Schurter EC12 Iec appliance inlet c20 with filter, line switch 2-pole Datasheet

EC12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
IEC Appliance Inlet C20 with Filter, Line Switch 2-pole
C20
Approvals and Compliances
70° C
Description
- Panel Mount :
Screw-on mounting from front side
- 3 Functions :
Appliance Inlet Protection class I , Line Switch 2-pole , Line filter in
standard and medical version
- Quick connect terminals 6.3 x 0.8 mm
Characteristics
-
All single elements are already wired
Line switch non-illuminated
With EMC-shield
Ideal for application with high transient loads
Suitable for use in equipment according to IEC/UL 60950
Suitable for use in medical equipment according to IEC/UL 60601-1
Other versions on request
- Line switch, illuminated
- Line switch with other rocker marking
- Variant with notch for V-Lock mating Cordsets
References
Alternative: version without line filter EC11
Alternative: Standard version
Weblinks
pdf datasheet, html-datasheet, General Product Information, DistributorStock-Check, Accessories, Detailed request for product
Newly available variants corresponding to V-Lock mating cordset. The connector is equipped with a notch intended for use with the latching cordset.
The cord latching system prevents against accidental removal of the cordset.
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temperature
Climatic Category
IP-Protection
Protection Class
Terminal
Panel Thickness S
Material: Housing
12 - 16 A @ Ta 40 °C / 250 VAC; 50 Hz
12 - 20 A @ Ta 40 °C / 125/250 VAC;
60 Hz
standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-25 °C to 85 °C
appliance inlet/-outlet
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
Quick connect terminals 6.3 x 0.8 mm
Screw: max 8 mm
Mounting screw torque max 0.5 Nm
Thermoplastic, black, UL 94V-0
MTBF
Line Switch
Line Filter
C20 acc. to IEC 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 16 A,
Protection Class I
Rocker switch 2-pole, non-illuminated,
acc. to IEC 61058-1
Technical Details
Standard and Medical Version, IEC
60939, UL 1283, CSA C22.2 no. 8
Technical Details
> 1'700'000 h acc. to MIL-HB-217 F
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
EMC Products
1
EC12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Approvals
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: EC12
Approval Logo
Certificates
Certification Body
Description
VDE Approvals
VDE
Certificate Number: 40001522
UL Approvals
UL
UL File Number: E72928
Design
Standard
Description
Designed according to
IEC 60320-1
Appliance couplers for household and similar general purposes
Designed according to
IEC 60939
Passive filters for suppressing electromagnetic interference
Designed according to
IEC 61058-1
Switches for appliances. Part 1. General requirements
Designed according to
UL 498
Standard for Attachment Plugs and Receptacles
Designed according to
UL 1283
Electromagnetic interference filters
Designed according to
CSA C22.2 no. 42
General Use Receptacles, Attachment Plugs, and Similar Wiring Devices
Designed according to
CSA C22.2 no. 8
Electromagnetic interference (EMI) filters
Design
Standard
Description
Designed for applications acc.
IEC/UL 60950
IEC 60950-1 includes the basic requirements for the safety of information
technologyequipment.
Designed for applications acc.
IEC 60601-1
Medical electrical equipment - Part 1: General requirements for basic
safety and essential performance
Details
Initiator
Description
CE declaration of conformity
SCHURTER AG
The CE marking declares that the product complies with the applicable
requirements laid down in the harmonisation of Community legislation on
its affixing in accordance with EU Regulation 765/2008.
RoHS
SCHURTER AG
EU Directive RoHS 2011/65/EU
China RoHS
SCHURTER AG
The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March
2007. It is similar to the EU directive RoHS.
REACH
SCHURTER AG
On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as
"REACH") entered into force.
SCHURTER AG
V-Lock system are based on a matching plug-dose combination. The
connector is equipped with a notch intended for use with the latching
cordset. The cord latching system prevents against accidental removal of
the cordset.
SCHURTER AG
Suitable for use in medical equipment according to IEC/UL 60601-1
Product standards
Product standards that are referenced
Organization
Application standards
Application standards where the product can be used
Organization
Compliances
The product complies with following Guide Lines
Identification
Medical Equipment
2
EMC Products
EC12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Dimension [mm]
31.1
37
2.8
32.9
3.6
0.8
32.2
R
48 ±0.10
R
12.55
57 ±0.10
47.05
23.85
46.2
12.2
10.9
4.
7
R6
5.5
.5
R
4.55 ±0.05
68
57
23.85
3.
55
±0
.0
5
05
3.
8
R 2.
S
3.3
6.4
9.5
33.9 ±0.10
59.5
5.3
Technical Data of Filter-Components
Rated Current
[A]
Filter-Type
Inductances L [mH]
Capacitance
CX [nF]
Capacitance
CY [nF]
R [MΩ]
12
Standard Version
2 x 0.8
100
2.2
1
16
Standard Version
2 x 0.6
100
2.2
1
20
Standard Version
2 x 0.3
100
2.2
1
12
Medical Version (M5)
2 x 0.8
100
-
1
16
Medical Version (M5)
2 x 0.6
100
-
1
20
Medical Version (M5)
2 x 0.3
100
-
1
Diagrams
Standard version
Medical version (M5)
L
L’
L1
1)
PE
Cx
Cy
R
L2
Cy
N
1) Line
2) Load
L
2)
PE’
N’
L’
L1
1)
PE
Cx
2)
PE’
R
L2
N’
N
1) Line
2) Load
Attenuation Loss
- - - - 50Ω differential mode _____ 50Ω common mode
Standard version
12 A
16 A
20 A
EMC Products
3
EC12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Medical version (M5)
12 A
16 A
20 A
All Variants
Rated Current [A]
Filter-Type
Internally wired
Line Switch
12
Standard Version
l
2-pole
12
Standard Version
l
2-pole
V-Lock
Order Number
EC12.3101.001
l
█
EC12.3101.001.21
16
Standard Version
l
2-pole
EC12.2101.001
█
20
Standard Version
l
2-pole
EC12.1101.001
█
12
Standard Version
2-pole
EC12.3101.002
16
Standard Version
2-pole
EC12.2101.002
20
Standard Version
2-pole
EC12.1101.002
12
Medical Version (M5)
l
2-pole
EC12.3201.001
16
Medical Version (M5)
l
2-pole
16
Medical Version (M5)
l
2-pole
20
Medical Version (M5)
l
2-pole
EC12.1201.001
12
Medical Version (M5)
2-pole
EC12.3201.002
16
Medical Version (M5)
2-pole
EC12.2201.002
20
Medical Version (M5)
2-pole
EC12.1201.002
EC12.2201.001
l
EC12.2201.001.21
█ Most Popular.
Availability for all products can be searched real-time:https://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
Packaging unit
20 Pcs
Accessories
Description
Wire Harness
Wire harness for SCHURTER products
Assorted Covers
Rear Cover
0859.0108
4
EMC Products
EC12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Cord retaining kits
Cord retaining strain relief
Flat head, H
4700.0008
Mating Outlets/Connectors
Category / Description
Connector Overview complete
IEC Connector C19, Rewireable, Straight
4795
IEC Connector C19, Rewireable, Angled
4790
IEC Connector C19, Rewireable, Straight
0104U
Connector further types to EC12
Mating Outlets/Connectors shuttered
Power Cord Overview complete
Overview Power Cord with IEC Appliance Connector C19, V-Lock, straight
VAC19KS
02.12.2017
Power Cord further types to EC12
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
EMC Products
5
Similar pages