Advantech ADAM-6060 6-ch digital input and 6-ch relay modbus tcp module Datasheet

ADAM-6060
6-ch Digital Input and 6-ch Relay Modbus TCP Module
Main Features
NEW
ƒƒ 6-ch DI, 6-ch RL, Ethernet-based smart I/O
ƒƒ Remote monitoring and control with mobile devices
ƒƒ Group configuration capability for multiple module setup
ƒƒ Flexible user-defined Modbus address
ƒƒ Intelligent control ability by Peer-to-Peer and GCL function
ƒƒ Active I/O message by data stream or event trigger function
ƒƒ Multiple protocol support: Modbus TCP, TCP/IP, UDP, HTTP, DHCP
ƒƒ Web language support: XML, HTML 5, Java Script
Introduction
Peer-to-Peer
ADAM-6000 accomplishes the integration of automation and enterprise systems easily
through internet technology, so that users can avoid changing the entire architecture of
the control system and even remotely monitor the device status more flexibly. ADAM-6000
modules are empowered by peer-to-peer (P2P) and Graphic Condition Logic (GCL), and
can perform as standalone products for measurement, control and automation. Instead
of having additional controllers or programming, system configurations can be done in
an extremely short time with the easy-to-use and intuitive graphic utility.
Modules will actively update the input channel status to specific output channels. Without
dealing with the trouble of long distance wiring, users can define the mapping between
a pair of modules.
Features
Group Configuration Capability for Multiple Module Setup
Graphic Condition Logic
To aid configuration and save time, engineers can configure and upgrade the firmware of
multiple ADAM-6000s simultaneously.
Users can define the control logic rules through graphical configuration Utility, and
download defined logic rules to specific ADAM module. Then, it will execute the logic
rules automatically just like a standalone controller.
Remote Monitoring and Control with Smart Phone
Architecture
With support for HTML5, the ADAM-6000 can be monitored and controlled from any
browser on mobile devices whilst in the field and when the engineer is connected to
their network.
Advanced Security and High Reliability
ADAM-6000 Ethernet I/O modules have fast response time, and advanced security and
reliability. When communication is broken, the digital output module can generate predefined values to ensure safety.
Ethernet I/O Modules
All product specifications are subject to change without notice
More Information Click Here
Last updated : 13-Jul-2015
Remote I/O
ADAM-6060
Specifications
Protection
ƒƒ Power Reversal Protection
ƒƒ Isolation Protection
2,000 VDC
Digital Input
ƒƒ Channels
ƒƒ Dry Contact
ƒƒ
ƒƒ
ƒƒ
ƒƒ
ƒƒ
6
Logic level 0: close to GND
Logic level 1: open
Wet Contact
Logic level 0: 3 VDC
Logic level 1: 10 ~ 30 VDC
Supports 3 kHz Counter Input (32-bit + 1-bit overflow)
Keep/Discard Counter Value when Power-off
Supports 3 kHz Frequency Input
Supports Inverted DI Status
Relay Output (Form A)
ƒƒ Channels
ƒƒ Contact Rating
(Resistive)
ƒƒ Breakdown Voltage
ƒƒ Relay On Time
ƒƒ Relay Off Time
ƒƒ Total Switching Time
ƒƒ Insulation Resistance
ƒƒ Maximum Switching
Rate (at rated load)
ƒƒ Supports Pulse Output
6
120 VAC @ 0.5 A, 30 VDC @ 1 A
500 VAC (50/60 Hz)
7 ms
3 ms
10 ms
1 GΩ min. at 500 VDC
20 operations/minute
Environment
ƒƒ
ƒƒ
ƒƒ
ƒƒ
Operating Temperature
Storage Temperature
Operating Humidity
Storage Humidity
-20 ~ 70°C (-4 ~ 158°F)
-30 ~ 80°C (-22 ~ 176°F)
20 ~ 95% RH (non-condensing)
0 ~ 95% RH (non-condensing)
Software
ƒƒ .NET Class Library (SDK) Windows and Windows CE Class Library, VB and VC#
Sample Code for I/O Reading or Configuration and
Communication
ƒƒ Adam/Apax .NET Utility Network Setting, I/O Configuration, Data stream, P2P,
GCL Configuration
Pin Assignment
General
ƒƒ LAN
ƒƒ Power Consumption
ƒƒ Connectors
ƒƒ
10/100Base-T(X)
3 W (max) @ 24 VDC
RJ-45 (Ethernet),
Plug-in screw terminal block (I/O and power)
Watchdog
System (1.6 second) and
Communication (programmable)
Power Input
10 ~ 30 VDC
Dimensions (W x H x D) 70 x 122 x 27 mm
Enclosure
PC
Mounting
DIN 35 rail, stack, wall
Supports Peer-to-Peer, GCL
ƒƒ
ƒƒ
ƒƒ
ƒƒ
ƒƒ
ƒƒ Supports User Defined Modbus Address
ƒƒ Supports Modbus/TCP, TCP/IP, UDP, DHCP and HTTP Protocols
Ordering Information
ƒƒ ADAM-6060
6-ch DI and 6-ch Relay Modbus TCP Module
Accessories
ƒƒ PWR-242
ƒƒ PWR-243
ƒƒ PWR-244
DIN-rail Power Supply (2.1A Output Current)
Panel Mount Power Supply (3A Output Current)
Panel Mount Power Supply (4.2A Output Current)
Software
ƒƒ PCLS-ADAMVIEW32
ƒƒ PCLS-OPC/MTP30
ADAMView Data Acquisition Software
OPC Server for Modbus/TCP protocol
Dimensions
Unit: mm
Online Download www.advantech.com/products
Similar pages