TDK JWS300-48 Single output industrial power supply Datasheet

JWS Series
Single Output Industrial Power Supplies
Features
u 5 Year Warranty
u Power factor Corrected
u Approved to VDE0160 Machinery Directive
u Universal Input (85 - 265VAC)
u Level B EMI
Key Market Segments & Applications
u Factory Automation Process Control, NC-Machining, Automotive,
Packaging Equipment, Materials Handling,
Chemical Processing, Robots
u Test & Measurement Burn-in & Test, Automated Test,
Instrumentation, Measurement, Detection
Not recommended for new designs - see HWS series
Specifications
Model
Input Voltage range
Inrush Current (100 / 200VAC)
Power Factor
Temperature Coefficient
Overcurrent Protection
Overvoltage Protection
Hold Up Time (Typ)
Leakage Current (max)
Remote Sense
Remote On / Off
AC Power Fail
Parallel Connection
Operating Temp. (open frame)
Operating Temp. (with cover)
Storage Temperature
Operating Humidity
Storage Humidity
Cooling
Withstand Voltage
(1)
(1)
Isolation Resistance
Vibration (non operating)
Shock
Safety Agency Approvals
Conducted & Radiated EMI
Recommended EMI Filter
Weight (Typ)
Size (WxHxD)
Warranty
JWS50
A
V
ms
mA
g
mm
-
JWS75
JWS100
JWS150
JWS300
JWS600
85 - 265VAC (47 - 63Hz) or 120 - 330VDC
14 / 28
25 / 50
20 / 40
Meets EN61000-3-2
<0.02%/°C
>105%
Yes
20
0.75
No
Yes
Specify as Option /R
Standard
Not Available
Standard
Not Available
Avail. JWS300 & 600 only
-10ºC~+60ºC, derate linearly to 60% load from 50ºC~60ºC
-10ºC~+50ºC, derate linearly to 60% load from 40ºC~50ºC (JWS50-150)
-10ºC~+65ºC, derate linearly to 55% load from 50ºC~65ºC (JWS300-600)
-30 to +85ºC
30 - 90% RH
10 - 90% RH
10 - 95% RH
JWS50 - JWS150 Convection, JWS300 & JWS600 Internal fan
Input to Ground 2kVAC (20mA), Input to Output 3kVAC (20mA),
Output to Ground 500VAC (100mA) for 1 min.
>100M at 25ºC & 70%RH, Output to Ground 500VDC
10 - 55Hz (1 minute sweep), 19.6m/s2 constant X, Y, Z 1 hour
< 196.1 m/s2
UL60950-1, CSA C22.2 No. 60950-1, EN60950-1, VDE0160, CE Mark, Built to meet DENTORI
EN55011 / EN55022-B, FCC Class B, VCCI-B
MAW1202-22
MAW1203-22
MB1210
MB1216
350
450
650
850
1900
3000
See side 2
Five Years
(1) Non condensing
1-800-526-2324 • www.us.tdk-lambda.com/lp/
11
Disclaimer: us.tdk-lambda.com/lp/legal.htm
JWS Series
Model Derating*
Model
JWS300-2
JWS600-2
JWS50-3/A
JWS75-3/A
JWS100-3/A
JWS150-3/A
JWS300-3
JWS600-3
JWS50-5/A
JWS75-5/A
JWS100-5/A
JWS150-5/A
JWS300-5
JWS600-5
JWS100-6/A
JWS300-6
JWS600-6
JWS600-8
JWS50-9/A
JWS100-9/A
JWS300-9
JWS600-9
JWS50-12/A
JWS75-12/A
JWS100-12A
JWS150-12/A
JWS300-12
JWS600-12
JWS50-15/A
JWS75-15/A
JWS100-15/A
JWS150-15/A
JWS300-15
JWS600-15
JWS50-24/A
JWS75-24/A
JWS100-24/A
JWS150-24/A
JWS300-24
JWS600-24
JWS50-28/A
JWS100-28/A
JWS150-28/A
JWS300-28
JWS600-28
JWS50-48/A
JWS75-48/A
JWS100-48/A
JWS150-48/A
JWS300-48
JWS600-48
Voltage
Adjust
Range
2.0V
2.0V
3.3V
3.3V
3.3V
3.3V
3.3V
3.3V
5.0V
5.0V
5.0V
5.0V
5.0V
5.0V
6.0V
6.0V
6.0V
8.0V
9.0V
9.0V
9.0V
9.0V
12.0V
12.0V
12.0V
12.0V
12.0V
12.0V
15.0V
15.0V
15.0V
15.0V
15.0V
15.0V
24.0V
24.0V
24.0V
24.0V
24.0V
24.0V
28.0V
28.0V
28.0V
28.0V
28.0V
48.0V
48.0V
48.0V
48.0V
48.0V
48.0V
1.8 - 2.4
1.8 - 2.4
2.85 - 3.63
2.85 - 3.63
2.85 - 3.63
2.85 - 3.63
2.97 - 3.96
2.97 - 3.96
4.5 - 5.5
4.5 - 5.5
4.5 - 5.5
4.5 - 5.5
4.5 - 6.0
4.5 - 6.0
5.4 - 6.6
5.4 - 7.2
5.4 - 7.2
7.2 - 9.6
8.1 - 9.9
8.1 - 9.9
8.1 - 10.8
8.1 - 10.8
10.8 - 13.2
10.8 - 13.2
10.8 - 13.2
10.8 - 13.2
10.8 - 14.4
10.8 - 14.4
13.5 - 16.5
13.5 - 16.5
13.5 - 16.5
13.5 - 16.5
13.5 - 18.0
13.5 - 18.0
21.6 - 26.4
21.6 - 26.4
21.6 - 26.4
21.6 - 26.4
21.6 - 28.8
21.6 - 28.8
25.2 - 30.8
25.2 - 30.8
25.2 - 30.8
25.2 - 33.6
25.2 - 33.6
43.2 - 52.8
43.2 - 52.8
43.2 - 52.8
43.2 - 52.8
43.2 - 52.8
43.2 - 52.8
JWS Outline Drawing
Max
Load
Line
Ripple Eff.
Curr. Reg mV Reg mV Noise (typ)%
60
120
10
15
20
30
60
120
10
15
20
30
60
120
16.7
50
100
68
5.6
11.2
34
68
4.3
6.3
8.5
13
27
53
3.5
5
7
10
22
43
2.2
3.2
4.5
6.5
14
27
2
3.6
5.5
12
23
1.1
1.6
2.1
3.3
6.5
13
20
30
40
40
40
40
20
30
40
40
40
40
20
30
48
36
36
48
76
72
54
54
96
96
96
96
48
72
120
120
120
120
60
90
150
150
150
150
144
144
160
160
160
168
168
240
240
240
240
288
288
20
20
20
20
20
20
20
20
20
20
20
20
20
20
24
24
24
32
36
36
36
36
48
48
48
48
48
48
60
60
60
60
60
60
96
96
96
96
96
96
112
112
112
112
112
192
192
192
192
192
192
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
150
120
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
200
200
200
200
350
350
60
61
65
67
67
67
68
70
74
74
75
75
74
75
75
74
75
77
74
75
76
77
76
76
76
77
76
80
77
77
77
78
77
81
79
79
79
80
80
82
79
79
80
80
82
79
79
79
80
80
83
W
H
FRONT VIEW
H
(BOTH SIDES)
SIDE VIEW
W
MOUNTING SURFACE
D
See website for detailed drawing.
Dimensions Table
JWS50
JWS75
JWS100
JWS150
JWS300
JWS600
Height (H)
Width (W)
Depth (D)
1.45”
1.65”
1.97”
2.56”
3.62”
3.62”
3.35”
3.62”
3.62”
3.62”
4.72”
6.29”
6.25”
6.88”
7.40”
7.80”
7.48”
7.90”
Other Industrial Products
Options
HWS
LZSA
DLP/DSP/DPP
Suffix
Description
Blank
/A*
/B
/C
/R
Screw terminals, no cover (JWS50 - JWS150)
Screw terminals, cover (JWS50 - JWS150)
Molex terminals, no cover (JWS50 & JWS75)
Molex terminals, cover (JWS50 & JWS75)
Remote On / Off (JWS50 - JWS150)
Example
Note:
JWS50-5/RA
* Standard US stock item.
15W to 1800W Single output
500 to 1500W Single output
10 to 480W DIN Rail Mount
For Additional Information, please visit
us.tdk-lambda.com/lp/products/jws-series.htm
Not recommended for new designs - see HWS series
1-800-526-2324 • www.us.tdk-lambda.com/lp/
12