Battery FTB155-12-GASSING Vrla rechargeable battery Datasheet

VRLA Rechargeable Battery
Measures
Technology
Values
Innovation
FTB155-12 (central gassing)
FEATURES
APPLICATION
Absorbent Glass Mat technology for efficient gas recombination
Front accessible terminal for ease of assembly
Carry handles for ease of installation
Strengthened rib design to maintain structural integrity
Flame-arrestor is installed to ensure safety
Battery design allows for 48VDC configuration in a standard 23'' rack
Telecom
UPS
Broadband
Electric Utility
Railroad Signal
Central Office
One-way self-resealing safety valve with gas collection system
for long life guarantee
SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
Terminals
Internal Resistance
Max. Discharge Current
Max. Charge Current
12 V
155Ah @ 8 hour rate F.V.(1.75V/cell)
55.4Kg(122.1lbs.)
I3 (M8 Female Thread)
(Fully Charged )
2.8m
800 A (5 sec.)
38.8 A
Charge:0oC~40oC(32oF~104oF)
Discharge:-20oC~50oC(-4oF~122oF)
Storage.:-20oC~40oC(-4oF~104oF)
Operating Temperature Range
Safety Valve
Container Material
Standard: ABS( UL 94-HB) FTB155-12
Optional: Flame Retardant ABS(UL 94-V0) FTB155-12FR
DIMENSION(mm/inch)
OUTER DIMENSIONS
M8 x 1.25
Terminal I 3
560.0 ± 2.0(22.05 ± 0.08)
277.0±2.0(10.91±0.08)
290.0±2.0(11.42±0.08)
125.0 ± 2.0(4.92 ± 0.08)
Container Height
290±2.0 (11.42±0.08)
Total Height
303±2.0 (11.93±0.08)
Constant power discharge characteristics at 25 oC/77 oF
1.90V
1.85V
1.80V
1.75V
1.70V
1.65V
1.60V
F.V.
(V/cell)
1.90V
1.85V
1.80V
1.75V
1.70V
1.65V
1.60V
[M8 BOLT]
Terminal Hardware Initial Torque: 10.0Nm ±5%
Unit: W
15 Min
30 Min
45 Min
1 Hr
2 Hr
3 Hr
4 Hr
5 Hr
8 Hr
10 Hr
20 Hr
2057
2436
2743
2953
3129
3241
3300
1767
1944
2065
2143
2190
2222
2244
1291
1411
1490
1540
1570
1591
1605
996.4
1109.2
1171.5
1200.0
1218.5
1235.0
1242.5
631.0
695.0
722.9
737.1
744.2
750.1
753.1
458.0
500.4
518.6
525.9
530.7
535.6
537.5
361.7
394.3
407.6
414.9
418.5
422.2
423.4
298.8
325.0
334.6
341.8
343.0
344.2
345.2
204.60
225.30
227.90
231.60
231.60
231.60
232.11
167.83
182.40
188.84
190.78
190.78
190.78
191.12
90.72
98.64
102.10
103.80
103.80
103.80
103.90
Constant current discharge characteristics at 25 oC/77 oF
Discharge
Time
2.0(0.08)
Width
125±2.0 (4.92±0.08)
M8x1.25
303.0±2.0(11.93±0.08)
560±2.0 (22.05±0.08)
Discharge
Time
TERMINAL TYPE
227.0(8.94)
57.1(2.25)
Length
F.V.
(V/cell)
IEC60896
BS6290/4
GB/T 19638
Eurobat guide
Opening pressure 10~35 kPa
Unit: A
15 Min
30 Min
45 Min
1 Hr
2 Hr
3 Hr
4 Hr
5 Hr
8 Hr
10 Hr
20 Hr
178.3
215.3
246.6
264.5
277.8
281.8
287.0
147.3
163.6
175.0
181.6
185.6
188.3
190.1
107.6
118.3
125.6
129.8
132.4
134.2
135.3
84.80
94.40
100.0
102.10
103.70
105.10
105.73
53.25
58.65
61.00
62.20
62.80
63.30
63.55
38.33
41.88
43.40
44.01
44.40
44.80
44.96
30.20
32.86
34.00
34.60
34.90
35.20
35.31
24.90
27.20
28.20
28.60
28.70
28.80
28.88
17.05
18.85
19.07
19.38
19.38
19.38
19.42
14.00
15.20
15.74
15.90
15.90
15.90
15.93
7.56
8.22
8.51
8.65
8.65
8.65
8.66
All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
For operation, please refer to the instruction from technical manual.
A/3 REV. Mar. 2014