Data Sheet August 2009 Compact Power Line CP2000AC54 Front-End Power Supply Input: 100-120/200-240 Vac; Outputs: ±54 Vdc at 2000W; 5 Vdc at 4W Features • Compact 1-RU form factor providing 20 W/in3 • Constant power from 52 – 58 Vdc • 2000W from nominal 200 – 240 Vac • 1200W from nominal 100 – 120 Vac • Output voltage programmable from 44V – 58 Vdc; • • Applications • 48Vdc distributed power architectures • Power over Ethernet • Routers/Switches • VoIP/Soft Switches • LAN/WAN/MAN applications • File servers • Indoor wireless • Telecommunications equipment • Enterprise Networks • SAN/NAS/iSCSI applications • Advanced workstations • • • • • • • • • • • output defaulted to 54V PMBus compliant dual I2C and RS485 serial bus communications Power factor correction (meets EN/IEC 61000-3-2 and EN 60555-2 requirements) Tested to IEEE802.3 Compliance, 2250 output*** isolation to chassis/signals for POE applications. (see ordering info) DC Output over-voltage and over-current protection AC Input over-voltage and under-voltage protection Over-temperature warning and protection Redundant, parallel operation with active load sharing and redundant +5V Aux power Remote ON/OFF Hot insertion/removal (hot plug) Four front panel LED indicators UL* Recognized to UL60950-1, CAN/ CSA† C22.2 No. 60950-1, and VDE‡ 0805-1 Licensed to IEC60950-1 CE mark meets 2006/95/EC directive§ Internal variable-speed fan control The CP2000AC54 Front-End Power Supplies in the Compact Power Line platform are specifically designed to operate as an integral part of a complete distributed power system. The high-density, front-toback airflow rectifier is designed for minimal space utilization and is highly expandable for future growth. It is provided with many features including PoE isolation, RS485 and dual-redundant I2C communications busses that allow it to be used in a broad range of applications. The flexible feature set makes this frontend power supply an excellent choice for applications requiring modular ac-to-dc bulk intermediate voltages, such as in distributed power. * † ‡ § UL is a registered trademark of Underwriters Laboratories, Inc. CSA is a registered trademark of Canadian Standards Association. VDE is a trademark of Verband Deutscher Elektrotechniker e.V. This product is intended for integration into end-user equipment. All the required procedures for CE marking of end-user equipment should be followed. (The CE mark is placed on selected products.) ** ISO is a registered trademark of the International Organization of Standards. *** For PoE applications, order the CP2000AC54PEZ, which is 100% factory hipot-tested per IEEE802.3. Data Sheet Compact Power Line CP2000AC54 Front-End Power Supply Specifications Input Parameter Min Typ Max Startup Input Voltage 1200W Operation 2000W Operation 85 175 150 Permitted Excursions 275 300 Surges 300 325 Input Frequency 47 120/200/240 200/240 275 275 175 63 13.3 11.2 11.8 9.9 Input Current Inrush Transient 25 Input Leakage Current 1.5 Power Factor 0.98 85 88 If started within low input line range. If started within high input line range. Will derate to 80% of full load; will shutdown below 150Vac. May not meet all requirements, but will maintain output regulation. May shut down but will not get damaged. Hz At 100 Vac At 120 Vac At 200 Vac At 240 Vac Apk Measured at 25°C for all line conditions; does not include X-Capacitors charging. mA Measured at 265Vac, 60Hz From 50% to 100% load. 90 93 % 15 Holdup Time Vac A 35 Notes The power supply automatically configures its operating mode based on the voltage level it reads on first turn ON. (This information is retained as long as internal bias is maintained.) 85 175 Operating Voltage Range 1200W Configuration 2000W Configuration 2000W Configuration Efficiency Units ms 20 At 100 Vac with Vout > 52V and Pout > 50%. At 230 Vac with Vout > 52V and Pout > 50%. Measurement starts at zero crossing of the ac voltage. Alarm issued via PFW signal going LO 5 ms prior to output voltages going out of limits. Measurements made at 65% full load and voltage allowed to decay to 49.5V. For loads below 1200W. Main Output Parameter Min Typ Maximum Output Power Output Voltage Setpoint Setpoint Accuracy Overall Regulation Output Voltage Margin Maximum Output Current Current Share Lineage Power Max Units 1200 2000 W At low-line input from 100-120Vac nominal. At high-line input from 200-240Vac nominal. Vdc Output floats with respect to frame ground. 54 Notes -1 +1 % -2 +2 % 44 58 Vdc Configured by hardware setting. 42 58 Vdc 2 Set either by I C or RS485 23 38.5 A 10 %FL Includes all variations due to specified load range, drift, and environmental conditions. At 1200W, 52V and 100-120Vac. At 2000W, 52V and 200-240Vac. Maintains tolerance to the average of all other rectifiers. Loads > 25%FL 2 Data Sheet Compact Power Line CP2000AC54 Front-End Power Supply Specifications (continued) Output (continued) Parameter Min Typ Max Units 250 500 2 mVrms mVpk-pk mVrms 5,000 µF 2 s ms s % Output Ripple RMS (5Hz to 20MHz) Peak-to-Peak (5Hz to 20MHz) Psophometric Noise External Bulk Load Capacitance 0 Turn-On Delay 1 Rise Time - Standard (PMBus) 2 -Telecom (RS-485) Overshoot 5 100 5 Load Step Response ∆I ∆V Response Time Overload Power Limit 3 Current Limit Inception Over-voltage Delayed Immediate Latchoff 50 2000 102 Auto-recoverable Monotonic Turn_On from 30% to 100% of Vnom above -5°C operation. Monotonic Turn_On from 60% to 100% of Vnom below -5°C operation. 108 W %FL 60 65 Vdc Vdc ∆I/∆t slew rate 1A/µs. Settling time to within regulation requirements. Down to -52Vdc Hiccup current limit. (FL = 38.5A) 200msec delayed shutdown to be implemented. Instantaneous shutdown above this point. Three restart attempts may be implemented within a one minute window prior to a latched shutdown Over-temperature Warning Shutdown Measured with 20MHz bandwidth under any condition of loading. Minimum load is 1A. External capacitance can be increased but the power supply will not meet its turn-ON rise time requirement. %FL Vdc ms 2.0 2 Notes 5 °C 20 Implemented prior to commencement of an OT shutdown Below the maximum rating of the device being protected °C Temperature hysteresis of approximately 10°C provided between shutdown and restart. 1. Below -5°C, the rise time is approximately 5 minutes to protect the bulk capacitors. 2. Complies with GR947 which calls for a minimum rise time proportional to output load. 3. Fold-down current limit is programmed as a default to permit system start-up when units are plugged in one at a time. Latchoff mode current limit can be activated via an I2c command. Auxiliary Output Parameter Min Typ Output Voltage Setpoint Output Current Overall Regulation Units 0.75 A -5 +10 % 100 mVpk-pk 50 Over-voltage Clamp 110 Notes Vdc 0.005 Ripple and Noise Over-current Limit Max 5 7 Vdc 175 %FL 20MHz bandwidth Physical Length (in./mm) 13.85 / 351.8 Width (in./mm) 4.00 / 101.6 Height (in./mm) 1.66 / 42.2 Weight (lb/kg) 4.6 / 2.1 Lineage Power 3 Data Sheet Compact Power Line CP2000AC54 Front-End Power Supply Specifications (continued) Environmental Parameter Min Ambient Temperature Operating Ambient Derating 2 Power Derating Storage Temperature Humidity Max Units Notes 45 1 2 °C °C %/°C %/°C Air inlet from sea level to 5,000 feet. Per 1,000 feet above 5,000 feet. Up to 55°C From 55 to 75 °C -40 85 °C 5 95 % -5 Typ 1 1 Relative humidity, non-condensing Shock and Vibration Operational Test Test Levels Drop and Tip Over Earthquake Rating IEC 68-2 IEC 721-3-2 IEC 68-2-31 4 Acoustic Noise 45 Harmonic Emissions Radiated Emissions Zone 4 Per Telcordia GR-63-CORE, all floors, when installed in CP Shelf. Noise is proportional to fan speed, load and ambient temperature. dBA Per EN/IEC61000-3-2 FCC and CISPR22 (EN55022) - Class B 3 Conducted Emissions - ac FCC and CISPR22 (EN55022) Class B Telcordia GR-1089-CORE - Class A Conducted Emissions - dc Telcordia GR-1089-CORE and CISPR22 (EN55022) - Class A ESD Error free per EN/IEC 61000-4-2 Level 4 (8 kV contact discharge, 15 kV air discharge). Radiated Immunity Error free per EN/IEC 61000-4-3 Level 3 (10 V/m). Electrical Fast Transient Burst Error free per EN/IEC 61000-4-4 Level 3 (2 kV, 5 kHz repetition rate) Lightning Surge Error Free Damage Free EN/IEC61000-4-5 Level 4 (4 kV common mode, 2 kV differential mode). ANSI C62.41 Level A3 (6 kV common and differential mode) Conducted Immunity Error free per EN/IEC 61000-4-6 Level 3 (10Vrms). Reliability (calculated) Isolation Input-Chassis/Signals Input - Output Output-Chassis/Signals Service Life 400,000 1500 3000 2250 10 Hours At ambient of 25°C at full load per Telcordia SR332, Reliability Prediction for Electronic Equipment, Method I Case III. Vrms Vrms Vdc Per EN60950-1. Consult factory for testing to this requirement Per IEEE802.3. Years 25°C ambient, full load excluding fans. 1. Designed to start at an ambient as low as -40°C, but may not meet operational limits until above -5°C. 2. Power derating shall consider only temperature variations at nominal line (100 – 120, 200 – 240Vrms). The unit may derate faster if the input line is below nominal. 3. Class B radiated emmissions compliance requires the addition of a ferrite bead to each power line cord at the shelf-end of the cable. See the figure below. 4. Radiated emissions compliance was met using a Lineage Power shelf. This shelf includes output common and differential mode capacitors that assist in meeting compliance. Lineage Power 4 Data Sheet Status and Control The rectifier provides three means for monitor/control: analog, PMBus compliant I2C, or RS485 for interfacing to Lineage Power controllers or battery plants. Details of analog controls are provided in this data sheet under Signal Definitions. Lineage Power will provide separate application notes on PMBus protocol for users to interface to the CPL rectifiers. Contact your local Lineage Power representative for details. Hot Plug When rapidly extracting and reinserting modules care should be taken to allow for discharging the internal bias supply so that a predictable restart could be achieved. The way to ensure that the circuit sufficiently discharges is to observe the spinning of the fans after an extraction. The unit should not be reinserted until the fans stop spinning. Compact Power Line CP2000AC54 Front-End Power Supply Module Present Signal: This signal has dual functionality. It can be used to alert the system when a module is inserted. Has a 500Ω resistor in series between this signal and Logic GRD. An external pull-up should not raise the voltage on the pin above 0.25Vdc. If raised the pin is raised to 5Vdc the write_protect feature of the EEPROM is enabled. Protocol Select: Establishes the communications mode of the power supply, between analog/I2C and RS485 modes. For RS485, connect 750 – 3.92kΩ pull-down resistor to 54_OUT(-DC). Enable: On/Off control when either PMBus communications or analog functions are utilized as configured by the Protocol pin. This pin must be pulled low to turn ON the main output of the power supply. The power supply will turn OFF if either the Enable or the ON/OFF pin is released. The Enable function does not work with the RS-485 protocol. This signal is referenced to Logic_GRD. All signals are referenced to Logic GRD unless otherwise noted. See the Signal Definitions Table at the end of this document for further description of all the signals. ON/OFF: This is a short pin utilized for hot-plug applications to ensure that the power supply turns OFF before the power pins are disengaged. It also ensures that the power supply turns ON only after the power pins have been engaged. Must be connected to 54_OUT (-DC). Input Signals Output Signals Control Definitions Margining: Setpoint of the rectifier can be changed via this input pin. Programming can be either a voltage source or a resistance divider. The margining pin is connected to 3.3Vdc via a 10kΩ resistor inside the rectifier. See graphs below. Alert #: PMBus interrupt signal. Fault: This signal goes LO for any failure that requires rectifier replacement. Some of these faults may be due to: • Fan failure • Over-temperature condition • Over-temperature shutdown • Over-voltage shutdown • Internal Rectifier Fault Power Capacity: A HI on this pin indicates rectifier configured for 2000W operation; a LO indicates rectifier configured for 1200W operation. An open circuit on this pin reverts the voltage level back to the original setting. Lineage Power 5 Data Sheet Compact Power Line CP2000AC54 Front-End Power Supply Alarm Table Power Supply LED State AC OK DC OK Service Fault Green Green Amber Red 1 1 0 0 Condition OK Thermal Alarm (5C before shutdown) Thermal Shutdown Defective Fan Blown AC Fuse in Unit No AC <15mS (single unit) AC Present but not within limits AC not present1 Boost Stage Failure Over Voltage Latched Shutdown Over Current Non-catastrophic Internal Failure2 1 Missing Module Monitoring Signals (Referenced to Logic_GRD) Module Fault OTW PFW Present HI HI HI LO 1 1 1 0 HI LO HI LO 1 1 1 0 Blinks 0 1 1 1 1 0 0 0 1 0 0 0 0 Blinks 1 1 0 0 0 0 0 0 0 0 0 1 1 1 0 0 0 1 1 0 1 LO LO LO HI HI HI LO LO HI LO LO HI HI HI HI HI HI HI HI HI LO LO LO LO3 LO LO LO LO LO HI LO LO LO LO LO LO LO LO LO LO HI 1 1 1 0 1 1 0 Blinks 0 0 0 Blinks HI HI HI HI HI HI LO HI HI LO LO LO Standby (remote) Service Request (PMBus mode) Communications Fault (RS485 mode) 1 This signal is correct if the rectifier is back biased from other rectifiers in the shelf . Any detectable fault condition that does not result in the power supply shutting down. For example, ORing FET failure, boost section out of regulation, etc. 3 Signal transition from HI to LO is output load dependent 2 Output Connector Mating Connector: AMP 1450572-1 A6 A1 Signal 6 A SCL_0 5 4 3 LOGIC_GRD P1 P7 Output Power 2 RS_485+ 1 MOD_PRES PFW B SCL_1 OTW Alert#_0 Alert#_1 RS_485- 8V_INT C SDA_0 Margin Enable Reset Ishare Protocol D SDA_1 Fault 5VA Power_Cap ON/OFF SHELF_ADDR P7 P6 Input Power P5 P4 P3 P2 P1 UNIT_ADDR 54_OUT 54_OUT (-DC) (+DC) Reserved EARTH LINE-2 LINE-1 (GND) (Neutral) (Line) Connector is viewed from the rear positioned inside the power supply. Signal pins columns 1 and 2 are referenced to 54_OUT (-DC). Signal pins columns 3 through 6 are referenced to Logic GRD. Last-to-make first-to-break pins. First-to-make last-to-break longest pin implemented in the mating connector. Lineage Power 6 Data Sheet Compact Power Line CP2000AC54 Front-End Power Supply Signal Definitions All hardware alarm signals (Fault, PFW, OTW, Power Capacity) are open drain FETs. These signals should be pulled HI to either 3.3V or 5V. Maximum sink current 5mA. An active LO signal (< 0.4Vdc). All signals are referenced to Logic GRD unless otherwise stated. Contact your Lineage Power representative for more details. Function Label Type Description Output Enable Enable Input If shorted to LOGIC_GRD, the rectifier output is enabled when using I2C mode of operation. May also be toggled to reset a latched OFF rectifier. Function not available in RS485 mode. Power Fail Warning PFW Output An open drain FET; normally HI, indicating output power is present. Changes to LO at least 5msec before the output voltage is lost. I2C Interrupt Alert#_0 Alert#_1 Output Interrupt signal via I2C lines indicating that service is requested from the host controller. This signal pin is pulled up to 3.3V via a 10kΩ resistor and switches to active LO when an interrupt occurs. Rectifier Fault Fault Output Indicates that an internal fault exists. An open drain FET; normally HI, changes to LO. Module Present MOD_PRES Output Short pin, see Status and Control description for further information on this signal. ON/OFF ON/OFF Input Short pin, connects last and breaks first; used to activate and deactivate output during hot-insertion and extraction, respectively. Ref: 54_OUT (-DC) Protocol select Protocol Input See Status and Control description for further information on this signal. Ref: 54_OUT (-DC). Margining Margin Input Allows changing of output voltage through an analog voltage input or via resistor divider. Over-Temperature Warning OTW Output An open drain FET; normally HI, changes to LO approximately 5°C prior to thermal shutdown. Power Capacity POWER_CAP Output An open drain FET; Used to indicate rectifier operation mode; HI indicates 2000W operation and LO indicates 1200W operation. Rectifier address Unit_addr Input Voltage level addressing of rectifiers within a single shelf. Ref: 54_OUT (-DC). Shelf Address Shelf_addr Input Voltage level addressing of rectifiers within multiple shelves. Ref: 54_OUT (-DC). Back bias 8V_INT _ Diode OR’ed 8Vdc drain; used to back bias microprocessors and DSP of failed rectifier from operating rectifiers. Ref: 54_OUT (-DC). Mux Reset Reset Input Resets the I2C lines to I2C line 0. Standby power 5VA Output 5V at 0.75A provided for external use by either adjacent power supplies or the using system. Current Share Ishare - A single wire interface between each of the power unit forces them to share the load current. Ref: 54_OUT (-DC). I2C Line 0 SCL_0, SDA_0 Input I2C line 0. I2C Line 1 SCL_1, SDA_1 Input I2C line 1. RS485 Line RS_485+ RS_485- RS485 line. Lineage Power Input 7 Data Sheet Compact Power Line CP2000AC54 Front-End Power Supply Front Panel LEDs I2C Mode Analog Mode RS485 Mode ON: Input ok Blinking: Input out of limits ON: Output ok Blinking: Overload ON: Over-temperature Warning ! ON: Over-temperature Warning Blinking: Service ON: Fault Dimensions ON: Over-temperature Warning ON: Fault Blinking: Not communicating 13.85 in. (351.8 mm) 4.00 in. (101.6 mm) Rear View 1.70 in. (43.2 mm) Top View Front View Ordering Information Item Description Comcode CP2000AC54PE Designed to IEEE802.3 POE compliance, RoHS 5/6 CC109120722 CP2000AC54PEZ Tested to IEEE802.3 POE compliance, RoHS 6/6 CC109139408 Asia-Pacific Headquarters Tel: +65 6593 7211 World Wide Headquarters Lineage Power LLC 601 Shiloh Road, Plano, TX 75074, USA +1-800-526-7819 (Outside U.S.A.: +1-972-284-2626) www.lineagepower.com e-mail: [email protected] Europe, Middle-East and Africa Headquarters Tel: +49 898 780 672 80 India Headquarters Tel: +91 80 2841 1633 Lineage Power reserves the right to make changes to the product(s) or information contained herein without notice. No liability is assumed as a result of their use or application. No rights under any patent accompany the sale of any such product(s) or information. © 2009 Lineage Power LLC, (Mesquite, Texas) All International Rights Reserved. Revision : GGS-August 2009 Lineage Power Page 8