550Vac (for L-L) or single phase 180-305Vac (for
L-N) for 24V/5A output. The DRP-24V240W2BN has safety approvals for single phase and two phase input according to
IEC/EN/UL 60950-1 and UL 508 safety standards. The product features wide AC input voltage for single or two phase range. Such
feature can protect the power supply from damage when user accidentally apply two phase input on the single phase power supply.
Other advantages include reduced external input protection components and improved installation time since there is only two phase
connection. The product performs under wide operating temperature from -30°C to 70°C with 2-Phase of 3-Phase application (for L-L).
Conformal coating is applied on the PCBA to protect against common dust and chemical pollutant to withstand harsh industrial
environments. Other major safety approvals included.
Model Information
CliQ II DIN Rail Power Supply
Model Number
Input Voltage Range
Rated Output Voltage
Rated Output Current
DRP-24V240W2BN
2 x 180-550Vac (2-Phase)
180-305Vac (Single Phase)
254-780Vdc
24Vdc
10.0A
Model Numbering
DR
P–
24V
DIN Rail
Power Supply
Output Voltage Output Power
1
240W
2
B
N
Two Phase
CliQ II Series
N - Metal Case,
without Class I, Div 2 and ATEX
All parameters are specified at 25°C ambient and AC x 2 input unless otherwise indicated.
www.DeltaPSU.com (December 2016, Rev. 01)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 240W 2 Phase / DRP-24V240W2BN
Specifications
Input Ratings / Characteristics
Nominal Input Voltage
2 x 200-500Vac (2-Phase)
200-277Vac (Single Phase)
Input Voltage Range
2 x 180-550Vac (2-Phase)
180-305Vac (Single Phase)
Nominal Input Frequency
50-60Hz
Input Frequency Range
47-63Hz
DC Input Voltage Range*
254-780Vdc
Input Current
< 2.00A @ 2 x 230Vac, < 1.00A @ 2 x 400Vac
Efficiency at 100% Load
> 90.0% @ 2 x 400Vac
Max Power Dissipation
0% load
100% load
< 8.5W @ 2 x 200Vac, < 9.5W @ 2 x 500Vac
< 26.5W @ 2 x 200Vac, < 21.5W @ 2 x 500Vac
Max Inrush Current (Cold Start)
< 50A @ 2 x 200Vac & 2 x 500Vac
Leakage Current
< 3.5mA @ 500Vac
*Safety approval according to IEC/EN/UL 60950-1.
Output Ratings / Characteristics**
Nominal Output Voltage
24Vdc
Factory Set Point Tolerance
24Vdc ± 2%
Output Voltage Adjustment Range
24-28Vdc
Output Current
10.0A (continuously operating at 24V)
12.0A (Power Boost for 3 seconds at 24V, refer to the details in
the Functions section)
Output Power
240W (continuously operating at 24V)
288W (Power Boost for 3 seconds at 24V, refer to the details in
the Functions section)
Line Regulation
< 0.5% typ. (@ 200-550Vac input, 100% load)
Load Regulation
< 1% typ. (@ 200-550Vac input, 0-100% load)
PARD*** (20MHz)
< 150mVpp @ -10°C and above
< 200mVpp @ below -10°C
Rise Time
< 100ms @ nominal input (100% load)
Start-up Time
< 1,000ms @ nominal input (100% load)
Hold-up Time
>18ms @ 2 x 230Vac (100% load)
> 30ms @ 2 x 400Vac (100% load)
Dynamic Response
(Overshoot & Undershoot O/P Voltage)
± 5% @ 0-100% load
Start-up with Capacitive Loads
10,000µF Max
Functional
DC OK Relay Contact
30V / 1A Max
The relay is usually closed when the output is normal
**For power de-rating from 50°C to 70°C, see power de-rating on page 3.
***PARD is measured with an AC coupling mode, 5cm wires, and in parallel with 0.1μF ceramic capacitor & 47μF electrolytic capacitor.
2
All parameters are specified at 25°C ambient and AC x 2 input unless otherwise indicated.
www.DeltaPSU.com (December 2016, Rev. 01)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 240W 2 Phase / DRP-24V240W2BN
Mechanical
Case Cover / Chassis
Aluminium
Dimensions (L x W x D)
124 x 60 x 117 mm (4.88 x 2.36 x 4.61 inch)
Unit Weight
0.81 kg (1.79 lb)
Indicator
Green LED (DC OK)
Cooling System
Terminal
Wire
Convection
Input
3 Pins (Rated 600V/35A)
Output
4 Pins (Rated 300V/28A)
Input
Output
AWG 18-8
AWG 16-12
Mounting Rail
Standard TS35 DIN Rail in accordance with EN 60715
Noise (1 Meter from power supply)
Sound Pressure Level (SPL) < 40dBA
Environment
Surrounding Air Temperature
Power De-rating
Operating
-30°C to +70°C
Storage
-40°C to +85°C
Vertical Mounting
Horizontal Mounting
Input Voltage
> 50°C de-rate power by 2.25% / °C
> 30°C de-rate power by 2% / °C
< 200Vac de-rate power by 0.5% / Vac
Operating Humidity
5 to 95% RH (Non-Condensing)
Operating Altitude
0 to 2,500 Meters (8,200 ft.) for ITE application (@ 50°C)
0 to 2,000 Meters (6,560 ft.) for Industrial application (@ 50°C)
Shock Test
Non-Operating
IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms,
1 times per direction, 2 times in total
Vibration
Non-Operating
IEC 60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak);
60 min per axis for all X, Y, Z direction
Over Voltage Category
III
Pollution Degree
2
According to IEC/EN 62477-1 /
EN 60204-1 (clearance and
creepage distances) and
IEC 62103 (safety part)
Protections
Overvoltage
32V ±10%, SELV Output, Hiccup Mode,
Non-Latching (Auto-Recovery)
Overload / Overcurrent
> 120-180% of rated load current, Constant current, Hiccup
Mode (Auto-Recovery)
Over Temperature
< 80°C Surrounding Air Temperature @ 100% load, NonLatching (Auto-Recovery)
Short Circuit
Hiccup Mode, Non-Latching
(Auto-Recovery when the fault is removed)
Internal Fuse
T3.15A
Degree of Protection
IP20
Protection Against Shock
Class I with PE* connection
*PE: Primary Earth
3
All parameters are specified at 25°C ambient and AC x 2 input unless otherwise indicated.
www.DeltaPSU.com (December 2016, Rev. 01)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 240W 2 Phase / DRP-24V240W2BN
Reliability Data
MTBF
> 500,000 hrs. as per Telcordia SR-332
I/P: 2 x 200Vac & 500Vac, O/P: 100% load, Ta: 25°C
Expected Cap Life Time
10 years (2 x 200Vac & 500Vac, 50% load @ 40°C)
Safety Standards / Directives
Electrical Equipment of Machines
EN 60204-1 (over voltage category III)
Electrical Equipment for Use in Electrical
Power Installations
IEC/EN 62477-1 / IEC 62103
Safety Entry Low Voltage
PELV* (EN 60204-1), SELV (EN 60950-1)
Electrical Safety
Industrial Control Equipment
SIQ Bauart
UL/cUL recognized
CB scheme
UL/cUL listed
CSA
CE
Material and Parts
Galvanic Isolation
EN 60950-1
UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395)
IEC 60950-1
UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355)
CSA C22.2 No. 107.1-01 (File No. 181564)
In conformance with EMC Directive 2014/30/EU (only AC
input) and Low Voltage Directive 2014/35/EU
RoHS Directive 2011/65/EU Compliant (EN 50581)
Input to Output
4.0KVac
Input to Ground
2.0KVac
Output to Ground
1.5KVac
*Output must be earthed in the final unit in order to comply with PELV requirements according to standard EN 60204-1.
4
All parameters are specified at 25°C ambient and AC x 2 input unless otherwise indicated.
www.DeltaPSU.com (December 2016, Rev. 01)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 240W 2 Phase / DRP-24V240W2BN
EMC
Emissions (CE & RE)
CISPR 22, EN 55022, CISPR 11, EN 55011, FCC Title 47:
Class B
Component Power Supply for General Use
EN 61204-3
Immunity
Generic Standards: EN 55024, EN 61000-6-2
1)
Electrostatic Discharge
IEC 61000-4-2
Radiated Field
IEC 61000-4-3
Level 4 Criteria A
Air Discharge: 15kV
Contact Discharge: 8kV
Level 3 Criteria A1)
80MHz-1GHz, 10V/M, 80% modulation (1kHz)
1.4GHz-2GHz, 3V/M, 80% modulation (1KHz)
2GHz-2.7GHz, 1V/M, 80% modulation (1KHz)
Electrical Fast Transient / Burst
IEC 61000-4-4
Level 3 Criteria A1)
2kV
Surge
IEC 61000-4-5
Conducted
IEC 61000-4-6
Level 3 Criteria A
2)
Common Mode : 2kV
Differential Mode3): 1kV
Level 3 Criteria A1)
150kHz-80MHz, 10Vrms
Power Frequency Magnetic Fields
IEC 61000-4-8
1)
1)
Criteria A
30A/Meter
Voltage Dips
IEC 61000-4-11
100% dip; 1 cycle (20ms); Self Recoverable
Low Energy Pulse Test (Ring Wave)
IEC 61000-4-12
Harmonic Current Emission
Level 3 Criteria A1)
2)
Common Mode : 2kV
Differential Mode3): 1kV
IEC/EN 61000-3-2, Class A
Voltage Fluctuation and Flicker
IEC/EN 61000-3-3
1) Criteria A: Normal performance within the specification limits
2) Asymmetrical: Common mode (Line to earth)
3) Symmetrical: Differential mode (Line to line)
5
All parameters are specified at 25°C ambient and AC x 2 input unless otherwise indicated.
www.DeltaPSU.com (December 2016, Rev. 01)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 240W 2 Phase / DRP-24V240W2BN
Block Diagram
Device Description
1)
2)
3)
4)
5)
6
Input terminal block connector
Output terminal block connector
DC Voltage adjustment potentiometer
DC OK LED (Green)
Universal mounting rail system
All parameters are specified at 25°C ambient and AC x 2 input unless otherwise indicated.
www.DeltaPSU.com (December 2016, Rev. 01)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 240W 2 Phase / DRP-24V240W2BN
Dimensions
L x W x D: 124 x 60 x 117 mm (4.88 x 2.36 x 4.61 inch)
Engineering Data
Output Load De-rating VS Surrounding Air Temperature
Note
1.
2.
3.
4.
5.
Fig. 1
De-rating for Vertical Mounting Orientation
> 50°C de-rate power by 2.25% / °C
Power supply components may degrade, or
be damaged, when the power supply is
continuously used outside the shaded region,
refer to the graph shown in Fig. 1.
If the output capacity is not reduced when the
surrounding air temperature >50°C (Vertical)
or >30°C (Horizontal), the device may run
into Over Temperature Protection. When
activated, the output voltage will go into
bouncing mode and will recover when the
surrounding air temperature is lowered or the
load is reduced as far as necessary to keep
the device in working condition.
In order for the device to function in the
manner intended, it is also necessary to keep
a safety distance as recommended in the
safety instructions while the device is in
operation.
Depending
on
the
surrounding
air
temperature and output load delivered by the
power supply, the device can be very hot!
If the device has to be mounted in any other
orientation,
please
contact
[email protected] for more details.
De-rating for Horizontal Mounting Orientation
> 30°C de-rate power by 2% / °C
7
All parameters are specified at 25°C ambient and AC x 2 input unless otherwise indicated.
www.DeltaPSU.com (December 2016, Rev. 01)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 240W 2 Phase / DRP-24V240W2BN
Output Load De-rating VS Input Voltage

No output power de-rating for the input
voltage range from 200Vac to 550Vac
Assembly & Installation
The power supply unit (PSU) can be mounted on 35mm DIN rails in accordance with EN 60715. For Vertical Mounting, the device
should be installed with input terminal block at the bottom. For Horizontal Mounting, the device should be installed with input terminal
block on the left side.
Each device is delivered ready to install.
Mounting
Dismounting
Fig. 2.1 Mounting
Fig. 2.2 Dismounting
Snap on the DIN rail as shown in Fig. 2.1:
1. Tilt the unit upwards and insert it onto the DIN rail.
2. Push downwards until stopped.
3. Press against the bottom front side for locking.
4. Shake the unit slightly to ensure that it is secured.
To uninstall, pull or slide down the latch with screw driver as
shown in Fig. 2.2. Then slide the power supply unit (PSU) in
the opposite direction, release the latch and pull out the power
supply unit (PSU) from the rail.
In accordance to EN 60950 / UL 50950, flexible cables require ferrules.
Use appropriate copper cables designed to sustain operating temperature of:
1. 60°C, 60°C / 75°C for USA
2. At least 75°C for ambient not exceeding 30°C, and 90°C for ambient exceeding 30°C for Canada.
8
All parameters are specified at 25°C ambient and AC x 2 input unless otherwise indicated.
www.DeltaPSU.com (December 2016, Rev. 01)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 240W 2 Phase / DRP-24V240W2BN
Safety Instructions

•
•
•
•
•
•
•
•
•
•
9
Vertical Mounting

Horizontal Mounting
ALWAYS switch mains of input power OFF before connecting and disconnecting the input voltage to the unit. If mains are not
turned OFF, there is risk of explosion / severe damage.
To guarantee sufficient convection cooling, please refer to the following instructions to ensure sufficient clearance
around the device.
Vertical Mounting: 50mm (1.97 inch) above and below the device as well as a lateral distance of 5mm (0.20 inch) to other
units.
Horizontal Mounting: 50mm (1.97 inch) above and below the device as well as a lateral distance of 50mm (1.97 inch) to
other units.
Note that the enclosure of the device can become very hot depending on the surrounding air temperature and load of the power
supply. Risk of burns!
The main power must be turned off before connecting or disconnecting wires to the terminals.
DO NOT insert any objects into the unit.
Hazardous voltages may be present for up to 5 minutes after the input mains voltage is disconnected. Do not touch the unit during
this time.
The power supplies unit should be installed in minimum IP54 rated enclosure.
The power supplies are built in units and must be installed in a cabinet or room (condensation free environment and indoor
location) that is relatively free of conductive contaminants.
CAUTION: Double pole/neutral fusing.
CAUTION: “For use in a controlled environment”.
All parameters are specified at 25°C ambient and AC x 2 input unless otherwise indicated.
www.DeltaPSU.com (December 2016, Rev. 01)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 240W 2 Phase / DRP-24V240W2BN
Functions
■ Graph illustrating the Start-up Time, Rise Time, and Hold-up Time
Start-up Time
The time required for the output voltage to reach 90% of its final steady state set value, after the input voltage is applied.
Rise Time
The time required for the output voltage to change from 10% to 90% of its final steady state set value.
Hold-up Time
Time between the collapse of the AC input voltage, and the output falling to 95% of its steady state set value.
Inrush Current
Dynamic Response
Inrush current is the peak, instantaneous, input current measured
and, occurs when the input voltage is first applied. For AC input
voltages, the maximum peak value of inrush current will occur
during the first half cycle of the applied AC voltage. This peak
value decreases exponentially during subsequent cycles of AC
voltage.
The power supply output voltage will remains within ±5% of its
steady state value, when subjected to a dynamic load from 0 to
100% of its rated current.
10
All parameters are specified at 25°C ambient and AC x 2 input unless otherwise indicated.
www.DeltaPSU.com (December 2016, Rev. 01)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 240W 2 Phase / DRP-24V240W2BN
Power Boost
Power Boost is the reserve power available
constantly that allows reliable startup to support
sudden and short spike of loads with high inrush
current typically during turn on to remove the
need of more expensive higher rated power
supply unit. After the output has reached its
steady state set value, the power supply can
support surge loads with a higher short-term
power demand up to 120% of maximum rated
load (IO Max), for a maximum duration of 3
seconds. The Power Boost is also available to
repeatedly basis with according to the condition of
an average (R.M.S) output power shall not
exceed continuous operating condition or refer to
duty cycle calculation below.
𝐷𝑢𝑡𝑦 𝑐𝑦𝑐𝑙𝑒 (%) =
𝑇𝑃
𝑇𝑜𝑡𝑎𝑙 𝑇𝑖𝑚𝑒
𝐴𝑣𝑒𝑟𝑎𝑔𝑒 𝑂𝑢𝑡𝑝𝑢𝑡 𝑃𝑜𝑤𝑒𝑟 (𝑃𝐴𝑣𝑔 ) =
OR
𝑁𝑜𝑛-𝑃𝑒𝑎𝑘 𝑃𝑜𝑤𝑒𝑟 =

(𝑃𝑜𝑤𝑒𝑟 𝐵𝑜𝑜𝑠𝑡 × 𝑇𝑃 ) + (𝑁𝑜𝑛-𝑃𝑒𝑎𝑘 𝑃𝑜𝑤𝑒𝑟 × 𝑇𝑁 )
𝑇𝑜𝑡𝑎𝑙 𝑇𝑖𝑚𝑒
�𝑃𝐴𝑣𝑔 × 𝑇𝑜𝑡𝑎𝑙 𝑇𝑖𝑚𝑒� − (𝑃𝑜𝑤𝑒𝑟 𝐵𝑜𝑜𝑠𝑡 × 𝑇𝑃 )
𝑇𝑁
An example of Power Boost and Average Output Power
Power Boost
Peak Power
(WP)
Power Boost
Duration (TP)
Duty Cycle
Non-Peak
Power (WN)
Non-Peak Power
Duration (TN)
Total Time
(T)
120%
288
3 sec
10%
235W
27 sec
30 sec
120%
288
3 sec
15%
232W
17 sec
20 sec
It is not recommended to prolong the duration of Power Boost to be longer than the specified duty cycle calculation, this may cause
damage to the PSU.
External Input Protection Device
The unit is protected at the L pin, with an internal fuse that cannot be replaced. The power supply has been tested and approved on
20A (UL) and 16A (IEC) branch circuits without additional protection device. An external protection device is only required if the
supplying branch has an ampacity greater than above. Thus, if an external protective device is necessary, or, utilized, please refer a
minimum value in instruction sheet with B or C characteristic breaker.
11
All parameters are specified at 25°C ambient and AC x 2 input unless otherwise indicated.
www.DeltaPSU.com (December 2016, Rev. 01)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 240W 2 Phase / DRP-24V240W2BN
Overload & Overcurrent Protections (Auto-Recovery)
Overvoltage Protection (Auto-Recovery)
The power supply’s Overcurrent (OCP) Protection will be
activated when output current is > 13A typ. In such occurrence,
the VO will start to droop and once the output voltage is below
18Vdc typ., the power supply will go into “Hiccup mode” (AutoRecovery). The power supply will recover once the fault condition
of the OCP is removed and IO is back within the specifications.
The power supply’s overvoltage circuit will be activated when its
internal feedback circuit fails. The output voltage shall not exceed
its specifications defined on Page 3 under “Protections”.
Over Temperature Protection (Auto-Recovery)
Short Circuit Protection (Auto-Recovery)
The power supply’s output OLP/OCP function also provides
protection against short circuits. When a short circuit is applied,
the output current will operate in “Hiccup mode”, as shown in the
illustration in the OLP/OCP section on this page. The power
supply will return to normal operation after the short circuit is
removed.
12
As described in load de-rating section, the power supply also has
Over Temperature Protection (OTP). In the event of a higher
operating temperature at 100% load, the power supply will run
into OTP when the operating temperature is beyond what is
recommended in the de-rating graph. When activated, the output
voltage will go into bouncing mode until the temperature drops to
its normal operating temperature as recommended in the derating graph.
All parameters are specified at 25°C ambient and AC x 2 input unless otherwise indicated.
www.DeltaPSU.com (December 2016, Rev. 01)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 240W 2 Phase / DRP-24V240W2BN
Operating Mode

Redundant Operation
In order to ensure proper redundant operation for the power
supply unit (PSU), the output voltage difference between the
two units must be kept at 0.45~0.50V for 24V supplies. Follow
simple steps given below to set them up for the redundant
operation:
Step 1.
Measure output voltage of PSU 1 and PSU 2. If PSU 1 is the
master unit, then VO of PSU 1 must be higher than PSU 2. In
order to set the output voltage, individually connect the power
supply to 50% of rated load, and set the PSU 1 and PSU 2
output voltage.
Fig. 3
Redundant Operation Connection Diagram
Step 2.
Connect the power supply units PSU 1 and PSU 2 to Vin 1 &
Vin 2, respectively, of the DRR-20N (or 20A) module shown
on the diagram on the right.
Step 3.
Connect the system load from Vout. Please note that output
voltage Vout from DRR module will be = VO (output voltage of
power supply) – Vdrop* (in DRR module).
*Vdrop will vary from 0.60V to 0.90V (Typical 0.65V) depending on the load current and surrounding air temperature.

Parallel Operation
The power supply units (PSUs) can also be used for parallel
operation in order to increase the output power. The
difference in output voltage between the two units must be
kept to within 25mV of each other. This difference must be
verified with the same output load connected independently
to each unit.
Parameters such as EMI, inrush current, leakage current,
PARD, start up time will be different from those on the
datasheet, when two units are connected in parallel. The user
will need to verify that any differences will still allow the two
power supplies connected in parallel will work properly in their
product/application.
Fig. 4
13
Parallel Operation Connection Diagram
All parameters are specified at 25°C ambient and AC x 2 input unless otherwise indicated.
www.DeltaPSU.com (December 2016, Rev. 01)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 240W 2 Phase / DRP-24V240W2BN
Others
Delta RoHS Compliant
Restriction of the usage of hazardous substances
The European directive 2011/65/EU limits the maximum impurity level of homogeneous materials such as lead,
mercury, cadmium, chrome, polybrominated flame retardants PBB and PBDE for the use in electrical and
electronic equipment. RoHS is the abbreviation for “Restriction of the use of certain hazardous substances in
electrical and electronic equipment”.
This product conforms to this standard.
Conformal Coating
The Protective Coating Technology
Delta Electronics Group has designed the perfect dipping technique which penetrates everywhere including
under device, and prevents leakage. The conformal coating dipping can be applied to PCBAs or circuit board.
The coating preserves the performance of precision electronic primarily by preventing ionizable contaminants
such as salt from reaching circuit nodes, where the material slumps around sharp edges. This can be a problem
especially in highly conversing atmosphere.
PFC – Norm EN 61000-3-2
Line Current Harmonic content
Typically, the input current waveform is not sinusoidal due to the periodical peak charging of the input capacitor.
In industrial environment, complying with EN 61000-3-2 is only necessary under special conditions. Complying
to this standard can have some technical drawbacks, such as lower efficiency as well as some commercial
aspects such as higher purchasing costs. Frequently, the user does not profit from fulfilling this standard,
therefore, it is important to know whether it is mandatory to meet this standard for a specific application.
14